      變電站電氣二次系統(tǒng)驗(yàn)收規(guī)范(小編整理)

      時(shí)間:2019-05-14 06:14:20下載本文作者:會(huì)員上傳
      簡介:寫寫幫文庫小編為你整理了多篇相關(guān)的《變電站電氣二次系統(tǒng)驗(yàn)收規(guī)范》,但愿對你工作學(xué)習(xí)有幫助,當(dāng)然你在寫寫幫文庫還可以找到更多《變電站電氣二次系統(tǒng)驗(yàn)收規(guī)范》。

      第一篇:變電站電氣二次系統(tǒng)驗(yàn)收規(guī)范

      750kV變電站電氣二次系統(tǒng)

      驗(yàn)收規(guī)范

      酒泉超高壓輸變電公司

      2010年3月

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      目 次

      前 言......................................................................II 1 范圍.......................................................................1 2 規(guī)范性引用文件..............................................................1 3 驗(yàn)收準(zhǔn)備...................................................................2 3.1 根據(jù)驗(yàn)收規(guī)范編制二次系統(tǒng)現(xiàn)場驗(yàn)收細(xì)則......................................2 3.2 檢驗(yàn)儀器、儀表、工器具及材料..............................................2 3.3 人員分工..................................................................2 4 驗(yàn)收項(xiàng)目及內(nèi)容..............................................................2 4.1 通用驗(yàn)收項(xiàng)目..............................................................2 4.2 線路保護(hù)驗(yàn)收項(xiàng)目..........................................................5 4.3 變壓器保護(hù)驗(yàn)收項(xiàng)目.......................................................10 4.4 母線保護(hù)驗(yàn)收項(xiàng)目.........................................................13 4.5 故障錄波器驗(yàn)收項(xiàng)目.......................................................15 5 自動(dòng)化系統(tǒng)、故障信息管理系統(tǒng)驗(yàn)收項(xiàng)目.......................................16 5.1 故障信息管理系統(tǒng)檢查.....................................................16 5.2 測控裝置驗(yàn)收項(xiàng)目.........................................................16 5.3 網(wǎng)絡(luò)交換機(jī)驗(yàn)收項(xiàng)目.......................................................17 5.4 監(jiān)控系統(tǒng)軟件功能驗(yàn)收項(xiàng)目.................................................17 5.5 監(jiān)控電源系統(tǒng).............................................................20 5.6 全站對時(shí)系統(tǒng)驗(yàn)收項(xiàng)目.....................................................21 6 站用直流系統(tǒng)驗(yàn)收...........................................................21 6.1 直流屏接線...............................................................21 6.2 硬母線連接...............................................................21 6.3 直流系統(tǒng)反措驗(yàn)收.........................................................21 6.4 直流系統(tǒng)微機(jī)監(jiān)控器.......................................................22 6.5 直流充電裝置.............................................................23 6.6 絕緣檢測裝置.............................................................23 6.7 電壓調(diào)節(jié)裝置.............................................................23 6.8 事故照明裝置.............................................................23 附件(范例)750KV線路保護(hù)及二次回路驗(yàn)收細(xì)則.................................23

      I 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      前 言

      為了加強(qiáng)750kV變電站繼電保護(hù)及二次系統(tǒng)的管理,使驗(yàn)收內(nèi)容、步驟、項(xiàng)目、方法、驗(yàn)收行為規(guī)范化,實(shí)現(xiàn)電氣二次設(shè)備投產(chǎn)驗(yàn)收的規(guī)范化、標(biāo)準(zhǔn)化,確保750kV變電站電氣二次設(shè)備零缺陷投運(yùn)。依據(jù)電力行業(yè)、國家電網(wǎng)公司、西北電網(wǎng)有限公司及甘肅省電力公司相關(guān)標(biāo)準(zhǔn)、規(guī)程、導(dǎo)則、規(guī)范,特制定此驗(yàn)收規(guī)范。

      本驗(yàn)收規(guī)范由酒泉超高壓輸變電公司進(jìn)行編制并負(fù)責(zé)解釋。本規(guī)范審核人:楊德志

      張宏軍

      本規(guī)范審核人:劉 罡

      張東良

      司軍章

      范曉峰 李玉明

      蘇軍虎康 鵬

      張致海

      本規(guī)范主要起草人:任

      石永安

      劉培民

      佳 王建剛

      海世杰

      張國林

      II

      茹秋實(shí) 高寶龍

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范 范圍

      本規(guī)范根據(jù)相關(guān)規(guī)程和反措規(guī)定了750kV變電站繼電保護(hù)、安全自動(dòng)裝置及其二次回路的驗(yàn)收內(nèi)容、項(xiàng)目和要求。

      本規(guī)范適用于750kV變電站繼電保護(hù)及二次系統(tǒng)的現(xiàn)場驗(yàn)收工作。其它電壓等級變電站繼電保護(hù)、安全自動(dòng)裝置及其二次回路的驗(yàn)收參照本規(guī)范執(zhí)行。規(guī)范性引用文件

      本《750kV變電站二次系統(tǒng)驗(yàn)收規(guī)范》是根據(jù)以下規(guī)范標(biāo)準(zhǔn)、規(guī)程以及對繼電保護(hù)專業(yè)的相關(guān)管理要求編寫:

      ? Q/GDW 157-2007《750kv電力設(shè)備交接試驗(yàn)標(biāo)準(zhǔn)》

      ? Q/GDW 239-2009《1000kv繼電保護(hù)和電網(wǎng)安全自動(dòng)裝置檢驗(yàn)規(guī)程》 ? 《西北750KV輸變電工程竣工預(yù)驗(yàn)收及分系統(tǒng)調(diào)試指導(dǎo)意見》西北電網(wǎng)生技2009年48號(hào)文

      ? GB 7261-2001《繼電器及繼電保護(hù)裝置基本試驗(yàn)方法》 ? GB50150-91《電氣裝置安裝工程電氣設(shè)備交接試驗(yàn)標(biāo)準(zhǔn)》 ? Q/GDW120-2005《750KV變電所電氣設(shè)備施工質(zhì)量檢驗(yàn)及評定規(guī)程》 ? DL/T 995-2006《繼電保護(hù)和電網(wǎng)安全自動(dòng)裝置檢驗(yàn)規(guī)程》 ? GB/T 14285-2006《繼電保護(hù)和安全自動(dòng)裝置技術(shù)規(guī)程》 ? DL/T 587-2007《微機(jī)繼電保護(hù)裝置運(yùn)行管理規(guī)程》 ? Q/GDW 161-2007《線路保護(hù)及輔助裝置標(biāo)準(zhǔn)化設(shè)計(jì)規(guī)范》

      ? Q/GDW 175-2008《變壓器、高壓并聯(lián)電抗器和母線保護(hù)及輔助裝置標(biāo)準(zhǔn)化設(shè)計(jì)規(guī)范》

      ? GB50171-92《電氣裝置安裝工程盤、柜及二次回路結(jié)線施工及驗(yàn)收規(guī)范》 ? 電氣裝置安裝工程電纜線路施工及驗(yàn)收規(guī)范

      ? 《國家電網(wǎng)公司十八項(xiàng)電網(wǎng)重大反事故措施》繼電保護(hù)重點(diǎn)實(shí)施要求 ? 《國家電網(wǎng)公司繼電保護(hù)全過程管理規(guī)定》 ? 電力工程直流系統(tǒng)設(shè)計(jì)技術(shù)規(guī)程(DL/T5044-2000)? 國家電網(wǎng)公司 《直流電源系統(tǒng)技術(shù)標(biāo)準(zhǔn)》 ? 國家電網(wǎng)公司 《直流電源系統(tǒng)運(yùn)行規(guī)范》 ? 國家電網(wǎng)公司 《直流電源系統(tǒng)技術(shù)監(jiān)督規(guī)定》 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      ? 國家電網(wǎng)公司 《預(yù)防直流電源系統(tǒng)事故措施》 3 驗(yàn)收準(zhǔn)備

      3.1 根據(jù)驗(yàn)收規(guī)范編制二次系統(tǒng)現(xiàn)場驗(yàn)收細(xì)則 3.2 檢驗(yàn)儀器、儀表、工器具及材料

      3.2.1 繼電保護(hù)班組應(yīng)配置必備的檢驗(yàn)用儀器儀表,應(yīng)能滿足繼電保護(hù)檢驗(yàn)需要,確保檢驗(yàn)質(zhì)量。

      3.2.2 定值檢驗(yàn)應(yīng)使用不低于0.5級的儀器、儀表;測控裝置應(yīng)使用不低于0.2級的儀器、儀表檢驗(yàn)。

      3.2.3 裝置檢驗(yàn)所用儀器、儀表應(yīng)經(jīng)過檢驗(yàn)合格。3.2.4 微機(jī)型繼電保護(hù)試驗(yàn)裝置應(yīng)經(jīng)過檢驗(yàn)合格。3.2.5 可根據(jù)現(xiàn)場實(shí)際需要準(zhǔn)備工器具及材料。3.3 人員分工

      3.3.1驗(yàn)收工作開始前,應(yīng)按照間隔分組安排驗(yàn)收人員。

      3.3.2對于端子箱、保護(hù)通道接口柜等驗(yàn)收交接面,應(yīng)在驗(yàn)收前明確各自驗(yàn)收范圍。3.3.2后臺(tái)四遙試驗(yàn)應(yīng)由運(yùn)行和保護(hù)人員共同驗(yàn)收,按照驗(yàn)收細(xì)則做好記錄。驗(yàn)收項(xiàng)目及內(nèi)容

      4.1 通用驗(yàn)收項(xiàng)目 4.1.1 資料驗(yàn)收 4.1.1.1 施工圖紙:

      所有施工圖齊全、正確,竣工圖紙及其電子版圖紙要求設(shè)計(jì)單位在工程竣工投產(chǎn)后三個(gè)月內(nèi)移交。

      4.1.1.2 調(diào)試報(bào)告及安裝記錄:

      檢查所有調(diào)試報(bào)告及安裝記錄是否齊全、正確。4.1.1.3 專用工具及備品備件:

      檢查專用工具及備品備件是否齊全,要求與裝箱記錄單上所記載的一致。4.1.1.4 廠家說明書、技術(shù)資料、組屏圖紙等的技術(shù)文件:

      檢查說明書、組屏圖紙等技術(shù)文件齊全,要求與裝箱記錄單上所記載一致,圖紙資料及技術(shù)說明書要求至少一式四份。4.1.2 外觀檢查 4.1.2.1 反措驗(yàn)收

      1)交、直流的二次線不得共用電纜;動(dòng)力線、電熱線等強(qiáng)電路不得與二次弱電回路共用電纜;各組電流和電壓線及其中性線應(yīng)分別置于同一電纜;雙重化配置的保護(hù)的電流回路、電壓回路、直流電源、雙跳閘繞組的控制回路等,兩套系統(tǒng)不應(yīng)合用一根多芯電纜。

      2)二次回路電纜不得多次過渡、轉(zhuǎn)接;變壓器、電抗器非電量保護(hù)由其就地端子箱引至保護(hù)室的二次回路不宜存在過渡或轉(zhuǎn)接。

      3)高頻同軸電纜屏蔽層應(yīng)在兩端分別接地,并沿高頻同軸電纜上方敷設(shè)截面不小于2100mm、兩端接地的銅導(dǎo)體。結(jié)合濾波器高頻電纜側(cè)的接地點(diǎn)應(yīng)與耦合電容的一次接地點(diǎn)分開,結(jié)合濾波器高頻電纜側(cè)的接地點(diǎn)應(yīng)在距一次接地點(diǎn)3~5m處與地網(wǎng)連接。

      24)所有保護(hù)屏地面下宜用截面不小于100mm的接地銅排直接連接構(gòu)成等電位接地母線,2接地母線應(yīng)首尾可靠連接形成環(huán)網(wǎng),并用截面不小于50 mm、不少于4根銅排與廠站的接地

      2網(wǎng)直接連接;屏柜裝置上的接地端子應(yīng)用截面不小于4 mm的多股銅線和接地銅排相連,接地銅排應(yīng)用截面不小于50 mm的銅排與地面下的等電位接地母線相連,所有二次電纜和高

      2頻電纜屏蔽層應(yīng)使用截面不小于4 mm 多股銅質(zhì)軟導(dǎo)線可靠連接到等電位接地網(wǎng)的銅排上。

      5)所有電流互感器、電壓互感器的二次繞組必須有且僅有一個(gè)接地點(diǎn);有電氣直接連 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      接的電流互感器的二次回路,其接地點(diǎn)應(yīng)在控制室一點(diǎn)接地;經(jīng)控制室零相小母線(N600)連通的幾組電壓互感器的二次繞組必須在控制室一點(diǎn)接地。各電壓互感器的中性線不得接有可能斷開的開關(guān)和接觸器,來自電壓互感器二次的4根開關(guān)場引入線和電壓互感器開口三角回路的2根開關(guān)場引入線必須分開且應(yīng)使用各自獨(dú)立的電纜。

      6)保護(hù)電源和控制電源應(yīng)該分別由獨(dú)立的的空氣開關(guān)控制;對于雙重化配置的保護(hù)裝置:兩套保護(hù)的直流電源應(yīng)相互獨(dú)立,分別由專用的直流熔斷器從不同的直流母線段供電,有兩組跳閘線圈的斷路器,各跳閘回路應(yīng)分別由專用的直流熔斷器從不同的直流母線段供電,保護(hù)電源應(yīng)與其對應(yīng)的操作回路的電源一一對應(yīng);對于由一套保護(hù)裝置控制的多組斷路器,要求每一斷路器的操作回路應(yīng)相互獨(dú)立,分別由專用的直流熔斷器供電;信號(hào)回路由專用熔斷器供電,不得與其它回路混用。

      7)每一套獨(dú)立的保護(hù)裝置應(yīng)有直流電源消失報(bào)警的回路。8)上、下級熔斷器之間的容量配合必須有選擇性。4.1.2.2其它部分驗(yàn)收

      4.1.2.2.1二次回路接線的檢查:

      1)電纜固定應(yīng)牢固,裝置及與之相連接的二次回路的接線應(yīng)該整齊美觀、牢固可靠,電纜牌及回路編號(hào)標(biāo)示清晰、正確、無褪色。

      2)跳(合)閘引出端子與正、負(fù)電源端子應(yīng)適當(dāng)隔開且有明顯標(biāo)識(shí)。

      5)所有二次電纜都應(yīng)采用阻燃鎧裝屏蔽電纜,屏蔽層在開關(guān)場、控制室同時(shí)接地,嚴(yán)禁采用電纜芯兩端接地的方法作為抗干擾措施,多股軟線必須經(jīng)壓接線頭接入端子。

      26)電流回路電纜芯截面≥2.5mm;控制電纜或絕緣導(dǎo)線芯截面、強(qiáng)電回路電纜芯截面222≥1.5mm;弱電回路電纜芯截面≥0.5mm;屏柜內(nèi)導(dǎo)線的芯線截面應(yīng)不小于1.0mm。

      7)所有端子排的接線穩(wěn)固,不同截面的電纜芯不許接入同一端子,同一端子接線不宜超過兩根。

      4.1.2.2.2 屏柜、端子箱內(nèi)端子排布置的檢查:

      1)屏柜上的端子排按照“功能分區(qū)、端子分段”的原則設(shè)置,端子排按段獨(dú)立編號(hào),每段應(yīng)預(yù)留備用端子,端子排名稱運(yùn)行編號(hào)應(yīng)正確,符合設(shè)計(jì)要求。

      2)端子排的安裝位置應(yīng)便于更換和接線,離地高度應(yīng)大于350mm。

      3)正、負(fù)電源之間以及正電源與跳合閘回路之間應(yīng)以一個(gè)空端子隔開。4.1.2.2.3 保護(hù)屏上設(shè)備及其編號(hào)、標(biāo)示的檢查:

      1)保護(hù)屏上的所有設(shè)備(壓板、按鈕、把手等)應(yīng)采用雙重編號(hào),內(nèi)容標(biāo)示明確規(guī)范,并應(yīng)與圖紙標(biāo)示內(nèi)容相符,滿足運(yùn)行部門要求。

      2)轉(zhuǎn)換開關(guān)、按鈕、連接片、切換片等安裝中心線離地面不宜低于300mm,便于巡視、操作、檢修。

      3)壓板不宜超過5排,每排設(shè)置9個(gè)壓板,不足一排時(shí)用備用壓板補(bǔ)齊,宜將備用壓板連片拆除;壓板在屏柜體正面自上而下,從左至右依次排列;保護(hù)跳合閘出口壓板及與失靈回路相關(guān)壓板采用紅色,壓板底座及其它壓板采用淺駝色,標(biāo)簽應(yīng)設(shè)置在壓板下放。4.1.2.2.4 保護(hù)屏屏頂小母線的檢查: 1)保護(hù)屏屏頂小母線的截面應(yīng)不小于6.0mm,兩屏之間的小母線應(yīng)用截面不小于6.0mm的多股軟線連接。小母線兩側(cè)應(yīng)有標(biāo)明其代號(hào)或名稱的絕緣標(biāo)志牌,字跡清晰、不宜脫色。

      2)屏頂小母線裸露部分與未經(jīng)絕緣的金屬體之間的電氣間隙不得小于12mm。4.1.2.2.5 保護(hù)屏、戶外端子箱(包括開關(guān)、互感器端子箱)、端子盒的檢查:

      1)端子箱應(yīng)有升高座,孔洞等密封良好,端子箱、端子盒應(yīng)有防雨、防潮、防塵措施,其外殼與主地網(wǎng)焊接。

      2)屏、柜、箱的接地應(yīng)牢固良好。可開啟的門,應(yīng)以裸銅軟線與接地的金屬構(gòu)架可靠 3 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      連接。

      3)安裝結(jié)束后,屏、柜、箱的預(yù)留孔洞及電纜管口應(yīng)封堵好。4.1.2.2.6電纜溝電纜敷設(shè)檢查:

      電纜溝電纜敷設(shè)應(yīng)整齊,標(biāo)志清晰,一二次電纜應(yīng)分層布置,二次電纜置于一次電纜下層。

      4.1.2.2.7 其他部分檢查: 1)安裝通信設(shè)備的小室,在屏地面下宜用截面不小于100mm 的接地銅排直接連接構(gòu)成等電位接地母線,接地母線應(yīng)首尾可靠連接形成環(huán)網(wǎng),并和保護(hù)室保護(hù)屏下敷設(shè)的接地銅2 排用不小于100mm銅線直接連接。

      2)傳輸保護(hù)信息的接口裝置至距保護(hù)裝置、光纖配線架大于50m時(shí)(特殊設(shè)備應(yīng)以廠家技術(shù)要求為準(zhǔn))應(yīng)采用光纜。

      3)分相電流差動(dòng)保護(hù)應(yīng)采用同一路由收發(fā)的通道。4.1.3 TV、TA及其相關(guān)二次回路檢查 4.1.3.1反措驗(yàn)收

      1)雙重化配置兩套保護(hù)的電流回路應(yīng)分別取自電流互感器互相獨(dú)立的繞組,二次繞組的分配應(yīng)避免主保護(hù)出現(xiàn)死區(qū)。

      2)雙重化配置的兩套保護(hù)之間不應(yīng)有任何電氣聯(lián)系,兩套主保護(hù)的電壓回路宜分別接入電壓互感器的不同二次繞組。4.1.3.2其它部分驗(yàn)收

      4.1.3.2.1 電流互感器及其相關(guān)回路檢查:

      1)檢查、試驗(yàn)互感器所有繞組的極性、變比、準(zhǔn)確級應(yīng)滿足對應(yīng)保護(hù)、測量和計(jì)量的要求,電流互感器的變化與定值通知單應(yīng)一致。

      2)利用飽和電流、勵(lì)磁電流和電流互感器二次回路阻抗近似校驗(yàn)各繞組是否滿足10%誤差要求。

      3)互感器各次繞組的連接方式、極性應(yīng)滿足設(shè)計(jì)和裝置實(shí)際要求。

      4)對電流互感器二次繞組接線進(jìn)行檢查:可采用二次通流的方法(在電流互感器接線盒處分別短接各繞組、保護(hù)屏處通入電流方法或在保護(hù)屏處分別短接各繞組、電流互感器接線盒處分別通入二次電流的方法)檢驗(yàn)接入保護(hù)、盤表、計(jì)量、錄波、母差等的二次繞組的連接組別的正確性和回路完整性。

      5)所有電流二次回路必須經(jīng)帶負(fù)荷測試來檢查回路是否正確和完整。6)備用電流回路的短接必須可靠,防止電流互感器二次回路開路。4.1.3.2.2 電壓互感器及其相關(guān)回路檢查:

      1)檢查、試驗(yàn)互感器各繞組的極性、變比、準(zhǔn)確級應(yīng)滿足對應(yīng)保護(hù)、測量和計(jì)量的要求,電壓互感器的變化與定值通知單應(yīng)一致。

      2)互感器各次繞組的連接方式、極性應(yīng)滿足設(shè)計(jì)和裝置實(shí)際要求。

      3)對電壓互感器二次繞組接線進(jìn)行檢查:要求對電壓互感器二次繞組進(jìn)行通電壓試驗(yàn)(可采用在電壓互感器接線盒處將接線打開并分別通入二次電壓的方法)檢驗(yàn)接入保護(hù)、盤表、計(jì)量等二次繞組的連接組別的正確性和回路的完整性。

      4)測量電壓回路自電壓互感器引出端子至屏柜電壓母線的每相電阻,并計(jì)算電壓互感器在額定容量下的壓降,其值不應(yīng)超過額定電壓的3%。

      5)所有電壓二次回路均必須經(jīng)帶負(fù)荷測試來檢查回路是否正確和完整。

      6)對于帶切換的電壓回路,實(shí)際分合1G、2G,觀察操作箱切換繼電器動(dòng)作情況及指示燈指示情況是否正確。

      6)試驗(yàn)端子等備用接線端子驗(yàn)收,防止電壓互感器二次回路造成短路。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      4.1.4 變電站內(nèi)部交、直流回路絕緣檢查

      1)在保護(hù)屏的端子排處將所有外部引入的回路及電纜全部斷開,分別將電流、電壓、直流控制信號(hào)回路的所有端子各自連接在一起,用1000V搖表測量絕緣電阻,各回路對地、各回路之間的阻值均應(yīng)大于10MΩ。

      2)檢查跳、合閘回路間及對地絕緣,阻值均應(yīng)大于10MΩ。4.1.5 公共回路檢查

      4.1.5.1 公共信號(hào)回路檢查:

      檢查電壓并列柜、公用測控柜接入的所有遙信量在監(jiān)控后臺(tái)數(shù)據(jù)庫定義的正確性。4.1.5.2 各間隔電氣閉鎖回路檢查:

      檢查閉鎖邏輯是否合理,是否符合變電站“五防”閉鎖技術(shù)要求,回路接線是否正確。4.2 線路保護(hù)驗(yàn)收項(xiàng)目

      4.2.1 線路保護(hù)二次回路檢查 4.2.1.1反措驗(yàn)收

      1)斷路器操作電源與保護(hù)電源分開且獨(dú)立:兩組操作電源分別引自不同直流母線段,兩套主保護(hù)裝置直流電源分別取自不同直流母線段且與其對應(yīng)的跳閘線圈操作電源一一對應(yīng),其他輔助保護(hù)電源、不同斷路器的操作電源應(yīng)有專用直流電源空氣開關(guān)供電。

      2)保護(hù)裝置至輔助保護(hù)、母差、失靈等重要起動(dòng)和跳閘回路均應(yīng)使用各自獨(dú)立的電纜。3)斷路器和隔離開關(guān)的輔助觸點(diǎn)、切換回路與不同保護(hù)配合的相關(guān)回路應(yīng)遵循相互獨(dú)立的原則。

      4)檢查防跳回路正確,斷路器防跳保護(hù)應(yīng)采用斷路器本體配置的保護(hù)。斷路器三相不一致保護(hù)應(yīng)采用斷路器本體配置的保護(hù) 4.2.1.2其它部分驗(yàn)收

      4.2.1.2.1 電源之間寄生回路的檢查:

      試驗(yàn)前所有保護(hù)、操作電源均投入,斷開某路電源,分別測試由其供電的直流端子對地電壓,其結(jié)果均為0V且不含交流分量。4.2.1.2.2 斷路器防跳躍檢查:

      斷路器處于分閘狀態(tài),短接跳閘接點(diǎn),手動(dòng)合斷路器并保持合后狀態(tài)一段時(shí)間,此過程中斷路器應(yīng)只合分一次。

      4.2.1.2.3 斷路器操作回路壓力閉鎖情況檢查:

      斷路器應(yīng)具備SF6壓力、空氣壓力/油壓降低閉鎖重合閘、閉鎖操作等功能。當(dāng)壓力降低至閉鎖重合閘時(shí),保護(hù)裝置應(yīng)顯示“壓力閉鎖重合閘”;當(dāng)壓力降低至閉鎖操作時(shí),無法分合開關(guān)。上述幾種情況信號(hào)系統(tǒng)應(yīng)發(fā)相應(yīng)聲光信號(hào)。4.2.2 線路保護(hù)裝置檢查

      4.2.2.1 線路保護(hù)裝置參數(shù)核對:

      1)保護(hù)裝置基本參數(shù)核對(定值區(qū)、通信地址、被保護(hù)設(shè)備名稱)符合要求。2)保護(hù)裝置交流插件參數(shù)與一次設(shè)備參數(shù)一致。

      3)保護(hù)裝置直流插件參數(shù)與本站直流額定電壓一致。4)保護(hù)裝置版本和校驗(yàn)碼在規(guī)定的有效版本范圍之內(nèi)。5)光纖通道兩側(cè)通道一一對應(yīng),收發(fā)路由一致。6)打印機(jī)參數(shù)與裝置打印參數(shù)設(shè)置。7)檢查GPS對時(shí)是否正確。4.2.2.2 收發(fā)信機(jī)參數(shù)和設(shè)置核對:

      1)收發(fā)信機(jī)通道、頻率兩側(cè)應(yīng)一致,設(shè)置頻率與本裝置晶振頻率、線濾一致。2)收發(fā)信機(jī)和保護(hù)配合參數(shù)核對設(shè)置正確。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      4.2.2.3 線路保護(hù)裝置電源的檢查:

      1)檢查輸出電壓及其穩(wěn)定性在裝置技術(shù)參數(shù)正常范圍以內(nèi)。

      2)檢查正、負(fù)極對地電壓;檢查工作地與保安地是否相連(要求不連);檢查逆變輸出電源對地有電壓。

      4.2.2.4 線路保護(hù)裝置的數(shù)模轉(zhuǎn)換精度的檢查:

      裝置電壓、電流、相位角度測量采樣應(yīng)在允許范圍之內(nèi)。4.2.2.5 線路保護(hù)裝置開關(guān)量輸入的檢查:

      1)檢查軟連接片和硬連接片的邏輯關(guān)系。2)保護(hù)壓板投退的開入符合設(shè)計(jì)要求。

      3)開關(guān)位置的開入:對單開關(guān)分別使A、B、C相位置動(dòng)作檢查其正確性;對3/2接線要求用把手切換、投退相應(yīng)壓板配合使相應(yīng)斷路器位置動(dòng)作來驗(yàn)證接線的正確性。

      4)其他開入量。

      4.2.2.6 線路保護(hù)裝置定值校驗(yàn):

      1)1.05倍及0.95倍定值校驗(yàn)。2)操作輸入和固化定值。

      4.2.2.7 線路保護(hù)保護(hù)功能檢驗(yàn)(主要檢查正、反向區(qū)內(nèi)、外故障動(dòng)作邏輯):

      1)縱聯(lián)保護(hù)。

      2)工頻變化量阻抗保護(hù)。

      3)接地距離Ⅰ、Ⅱ、Ⅲ段保護(hù)。4)相間距離Ⅰ、Ⅱ、Ⅲ段保護(hù)。

      5)零序Ⅰ、Ⅱ、Ⅲ、Ⅳ段、零序反時(shí)限保護(hù)。6)電壓互感器斷線過流保護(hù)。7)弱饋功能。

      8)電壓互感器斷線閉鎖功能。9)振蕩閉鎖功能。

      10)重合閘后加速功能。11)手合后加速功能。4.2.3 失靈遠(yuǎn)跳判別檢查

      4.2.3.1 失靈遠(yuǎn)跳判別裝置參數(shù)核對:

      1)裝置基本參數(shù)核對(定值區(qū)、通信地址、被保護(hù)設(shè)備名稱)符合要求。2)裝置交流插件參數(shù)與一次設(shè)備參數(shù)一致。3)裝置直流插件參數(shù)與本站直流額定電壓一致。4)裝置版本和校驗(yàn)碼在規(guī)定的有效版本范圍之內(nèi)。5)光纖通道兩側(cè)應(yīng)一一對應(yīng)。

      6)打印機(jī)參數(shù)與裝置打印參數(shù)設(shè)置。7)檢查GPS對時(shí)是否正確。4.2.3.2 失靈遠(yuǎn)跳裝置電源的檢查

      1)檢查輸出電壓及其穩(wěn)定性在裝置技術(shù)參數(shù)正常范圍以內(nèi)。

      2)檢查正、負(fù)極對地電壓;檢查工作地與保安地是否相連(要求不連);檢查逆變輸出電源對地有電壓。

      4.2.3.3 失靈遠(yuǎn)跳裝置的數(shù)模轉(zhuǎn)換精度的檢查:

      裝置電壓、電流、相位角度測量采樣應(yīng)在允許范圍之內(nèi)。4.2.3.4 失靈遠(yuǎn)跳裝置開關(guān)量輸入的檢查:

      1)檢查軟連接片和硬連接片的邏輯關(guān)系。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      2)保護(hù)壓板投退的開入符合設(shè)計(jì)要求。

      3)開關(guān)位置的開入:對單開關(guān)分別使A、B、C相位置動(dòng)作檢查其正確性。4)其他開入量。

      4.2.3.5 失靈遠(yuǎn)跳裝置的定值校驗(yàn):

      1)1.05倍及0.95倍定值校驗(yàn)。2)操作輸入和固化定值。

      4.2.3.6 失靈遠(yuǎn)跳裝置保護(hù)功能檢驗(yàn):

      1)過電壓保護(hù)。2)低功率保護(hù)。3)過流保護(hù)。

      4)收信直跳(分別試驗(yàn)二取一、二取二方式)。4.2.4 線路間隔的斷路器輔助保護(hù)檢查

      4.2.4.1 線路間隔的斷路器輔助保護(hù)基本參數(shù)核對:

      1)保護(hù)裝置基本參數(shù)核對(定值區(qū)、通信地址、被保護(hù)設(shè)備名稱)符合要求。2)保護(hù)裝置交流插件參數(shù)與一次設(shè)備參數(shù)一致。

      3)保護(hù)裝置直流插件參數(shù)與本站直流額定電壓一致。4)保護(hù)裝置版本和校驗(yàn)碼在規(guī)定的有效版本范圍之內(nèi)。5)打印機(jī)參數(shù)與裝置打印參數(shù)設(shè)置。6)檢查GPS對時(shí)是否正確。

      7)操作箱跳、合閘回路與斷路器跳合閘線圈參數(shù)核對(電流啟動(dòng)或保持的數(shù)值小于等于跳合閘回路電流數(shù)值的50%)。

      8)操作箱出口繼電器動(dòng)作值核對涉及直接跳閘的重要回路繼電器動(dòng)作電壓在額定直流電源電壓的55%-70%,動(dòng)作功率不低于5W)。

      4.2.4.2 線路間隔的斷路器輔助保護(hù)電源的檢查:

      1)檢查輸出電壓及其穩(wěn)定性在裝置技術(shù)參數(shù)正常范圍以內(nèi)。

      2)檢查正、負(fù)極對地電壓;檢查工作地與保安地是否相連(要求不連);檢查逆變輸出電源對地有電壓。

      4.2.4.3 線路間隔的斷路器輔助保護(hù)裝置數(shù)模轉(zhuǎn)換精度的檢查:

      裝置電壓、電流、相位角度測量采樣應(yīng)在允許范圍之內(nèi)。4.2.4.4 線路間隔的斷路器輔助保護(hù)開關(guān)量輸入的檢查:

      1)檢查軟連接片和硬連接片的邏輯關(guān)系。2)保護(hù)壓板投退的開入符合設(shè)計(jì)要求。

      3)開關(guān)位置的開入:對單開關(guān)分別使A、B、C相位置動(dòng)作檢查其正確性;對3/2接線要求用把手切換或投退相應(yīng)壓板配合相應(yīng)斷路器位置動(dòng)作來驗(yàn)證接線的正確性。

      4)其他開入量。

      4.2.4.5 線路間隔的斷路器輔助保護(hù)定值校驗(yàn):

      1)1.05倍及0.95倍定值校驗(yàn)。2)操作輸入和固化定值。

      4.2.4.6 線路間隔的斷路器輔助保護(hù)功能、回路檢驗(yàn):

      1)重合閘。

      2)斷路器失靈保護(hù)。3)死區(qū)保護(hù)。4)過流保護(hù)。

      5)失靈啟動(dòng)及出口回路。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      6)三相不一致啟動(dòng)回路。7)重合閘啟動(dòng)回路。8)閉鎖重合閘回路。

      9)先合、后合相互閉鎖回路。

      4.2.5 線路間隔的相關(guān)告警信號(hào)檢查:

      1)開關(guān)本體告警信號(hào)(包括氣體壓力、液壓和彈簧未儲(chǔ)能、三相不一致、電機(jī)就地操作電源消失等,要求檢查聲光信號(hào)正確)。

      2)保護(hù)異常告警信號(hào)(包括保護(hù)動(dòng)作、重合閘動(dòng)作、保護(hù)裝置告警信號(hào)等,要求檢查聲光信號(hào)正確)。

      3)回路異常告警信號(hào)(包括控制回路斷線、電流互感器和電壓互感器回路斷線、切換同時(shí)動(dòng)、直流電源消失、操作電源消失等,要求檢查聲光信號(hào)正確)。

      4)跳、合閘監(jiān)視回路。

      5)高頻或光纖通道告警信號(hào)(要求檢查聲光信號(hào)正確)。6)其他信號(hào)(要求檢查聲光信號(hào)正確)。4.2.6 線路保護(hù)錄波信號(hào)檢查:

      1)保護(hù)動(dòng)作或跳閘接點(diǎn)作為啟動(dòng)量。2)重合閘動(dòng)作接點(diǎn)作為啟動(dòng)量。

      3)收信輸入(閉鎖式縱聯(lián)保護(hù)要錄“收信輸入”接點(diǎn),允許式要求發(fā)信也錄波)。4)高頻模擬量。

      4.2.7 通道傳輸裝置及回路檢查

      4.2.7.1 高頻保護(hù)專用收發(fā)信機(jī)檢查:

      1)收發(fā)信機(jī)發(fā)信振蕩頻率。2)收發(fā)信機(jī)發(fā)信輸出功率。

      3)收發(fā)信機(jī)的輸出阻抗及輸入阻抗的測定。4)檢驗(yàn)通道監(jiān)測回路工作應(yīng)正常。5)收信機(jī)收信靈敏啟動(dòng)性能的檢測。6)兩側(cè)收發(fā)信機(jī)通道交換邏輯正確。7)測量通道的傳輸衰耗、工作衰耗。8)3dB告警檢查。

      9)檢查收信電平,設(shè)置衰耗值,檢查收信裕度(15~16dB)。4.2.7.2 失靈遠(yuǎn)跳專用收發(fā)信機(jī)檢查:

      1)收發(fā)信機(jī)發(fā)信振蕩頻率。2)收發(fā)信機(jī)發(fā)信輸出功率。

      3)收發(fā)信機(jī)的輸出阻抗及輸入阻抗的測定。4)檢驗(yàn)通道監(jiān)測回路工作應(yīng)正常。5)收信機(jī)收信靈敏啟動(dòng)性能的檢測。

      6)模擬本側(cè)失靈出口,檢查對側(cè)是否收到遠(yuǎn)跳命令。7)模擬對側(cè)失靈出口,檢查本側(cè)是否收到遠(yuǎn)跳命令。4.2.7.3 光纖通道光電轉(zhuǎn)換裝置檢查:

      1)本側(cè)電路自環(huán)檢查保護(hù)裝置誤碼及延時(shí)和光電轉(zhuǎn)換裝置通道指示狀況。2)本側(cè)光路自環(huán)檢查保護(hù)裝置誤碼及延時(shí)和光電轉(zhuǎn)換裝置通道指示狀況。

      3)恢復(fù)至通道正常狀態(tài)檢查保護(hù)裝置誤碼及延時(shí)和光電轉(zhuǎn)換裝置通道指示狀況。4)光電轉(zhuǎn)換裝置屏內(nèi)尾纖排列整齊,標(biāo)志清晰,固定可靠。4.2.7.4 光纖通道調(diào)試:

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      1)光纖通道可以采用自環(huán)的方式檢查光纖通道是否完好。

      -62)傳輸延時(shí)及誤碼率檢查(光纖通道的誤碼碼率和傳輸時(shí)間進(jìn)行檢查,誤碼率小于10,兩側(cè)的傳輸延時(shí)應(yīng)接近相等)。

      3)傳輸設(shè)備發(fā)信光功率,收信靈敏度及通道裕度(對于專用光纖通道應(yīng)對其發(fā)信電平,收信靈敏啟動(dòng)電平進(jìn)行測試并保證通道的裕度滿足要求)。

      4)通道遠(yuǎn)跳信號(hào)試驗(yàn)(分別模擬兩側(cè)失靈出口,檢查對側(cè)是否收到遠(yuǎn)跳命令)。4.2.7.4 高頻保護(hù)聯(lián)調(diào):

      1)模擬區(qū)內(nèi)故障(對于閉鎖式,高頻保護(hù)短時(shí)發(fā)信5ms后停信;對于允許式,高頻保護(hù)發(fā)允許跳閘信號(hào),對側(cè)高頻保護(hù)在收到允許跳閘信號(hào)動(dòng)作跳閘。要求對側(cè)高頻保護(hù)投入,斷路器在斷開位置)。

      2)模擬正方向區(qū)外故障(對于閉鎖式,高頻保護(hù)短時(shí)發(fā)信5ms后停信,但由于本側(cè)收到對側(cè)閉鎖信號(hào),本側(cè)高頻保護(hù)不動(dòng)作;對于允許式高頻保護(hù)不向?qū)?cè)發(fā)允許跳閘信號(hào),本側(cè)高頻保護(hù)不動(dòng)作跳閘。要求對側(cè)高頻保護(hù)投入,斷路器在合閘位置)。

      3)模擬反方向故障(對于閉鎖式,高頻保護(hù)發(fā)信后不停信,由于兩側(cè)收到閉鎖信號(hào),兩側(cè)高頻保護(hù)不動(dòng)作;對于允許式,高頻保護(hù)不向?qū)?cè)發(fā)允許跳閘信號(hào),本側(cè)高頻保護(hù)不動(dòng)作跳閘。要求對側(cè)高頻保護(hù)投入,斷路器在合閘位置)。4.2.7.5 光纖保護(hù)聯(lián)調(diào):

      1)通入三相電流(兩側(cè)分別加入三相電流,檢查本側(cè)和對側(cè)顯示誤差值應(yīng)不于5%)。2)區(qū)內(nèi)各種短路故障,保護(hù)動(dòng)作。

      3)對于傳輸遠(yuǎn)傳命令的通道,兩側(cè)分別模擬失靈動(dòng)作,對側(cè)檢查是否正確收到命令。4.2.8 線路保護(hù)整組試驗(yàn)(帶模擬開關(guān)):

      1)單相瞬時(shí)接地故障(重合閘置于單重位置,同一被保護(hù)設(shè)備的各套保護(hù)裝置的電流回路臨時(shí)串聯(lián),相應(yīng)電壓回路并聯(lián),分別模擬A、B、C相單相故障,檢查各裝置在同一故障時(shí)的動(dòng)作情況、跳閘回路和重合閘回路的正確性,要求保護(hù)與模擬開關(guān)動(dòng)作情況一致)。

      2)單相永久性接地故障(重合閘置于單重位置,同一被保護(hù)設(shè)備的各套保護(hù)裝置的電流回路臨時(shí)串聯(lián),相應(yīng)電壓回路并聯(lián),任意模擬一次單相永久性接地故障,以檢查各裝置在同一故障時(shí)的動(dòng)作情況、跳閘回路和重合閘回路的正確性、保護(hù)后加速功能正確性。對于3/2接線的開關(guān),重合短延時(shí)開關(guān)單跳單合后三相跳閘,重合長延時(shí)開關(guān)單跳后三相跳閘)。

      3)兩相接地瞬時(shí)故障(重合閘置于單重位置,同一被保護(hù)設(shè)備的各套保護(hù)裝置的電流回路臨時(shí)串聯(lián),相應(yīng)電壓回路并聯(lián),分別模擬兩相故障,檢查各裝置在同一故障時(shí)的動(dòng)作情況、跳閘回路和重合閘回路的正確性、保護(hù)三跳回路正確性)。

      4)永跳TJR和三跳TJQ動(dòng)作(對有三跳停信的保護(hù)需要檢查保護(hù)三跳停信)。

      5)重合閘啟動(dòng)回路(用兩套保護(hù)分別帶輔助保護(hù)和開關(guān),檢查保護(hù)出口啟動(dòng)重合閘回路是否正確)。

      6)閉鎖重合閘回路(用手跳和永跳、單重方式時(shí)三跳閉鎖重合閘等檢查重合閘回路是否正確;模擬斷路器壓力降低鎖重合閘,檢查其回路正確性)。

      7)失靈啟動(dòng)及出口回路(包括保護(hù)啟動(dòng)失靈觸點(diǎn)、失靈電流判別元件及TJR啟動(dòng)失靈觸點(diǎn)檢查。用兩套保護(hù)分別帶輔助保護(hù),模擬A、B、C和三相保護(hù)動(dòng)作相應(yīng)開關(guān)失靈,用導(dǎo)通法在失靈保護(hù)屏測啟動(dòng)失靈的正確性,以按相檢驗(yàn)失靈回路中每個(gè)觸點(diǎn)、壓板接線的正確性)。

      8)失靈、母差出口跳本間隔檢查(在確保失靈、母差保護(hù)屏內(nèi)回路正確的前提下,打開本間隔開關(guān)回路接線,用短接方法檢查失靈、母差出口跳本開關(guān)回路是否正確。應(yīng)閉鎖重合閘,開放對側(cè)縱聯(lián)保護(hù))。

      9)失靈遠(yuǎn)跳試驗(yàn)(分別模擬兩側(cè)失靈出口,檢查對側(cè)是否收到遠(yuǎn)跳命令就地判別滿足 9 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      動(dòng)作)。

      4.2.9 線路保護(hù)傳動(dòng)試驗(yàn):

      1)單相瞬時(shí)接地故障(重合閘置于單重位置,分別模擬A、B、C相單相故障,檢查跳閘回路和重合閘回路的正確性,保護(hù)與開關(guān)動(dòng)作一致,信號(hào)指示正確)。

      2)單相永久性接地故障(重合閘置于單重位置,模擬B相單相永久性接地故障,檢查跳閘回路和重合閘回路的正確性,保護(hù)與開關(guān)動(dòng)作一致,信號(hào)指示正確)。

      3)兩相接地瞬時(shí)故障(重合閘置于單重位置,模擬A、C兩相接地瞬時(shí)故障,保護(hù)與開關(guān)動(dòng)作一致,信號(hào)指示正確)。

      4)斷路器三相不一致保護(hù)檢查(分別模擬斷路器A、B、C三相不一致,保護(hù)開入和動(dòng)作出口回路的正確,信號(hào)指示正確)。

      5)斷路器防跳檢查(斷路器處于分閘狀態(tài),短接跳閘接點(diǎn),手動(dòng)合斷路器并保持合后狀態(tài)一段時(shí)間,此過程斷路器應(yīng)只合分一次)。4.2.10 線路保護(hù)裝置投運(yùn)前檢查:

      1)打印定值與定值單核對(與定值單要求一致)。

      2)恢復(fù)所有打開的接線(電流回路應(yīng)進(jìn)行緊固,所有臨時(shí)線拆除,接線恢復(fù)到運(yùn)行狀態(tài))。

      3)壓板以及把手等(測試保護(hù)壓板上下樁頭的電位,檢查是否存在回路接點(diǎn)粘合情況, 把手等恢復(fù)至運(yùn)行狀態(tài))。

      4)打印機(jī)(打印機(jī)指示正確,打印紙放置良好,打印機(jī)防塵蓋放置正確)。4.2.11 線路保護(hù)帶負(fù)荷后的向量測試、檢查:

      1)裝置顯示及信號(hào)指示(裝置面板顯示模擬量符合系統(tǒng)潮流大小及方向,開關(guān)量正確,信號(hào)指示無異常)。

      2)測量電壓、電流的幅值及相位關(guān)系,對于電流回路的中性線應(yīng)進(jìn)行幅測量(測量中性線不平衡電流,要求與當(dāng)時(shí)系統(tǒng)潮流大小及方向核對)。

      3)線路光纖差動(dòng)保護(hù)差流的檢查(檢查其差流大小是否正常,并記錄存檔)。

      4)高頻通道信號(hào)復(fù)測(測收信和發(fā)信電平,觀察是否與供電前一致,若不一致,應(yīng)進(jìn)行通道裕量和3dB衰耗告警調(diào)試)。4.3 變壓器保護(hù)驗(yàn)收項(xiàng)目

      4.3.1 變壓器保護(hù)相關(guān)二次回路檢查: 4.3.1.1反措驗(yàn)收

      1)保護(hù)電源配置情況:兩套完整、獨(dú)立的電氣量保護(hù)和一套非電氣量保護(hù)應(yīng)使用各自獨(dú)立的電源回路,兩套電氣量保護(hù)的直流電源分別取自不同直流母線段,兩套主保護(hù)和兩組操作電源應(yīng)一一對應(yīng)。

      2)非電量保護(hù)應(yīng)同時(shí)作用于斷路器的兩個(gè)跳閘線圈。4.3.1.2其它部分驗(yàn)收

      1)變壓器本體回路檢查:

      有載、本體重瓦斯投跳閘;輕瓦斯、壓力釋放、繞組溫度高、油溫高、冷控失電等根據(jù)變壓器運(yùn)行要求投信號(hào)或跳閘;

      2)各側(cè)斷路器防跳躍檢查: 各側(cè)斷路器分別處于分閘狀態(tài),短接跳閘接點(diǎn),手動(dòng)合斷路器并保持合后狀態(tài)一段時(shí)間,此過程斷路器應(yīng)只合分一次。

      3)操作回路閉鎖情況檢查(斷器SF6壓力、空氣壓力/油壓降低和彈簧未儲(chǔ)能禁止重合閘、閉鎖操作等功能,其中閉鎖重合閘回路可以和保護(hù)裝置開入量驗(yàn)收同步進(jìn)行。由開關(guān)專業(yè)人員配合,實(shí)際模擬空氣壓力/油壓降低,當(dāng)壓力降低至閉鎖重合閘時(shí),保護(hù)顯示”閉鎖 10 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      重合閘開入量”變位;當(dāng)壓力降低至閉鎖操作時(shí),無法分合開關(guān)。上述幾種情況信號(hào)系統(tǒng)應(yīng)發(fā)相應(yīng)聲光信號(hào))。

      4)非電量保護(hù)不啟動(dòng)斷路器失靈保護(hù) 4.3.2 變壓器保護(hù)裝置檢查

      4.3.2.1 變壓器保護(hù)裝置參數(shù)核對:

      1)保護(hù)裝置基本參數(shù)核對(定值區(qū)、通信地址、被保護(hù)設(shè)備名稱)符合要求。2)保護(hù)裝置交流插件參數(shù)與一次設(shè)備參數(shù)一致。

      3)保護(hù)裝置直流插件參數(shù)與本站直流額定電壓一致。4)保護(hù)裝置版本和校驗(yàn)碼在規(guī)定的有效版本范圍之內(nèi)。5)打印機(jī)參數(shù)與裝置打印參數(shù)設(shè)置。6)檢查GPS對時(shí)是否正確。

      4.3.2.2 變壓器保護(hù)裝置電源的檢查:

      1)檢查輸出電壓及其穩(wěn)定性在裝置技術(shù)參數(shù)正常范圍以內(nèi)

      2)檢查正、負(fù)對地是否有電壓;檢查工作地與保安地是否相連(要求不連);檢查逆變輸出電源對地是否有電壓。

      4.3.2.3 變壓器保護(hù)裝置的數(shù)模轉(zhuǎn)換精度的檢查:

      裝置電壓、電流、相位角度測量采樣應(yīng)在允許范圍之內(nèi)。4.3.2.4 變壓器保護(hù)裝置開關(guān)量輸入的檢查:

      1)檢查軟連接片和硬連接片的邏輯關(guān)系。2)保護(hù)壓板投退的開入符合設(shè)計(jì)要求。

      3)各側(cè)電壓閉鎖的投入:變位情況應(yīng)與裝置及設(shè)計(jì)要求一致。

      4)非電量保護(hù):非電量保護(hù)作用于跳閘的啟動(dòng)功率應(yīng)大于5W,動(dòng)作電壓在額定電源電壓的55%-70%范圍內(nèi),動(dòng)作時(shí)間為10ms-35ms。4.3.2.5 變壓器保護(hù)定值校驗(yàn):

      1)1.05倍及0.95倍定值校驗(yàn)。2)操作輸入和固化定值。4.3.2.6 變壓器保護(hù)功能檢驗(yàn):

      1)差動(dòng)保護(hù)。

      2)高壓側(cè)相間方向復(fù)壓過流。3)中壓側(cè)相間方向復(fù)壓過流。4)低壓側(cè)相間方向復(fù)壓過流。5)零序過流保護(hù)。6)間隙零流保護(hù)。7)零壓保護(hù)。8)本體保護(hù)。

      4.3.3 主變間隔的斷路器輔助保護(hù)及操作箱檢查

      4.3.3.1 主變間隔的斷路器輔助保護(hù)及操作箱基本參數(shù)核對:

      1)保護(hù)裝置基本參數(shù)核對(定值區(qū)、通信地址、被保護(hù)設(shè)備名稱)符合要求。2)保護(hù)裝置交流插件參數(shù)與一次設(shè)備參數(shù)一致。

      3)保護(hù)裝置直流插件參數(shù)與本站直流額定電壓一致。4)保護(hù)裝置版本和校驗(yàn)碼在規(guī)定的有效版本范圍之內(nèi)。5)打印機(jī)參數(shù)與裝置打印參數(shù)設(shè)置。6)檢查GPS對時(shí)是否正確。

      7)操作箱跳、合閘回路與斷路器跳合閘線圈參數(shù)核對:電流啟動(dòng)或保持的數(shù)值小于等 11 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      于跳合閘回路電流數(shù)值的50%。

      8)操作箱出口繼電器動(dòng)作值核對:涉及直接跳閘的重要回路繼電器動(dòng)作電壓在額定直流電源電壓的55%-70%,動(dòng)作功率不低于5W。

      4.3.3.2 主變間隔的斷路器輔助保護(hù)及操作箱電源的檢查:

      1)檢查輸出電壓及其穩(wěn)定性在裝置技術(shù)參數(shù)正常范圍以內(nèi)。

      2)檢查正、負(fù)對地是否有電壓;檢查工作地與保安地是否相連(要求不連);檢查逆變輸出電源對地是否有電壓。

      4.3.3.3 主變間隔相關(guān)斷路器的輔助保護(hù)裝置精度的檢查:

      裝置電壓、電流、相位角度測量采樣應(yīng)在允許范圍之內(nèi)。4.3.3.4 主變間隔的斷路器輔助保護(hù)裝置開關(guān)量輸入的檢查:

      1)檢查軟連接片和硬連接片的邏輯關(guān)系。2)保護(hù)壓板投退的開入符合設(shè)計(jì)要求。

      3)開關(guān)位置的開入:變位情況應(yīng)與裝置及設(shè)計(jì)要求一致。4.3.3.5 主變間隔的斷路器輔助保護(hù)裝置定值校驗(yàn):

      1)1.05倍及0.95倍定值校驗(yàn)。2)操作輸入和固化定值。

      4.3.3.6 主變間隔的斷路器輔助保護(hù)功能檢驗(yàn):

      1)斷路器失靈保護(hù)。2)死區(qū)保護(hù)。3)過流保護(hù)。

      4)失靈啟動(dòng)及出口回路。

      5)三相不一致啟動(dòng)回(檢驗(yàn)屏內(nèi)啟動(dòng)回路、開關(guān)本體三相不一致保護(hù)是否按定值單要求整定)。

      4.3.4 變壓器間隔相關(guān)告警信號(hào):

      1)開關(guān)本體告警信號(hào)(包括氣體壓力、液壓和彈簧未儲(chǔ)能、三相不一致、電機(jī)就地操作電源消失等,要求檢查聲光信號(hào)正確)。

      2)保護(hù)異常告警信號(hào)(包括保護(hù)動(dòng)作、重合閘動(dòng)作、保護(hù)裝置告警信號(hào)等,要求檢查聲光信號(hào)正確)。

      3)回路異常告警信號(hào)(包括控制回路斷線、電流互感器和電壓互感器回路斷線、切換同時(shí)動(dòng)、直流電源消失、操作電源消失等,要求檢查聲光信號(hào)正確)。

      4)跳、合閘監(jiān)視回路。

      5)本體保護(hù)檢查:包括本體瓦斯、有載瓦斯、油溫高、風(fēng)冷全停、釋壓器、油壓速動(dòng)信號(hào)、要求檢查聲光信號(hào)正確。4.3.5 變壓器保護(hù)錄波信號(hào):

      1)差動(dòng)保護(hù)跳閘作為啟動(dòng)量。2)后備保護(hù)跳閘作為啟動(dòng)量。3)本體保護(hù)跳閘作為啟動(dòng)量。

      4.3.6 變壓器保護(hù)整組試驗(yàn)(兩套保護(hù)時(shí)應(yīng)用電流回路串聯(lián)、電壓回路并聯(lián)的方法進(jìn)行):

      1)差動(dòng)保護(hù):檢查比例制動(dòng),諧波制動(dòng),電流互感器斷線閉鎖等。2)高壓側(cè)后備保護(hù):方向過流保護(hù)、復(fù)壓過流保護(hù)等。3)中壓側(cè)后備保護(hù):方向過流保護(hù),復(fù)壓過流保護(hù)等。4)低壓側(cè)后備保護(hù):方向過流保護(hù),復(fù)壓過流保護(hù)等。5)定時(shí)限、反時(shí)限零序保護(hù)。6)阻抗保護(hù)。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      7)間隙零序過壓及過流保護(hù)。

      8)本體非電量保護(hù):非電量保護(hù)分別投跳閘和信號(hào),模擬本體與有載的重瓦斯和輕瓦斯、壓力釋放、冷控失電、油溫高等非電量保護(hù)動(dòng)作,觀察報(bào)文和后臺(tái)信息;模擬過負(fù)荷,觀察啟動(dòng)風(fēng)冷和試驗(yàn)閉鎖有載調(diào)壓。

      4.3.7 變壓器相關(guān)斷路器的跳閘、失靈啟動(dòng)和三相不一致保護(hù)回路檢查: 4.3.7.1 失靈啟動(dòng)回路:

      1)保護(hù)啟動(dòng)失靈觸點(diǎn)、失靈電流判別元件觸點(diǎn)及三跳啟動(dòng)失靈啟動(dòng)失靈觸點(diǎn)。

      2)用兩套保護(hù)分別帶輔助保護(hù)、開關(guān),模擬A、B、C和三相保護(hù)動(dòng)作相應(yīng)開關(guān)失靈,用導(dǎo)通法在失靈保護(hù)屏測啟動(dòng)失靈的正確性,按相檢驗(yàn)失靈回路中每個(gè)觸點(diǎn)和壓板接線的正確性。

      3)變壓器高壓側(cè)斷路器失靈保護(hù)動(dòng)作后跳變壓器各側(cè)斷路器,變壓器高壓側(cè)失靈動(dòng)作開入后,應(yīng)經(jīng)靈敏的、不需整定的電流元件并帶50 ms延時(shí)后跳變壓器各側(cè)斷路器。

      4)變壓器中壓側(cè)斷路器失靈保護(hù)動(dòng)作后跳變壓器各側(cè)斷路器,變壓器中壓側(cè)失靈動(dòng)作開入后,應(yīng)經(jīng)靈敏的、不需整定的電流元件并帶50 ms延時(shí)后跳變壓器各側(cè)斷路器。4.3.7.2 失靈、母差出口跳本間隔檢查:

      在確保失靈、母差保護(hù)屏內(nèi)回路正確和打開本間隔開關(guān)回路接線的情況下用短接的方法檢查失靈、母差出口跳本開關(guān)回路是否正確,應(yīng)閉鎖重合閘,開放對側(cè)縱聯(lián)保護(hù)。4.3.7.3 三相不一致啟動(dòng)回路檢查:

      檢查啟動(dòng)回路和開關(guān)三相不一致保護(hù)是否按定值單整定。4.3.7.4 出口跳、合閘回路:

      主保護(hù)、后備保護(hù)出口跳閘各側(cè)斷路器和母聯(lián)斷路器回路的正確性 4.3.8 主變保護(hù)傳動(dòng)試驗(yàn)(帶開關(guān)進(jìn)行):

      1)區(qū)內(nèi)單相瞬時(shí)接地故障。

      2)模擬高壓側(cè)區(qū)外兩相瞬時(shí)故障。3)模擬中壓側(cè)區(qū)外兩相瞬時(shí)故障。4)模擬低壓側(cè)區(qū)外三相瞬時(shí)故障。5)模擬重瓦斯、有載瓦斯保護(hù)動(dòng)作.4.3.9 主變保護(hù)投運(yùn)前檢查:

      1)打印定值與定值單核對(與定值單要求一致)。

      2)恢復(fù)所有打開的接線(電流回路應(yīng)進(jìn)行緊固,所有臨時(shí)線拆除,接線恢復(fù)到運(yùn)行狀態(tài))。

      3)壓板以及把手等(測試保護(hù)壓板上下樁頭的電位,檢查是否存在回路接點(diǎn)粘合情況, 把手等恢復(fù)至運(yùn)行狀態(tài))。

      4)打印機(jī)(打印機(jī)指示正確,打印紙放置良好,打印機(jī)防塵蓋放置正確)。4.3.10 主變保護(hù)帶負(fù)荷向量測試、檢查:

      1)測量電流差動(dòng)保護(hù)各組電流互感器的相位以及各側(cè)電壓,電流的幅值及相位關(guān)系。對于電流回路的中性線也應(yīng)進(jìn)行幅值測量(測量流過中性線的不平衡電流): 要求與當(dāng)時(shí)系統(tǒng)潮流大小及方向核對。

      2)差動(dòng)保護(hù)的差流測試:檢查其大小是否正常,并記錄存檔。3)方向零序保護(hù)及方向過流的方向測試:通過系統(tǒng)潮流方向核對。4.4 母線保護(hù)驗(yàn)收項(xiàng)目

      4.4.1 母線保護(hù)電流、電壓回路檢查:

      1)檢查各間隔電流互感器的變比、極性、準(zhǔn)確級應(yīng)正確,應(yīng)與定值單要求相一致(應(yīng)特別注意母差保護(hù)對母聯(lián)TA極性的要求)。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      2)檢查母線電壓閉鎖是否正確。4.4.2 母線保護(hù)相關(guān)二次回路的檢查:

      1)檢查接入母差保護(hù)每一間隔的接點(diǎn)與電流二次回路接線的一致性:要求接入母差保護(hù)每一間隔的隔離開關(guān)接點(diǎn)應(yīng)能正確反映本間隔一次隔離開關(guān)的位置,對間隔的隔離開關(guān)與電流二次回路接線的一致性進(jìn)行檢查。

      2)隔離開關(guān)切換檢查:分別切換1G、2G,檢查裝置切換變位是否一致。3)失靈啟動(dòng)、母差跳閘回路。此項(xiàng)分別在各間隔驗(yàn)收時(shí)進(jìn)行試驗(yàn)。4.4.3 母線保護(hù)裝置檢查

      4.4.3.1 母線保護(hù)裝置參數(shù)核對:

      1)保護(hù)裝置基本參數(shù)核對(定值區(qū)、通信地址、被保護(hù)設(shè)備名稱)符合要求。2)保護(hù)裝置交流插件參數(shù)與一次設(shè)備參數(shù)一致。

      3)保護(hù)裝置直流插件參數(shù)與本站直流額定電壓一致。4)保護(hù)裝置版本和校驗(yàn)碼在規(guī)定的有效版本范圍之內(nèi)。5)打印機(jī)參數(shù)與裝置打印參數(shù)設(shè)置。6)檢查GPS對時(shí)是否正確。4.4.3.2 母線保護(hù)電源的檢查:

      1)檢查輸出電壓及其穩(wěn)定性在裝置技術(shù)參數(shù)正常范圍以內(nèi)。

      2)檢查正、負(fù)對地是否有電壓;檢查工作地與保安地是否相連(要求不連);檢查逆變輸出電源對地是否有電壓。

      4.4.3.3 母線保護(hù)保護(hù)裝置的數(shù)模轉(zhuǎn)換精度的檢查:

      裝置電壓、電流、相位角度測量采樣應(yīng)在允許范圍之內(nèi)。4.4.3.4 母線保護(hù)裝置開關(guān)量輸入的檢查:

      1)檢查軟連接片和硬連接片的邏輯關(guān)系。2)保護(hù)壓板投退的開入符合設(shè)計(jì)要求。

      3)各間隔隔離開關(guān)切換觸點(diǎn)(包括母聯(lián)間隔):應(yīng)直接操作隔離開關(guān)進(jìn)行檢查,并且要結(jié)合電流回路進(jìn)行檢查。

      4.4.3.5 母線保護(hù)定值檢查:

      1)1.05倍及0.95倍定值校驗(yàn)。2)操作輸入和固化定值。4.4.3.6 母線保護(hù)功能檢驗(yàn):

      1)差動(dòng)保護(hù):分別模擬母線區(qū)內(nèi)、外故障,并檢查母差保護(hù)的動(dòng)作行為及測量保護(hù)動(dòng)作時(shí)間。保護(hù)動(dòng)作后應(yīng)同時(shí)跳開接于故障母線上的各斷路器。

      2)失靈保護(hù)啟動(dòng)和母差跳閘:按間隔進(jìn)行,對于雙母線接線,分別模擬接入I、II段母線斷路器失靈,失靈保護(hù)動(dòng)作后應(yīng)先斷開母聯(lián)斷路器,后斷開相應(yīng)母線上的各斷路器;若母聯(lián)斷路器失靈,應(yīng)跳開兩段母線上的所有斷路器。

      3)充電保護(hù)。4)死區(qū)保護(hù)。5)過流保護(hù)。

      4.4.4 母線保護(hù)電壓切換的檢查:能夠正常自動(dòng)切換。4.4.5 母線保護(hù)告警信號(hào):

      1)保護(hù)異常告警信號(hào)。2)回路異常告警信號(hào)。3)電壓異常告警。

      4)電流互感器斷線告警信號(hào)。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      4.4.6 母線保護(hù)錄波信號(hào):

      1)母差動(dòng)作作為啟動(dòng)量。

      2)電壓閉鎖不要求作為啟動(dòng)量。

      4.4.7 母線保護(hù)整組傳動(dòng)試驗(yàn):檢查選擇故障母線功能的正確性。

      1)模擬甲母故障。2)模擬乙母故障。

      3)模擬甲母某間隔失靈。4)模擬乙母某間隔失靈。5)模擬母聯(lián)充電保護(hù)動(dòng)作。4.4.8 母線保護(hù)投運(yùn)前檢查:

      1)打印定值與定值單核對(與定值單要求一致)。

      2)恢復(fù)所有打開的接線(電流回路應(yīng)進(jìn)行緊固,所有臨時(shí)線拆除,接線恢復(fù)到運(yùn)行狀態(tài))。

      3)壓板以及把手等(測試保護(hù)壓板上下樁頭的電位,檢查是否存在回路接點(diǎn)粘合情況, 把手等恢復(fù)至運(yùn)行狀態(tài))。

      4)打印機(jī)(打印機(jī)指示正確,打印紙放置良好,打印機(jī)防塵蓋放置正確)。4.4.9 母線保護(hù)帶負(fù)荷后向量測試、檢查:

      1)測量電流差動(dòng)保護(hù)各組電流互感器的幅值及相位關(guān)系,對電流回路的中性線也應(yīng)進(jìn)行幅值測量(測量流過中性線的不平衡電流):

      要求與當(dāng)時(shí)系統(tǒng)潮流大小及方向核對。

      2)母差保護(hù)差流測試:檢查其大小是否正常,并記錄存檔。4.5 故障錄波器驗(yàn)收項(xiàng)目

      4.5.1 故障錄波器電流、電壓回路檢查:

      1)檢查各輸入模擬量的極性是否正確:包括零序電流極性是否正確。2)電壓回路檢查:檢查電壓回路接入是否正確。4.5.2 故障錄波器裝置檢查

      4.5.2.1 故障錄波器裝置參數(shù)核對:

      1)裝置基本參數(shù)核對(定值區(qū)、通信地址、被保護(hù)設(shè)備名稱)符合要求。2)裝置交流插件參數(shù)與一次設(shè)備參數(shù)一致。

      3)裝置版本和校驗(yàn)碼在規(guī)定的有效版本范圍之內(nèi)。4)打印機(jī)參數(shù)與裝置打印參數(shù)設(shè)置。5)檢查GPS對時(shí)是否正確。

      4.5.2.2 故障錄波器裝置電源的檢查:

      1)檢查輸出電壓及其穩(wěn)定性在裝置技術(shù)參數(shù)正常范圍以內(nèi)。

      2)檢查正、負(fù)對地是否有電壓;檢查工作地與保安地是否相連(要求不連);檢查逆變輸出電源對地是否有電壓。

      4.5.2.3 故障錄波器裝置的數(shù)模轉(zhuǎn)換精度的檢查:

      裝置電壓、電流、相位角度測量采樣應(yīng)在允許范圍之內(nèi)。4.5.2.4 故障錄波器開關(guān)量輸入的檢查:

      1)各間隔保護(hù)的開關(guān)量是否齊全。2)各間隔的開入是否定義正確。4.5.2.5 故障錄波器裝置定值校驗(yàn):

      1)1.05倍及0.95倍定值校驗(yàn)。2)操作輸入和固化定值。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      4.5.3 錄波檢查及波形分析:

      1)開關(guān)量啟動(dòng)錄波:檢查各開關(guān)量啟動(dòng)錄波是否正確。2)模擬量啟動(dòng)錄波:檢查各模擬量啟動(dòng)錄波是否正確。3)其他量啟動(dòng)錄波:檢查頻率等其他量啟動(dòng)錄波是否正確。4)就地波形分析(含后臺(tái)機(jī)):檢查是否能夠正常進(jìn)行分析。5)打印故障波形:檢查打印報(bào)告是否完整。4.5.4 故障錄波器告警信號(hào):

      1)裝置異常告警信號(hào)。2)電壓異常告警。

      4.5.5 故障錄波器投運(yùn)前檢查:

      1)打印定值與定值單核對(與定值單要求一致)。

      2)恢復(fù)所有打開的接線(電流回路應(yīng)進(jìn)行緊固,所有臨時(shí)線拆除,接線恢復(fù)到運(yùn)行狀態(tài))。

      3)壓板以及把手等(測試保護(hù)壓板上下樁頭的電位,檢查是否存在回路接點(diǎn)粘合情況, 把手等恢復(fù)至運(yùn)行狀態(tài))。

      4)打印機(jī)(打印機(jī)指示正確,打印紙放置良好,打印機(jī)防塵蓋放置正確)。5 自動(dòng)化系統(tǒng)、故障信息管理系統(tǒng)驗(yàn)收項(xiàng)目 5.1 故障信息管理系統(tǒng)檢查

      各種繼電保護(hù)的動(dòng)作信息、告警信息、保護(hù)狀態(tài)信息、錄播信息及定值信息的傳輸正確。5.2 測控裝置驗(yàn)收項(xiàng)目

      5.2.1 測控裝置設(shè)備連接及防護(hù):

      1)設(shè)備連接:采取抗干擾措施,裝置外殼具備可靠的接地點(diǎn)。2)金屬結(jié)構(gòu)件:油漆無脫落。

      3)隔離端子:直、交流及控制回路加裝隔離端子或隔離片。

      4)接地:不設(shè)置單獨(dú)的接地網(wǎng),接地線與變電站主接地網(wǎng)連接;機(jī)箱、機(jī)柜及電纜屏蔽層均可靠接地。

      5)抗干擾:滿足電磁兼容性,具有抗輻射電磁場干擾等功能。6)外殼防護(hù):防止直徑12.5mm及以上的固體異物進(jìn)入。5.2.2 測控裝置基本性能:

      1)直流模擬量:

      模擬量輸入總誤差不大于0.2%,輸入電流信號(hào)最大負(fù)載阻抗為5V/mA(電流標(biāo)稱值),電壓信號(hào)最小負(fù)載阻抗為200kΩ/V;數(shù)模轉(zhuǎn)換總誤差不大于0.2%,輸出電流信號(hào)最大負(fù)載阻抗為5V/mA(電流標(biāo)稱值),電壓信號(hào)最小負(fù)載阻抗為200kΩ/V。

      2)工頻交流模擬量: 輸入回路要求:工頻交流電量輸入回路應(yīng)有隔離電路,且應(yīng)有電壓互感器和電流互感器回路異常報(bào)警;設(shè)備上二次電壓互感器、電流互感器插件拔插應(yīng)可靠的保證交流電壓輸入外回路開路、交流電流輸入外回路短路;電壓回路要經(jīng)過熔絲,電流回路要直接與端子牢固連接。功率消耗:工頻交流電量每一電流輸入回路的功率消耗<0.75VA,每一電壓輸入回路的功率消耗≤0.5VA。

      3)故障電流:故障電流的總誤差≤3%。4)狀態(tài)量:閉合對應(yīng)二進(jìn)制碼“1”,斷開對應(yīng)二進(jìn)制碼“0”;輸入回路應(yīng)有電氣隔離措施,延遲時(shí)間為10ms~100ms。

      5)脈沖量:輸入回路采用光電隔離;脈寬≥10ms;接口電平為0~24V。6)與通信系統(tǒng)接口:

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      遠(yuǎn)動(dòng)設(shè)備(DTE)和數(shù)據(jù)電路終端設(shè)備(DCE)間物理距離和最大傳輸速度之間的關(guān)系滿足:物理距離1000m時(shí),最大傳輸速度為1kbit/s;物理距離100m時(shí),最大傳輸速度為10kbit/s;物理距離10m時(shí),最大傳輸速度為100kbit/s。

      7)遠(yuǎn)動(dòng)規(guī)約:遠(yuǎn)動(dòng)規(guī)約可采用DL/T 634,變電站內(nèi)通信規(guī)約可采用DL/T 667。8)遙控輸出(接點(diǎn)容量):直流:30V、5A,交流:220V、5A。

      9)故障告警及閉鎖:發(fā)生任何軟硬件故障能立即告警,視故障類別閉鎖其出口;任何軟硬件(元器件)發(fā)生一處故障不會(huì)導(dǎo)致誤出口和誤閉鎖。

      10)雙電源檢查:I/O測控單元柜采用2路220V 直流電源供電;各裝置應(yīng)具有直流快速小開關(guān),與裝置安裝在同一面柜上;當(dāng)在該直流回路中任何一處發(fā)生斷線或短路時(shí),均發(fā)告警信號(hào)。

      11)PT回路:測控柜PT回路接線良好、極性正確。

      12)遙信檢查:斷路器、隔離開關(guān)及接地刀閘具有分、合閘信號(hào)。13)連續(xù)通電電源影響:

      a)連續(xù)通電:進(jìn)行不少于72小時(shí)連續(xù)穩(wěn)定的通電測試,考核其穩(wěn)定性(交直流電壓為額定值)。

      b)直流電源:電壓在80%~110%額定值220V范圍內(nèi)(176V~242V)變化、紋波系數(shù)≤5%時(shí),設(shè)備能正常工作。

      c)交流電源:電壓在80%~110%額定值220V范圍內(nèi)(176V~242V)變化、諧波分量≤5%、頻率在47.5~52.5Hz間變化時(shí),設(shè)備能正常工作。

      14)同期系統(tǒng)回路檢查:

      檢查同期系統(tǒng)公共回路接線是否正確,各間隔模擬手動(dòng)同期合閘。5.3 網(wǎng)絡(luò)交換機(jī)驗(yàn)收項(xiàng)目

      5.3.1 通訊線/網(wǎng)線接線檢查:

      1)安裝、排列及標(biāo)識(shí)。2)水晶頭、電纜頭。3)線束綁扎松緊、形式。4)端部彎圈。

      5.3.2 裝置功能檢查:

      1)信息處理:每套通訊管理機(jī)應(yīng)能完整、獨(dú)立的處理所有信息;兩套裝置之間不應(yīng)有任何電氣聯(lián)系,當(dāng)一套裝置退出不應(yīng)影響另一套裝置的正常運(yùn)行。

      2)獨(dú)立性:每套通訊管理機(jī)應(yīng)配置獨(dú)立的通信設(shè)備(包含交換機(jī)、光纖收發(fā)器、光纜等),不存在物理連接。

      3)運(yùn)行方式:通訊管理機(jī)應(yīng)采用雙機(jī)熱備用方式。4)采集數(shù)據(jù):采集規(guī)約及數(shù)據(jù)正確性檢查。5)上傳數(shù)據(jù):上傳規(guī)約及數(shù)據(jù)正確性檢查。

      6)供電電源:兩套通訊裝置、交換機(jī)的直流電源應(yīng)取自不同蓄電池組供電的直流母線段。

      5.4 監(jiān)控系統(tǒng)軟件功能驗(yàn)收項(xiàng)目 5.4.1 應(yīng)用軟件檢查

      1)應(yīng)用軟件總體要求: 具有實(shí)時(shí)庫、歷史庫、追憶庫管理功能。2)系統(tǒng)維護(hù): 可在線、離線修改數(shù)據(jù)庫信息。

      3)數(shù)據(jù)管理: 按年、月、周、日的電壓、電流、有功、無功具有峰、谷值統(tǒng)計(jì)等功能。4)雙機(jī)切換: 雙機(jī)切換時(shí)間≤30s。

      5)操作權(quán)限: 可設(shè)置管理員、監(jiān)護(hù)人、操作人等權(quán)限。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      6)控制操作:具有單人、雙人監(jiān)控操作功能。7)報(bào)警處理:實(shí)現(xiàn)實(shí)時(shí)報(bào)警、歷史報(bào)警查詢功能。8)事件順序記錄SOE:按照事件發(fā)生的時(shí)間順序記錄。

      9)計(jì)算及制表:可自定義公式,實(shí)現(xiàn)在線計(jì)算、制表功能。10)畫面:畫面清晰,顏色分明,操作有效。5.4.2 數(shù)據(jù)的采集及傳輸功能檢查 5.4.2.1 數(shù)據(jù)的采集

      1)模擬量:具有有功、無功、電流、電壓、溫度等采集功能。

      2)數(shù)字量:具有采集保護(hù)、位置、狀態(tài)、壓板信號(hào);事故總、預(yù)告信號(hào);保護(hù)及綜合自動(dòng)化報(bào)文信息等功能。

      3)實(shí)時(shí)數(shù)據(jù):智能電子設(shè)備IED實(shí)時(shí)數(shù)據(jù)(如智能UPS,消防系統(tǒng),電表等)確認(rèn)接收端口,查看相應(yīng)緩沖區(qū)報(bào)文內(nèi)容。

      4)網(wǎng)絡(luò):確認(rèn)外部網(wǎng)絡(luò)接收端口,查看相應(yīng)緩沖區(qū)報(bào)文內(nèi)容。

      5)輔助設(shè)備:其他輔助設(shè)備及接口(如大屏幕投影等)檢查接口設(shè)備與接口服務(wù)器數(shù)據(jù)一致性。

      6)循環(huán)式規(guī)約:循環(huán)式規(guī)約(如頒布循環(huán)遠(yuǎn)動(dòng)規(guī)約CDT等)上行信息接收與處理正確;下發(fā)信息正確;空閑時(shí)下發(fā)同步字頭,同步字可修改,如EB90或者D709。5.4.2.2 傳輸功能

      1)問答式:(如103發(fā)送數(shù)據(jù),104接收數(shù)據(jù)等)在通信機(jī)界面查看

      2)通道緩存:查看收、發(fā)緩沖區(qū)信息,對報(bào)文原碼進(jìn)行實(shí)時(shí)監(jiān)視、截取、鎖定,檢查強(qiáng)制系統(tǒng)數(shù)據(jù)報(bào)文的自動(dòng)下發(fā)。

      3)狀態(tài)監(jiān)視:監(jiān)視通信服務(wù)器、通道、路徑狀態(tài)及統(tǒng)計(jì)通道誤碼。4)數(shù)據(jù)監(jiān)視:正確顯示各通道的遙測、遙信、電量。

      5)數(shù)據(jù)變化:從前置機(jī)模擬遙信變位、事故、遙測變化、事件順序記錄系統(tǒng)SOE、遙控等功能。

      6)事項(xiàng)緩沖:事件順序記錄系統(tǒng)SOE在事項(xiàng)緩沖區(qū)正確顯示。

      7)通道告警:正確產(chǎn)生通道報(bào)警事項(xiàng);對通道及通道數(shù)據(jù)的各類異常(包括失步、誤碼高、死數(shù)據(jù)等)進(jìn)行分類報(bào)警。

      8)通道切換:設(shè)定時(shí)間判別,人工中斷主通道,通訊中斷后備通道正確接收信息,強(qiáng)制指定主通道。

      9)保護(hù)措施:通訊接口部分采取防護(hù)措施。10)主備切換:自動(dòng)/人工二種方式。5.4.3 計(jì)算、數(shù)據(jù)處理

      1)算術(shù)運(yùn)算:算術(shù)運(yùn)算(可自定義),查看計(jì)算公式或用戶定義過程工程。2)邏輯運(yùn)算:邏輯運(yùn)算(與或非),查看計(jì)算量公式。3)條件運(yùn)算:條件運(yùn)算(if else),查看用戶過程,如將遙信表示的有載調(diào)壓變壓器檔位轉(zhuǎn)化為數(shù)字量檔位。

      4)累計(jì)計(jì)算:電壓合格率、超限時(shí)間累計(jì)計(jì)算基于以1分鐘為單位的存盤周期平均值統(tǒng)計(jì)或基于瞬時(shí)存盤值的統(tǒng)計(jì),并在報(bào)表中顯示。

      5)遙信和遙測相關(guān)判斷:線路開關(guān)為分,而其潮流不為0,置遙測可疑標(biāo)志;條件自動(dòng)置零(開關(guān)分且負(fù)荷在零漂范圍內(nèi),自動(dòng)置零)。

      6)數(shù)據(jù)存盤:把當(dāng)前遙測值存入歷史數(shù)據(jù)庫。

      7)模擬量越限及恢復(fù)處理:設(shè)置一重或二重越限參數(shù)和恢復(fù)系數(shù)。當(dāng)系統(tǒng)發(fā)生越限或異常時(shí),系統(tǒng)發(fā)出區(qū)別于系統(tǒng)事故的聲光及語音告警,打印越限值記錄及相關(guān)參數(shù);恢復(fù)正 18 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      常后,聲光自動(dòng)解除。

      8)遙信人工設(shè)置:設(shè)置某個(gè)遙信為人工設(shè)置狀態(tài),檢查該遙信在畫面上的顏色。

      9)遙信變位處理:接收并處理正常的變位,根據(jù)用戶設(shè)定的報(bào)警類型報(bào)警并生成事項(xiàng)。10)報(bào)警確認(rèn)、禁止及恢復(fù):報(bào)警有逐項(xiàng)確認(rèn)和全部確認(rèn)兩種方式,其中全部確認(rèn)只確認(rèn)本站的所有報(bào)警信息。畫面上的所有信息點(diǎn)的報(bào)警均由用戶通過人機(jī)界面人工設(shè)置禁止或恢復(fù),禁止后的信息不再啟動(dòng)相關(guān)報(bào)警,但還應(yīng)在事項(xiàng)中可以正常記錄,配置定時(shí)停閃、手動(dòng)停閃,檢查遙信閃爍,并按設(shè)置的方式停閃。

      11)開關(guān)事故判定邏輯:可用事故總信號(hào)、保護(hù)信號(hào)做判斷事故依據(jù)。

      12)事故追憶:模擬事故,啟動(dòng)追憶過程,在值班員界面中查看追憶數(shù)據(jù),事故追憶點(diǎn)可為任何實(shí)時(shí)數(shù)據(jù)及計(jì)算數(shù)據(jù),對重要的遙測量記錄事故前后若干周期的量值,形成事故追憶表及顯示畫面,對追憶數(shù)據(jù)進(jìn)行事故重演。

      13)異常信號(hào)分級別處理:模擬異常信號(hào),系統(tǒng)發(fā)出不同于事故情況的聲光報(bào)警,并產(chǎn)生對應(yīng)事項(xiàng)。

      14)多重事故推圖:模擬多次事故,系統(tǒng)正確反應(yīng)事故畫面,并伴有相應(yīng)的聲光報(bào)警。當(dāng)多重報(bào)警畫面疊加時(shí),不完全覆蓋原監(jiān)控畫面。5.4.4 控制、圖形功能 5.4.4.1 控制功能

      1)狀態(tài)輸出控制功能:進(jìn)行斷路器、隔離開關(guān)的分/合、電抗器/電容器的投切、有載調(diào)壓變壓器、保護(hù)定值的遙控控制。

      2)權(quán)限:控制權(quán)限保護(hù)(時(shí)限/口令),設(shè)置權(quán)限。

      3)保護(hù)功能:在定時(shí)限內(nèi)如果遙控命令沒有執(zhí)行,將自動(dòng)撤消這次命令。4)監(jiān)護(hù)操作:雙機(jī)監(jiān)護(hù)操作設(shè)置權(quán)限及相應(yīng)配置。

      5)遙控閉鎖:設(shè)置閉鎖、禁止控制或操作標(biāo)志,該標(biāo)志可在線修改并自動(dòng)保存,禁止同一設(shè)備的不同操作或不同用戶對同一設(shè)備的操作,具有防誤閉鎖功能。

      6)

      5.4.4.2 圖形操作功能

      1)畫面種類:監(jiān)控自動(dòng)化系統(tǒng)結(jié)構(gòu)工況圖、通道結(jié)構(gòu)圖、潮流圖、主機(jī)資源圖、通道誤碼率統(tǒng)計(jì)表等。

      2)畫面調(diào)用:具有特殊功能鍵調(diào)用、菜單調(diào)用、按光敏區(qū)顯示調(diào)用、右鍵調(diào)用功能。3)畫面刷新:具有周期性刷新(對周期用戶可調(diào))、強(qiáng)制性刷新、特殊電網(wǎng)事件觸發(fā)刷新功能。

      4)畫面縮放:界面可進(jìn)行畫面縮放操作。

      5)畫面移動(dòng):界面可進(jìn)行上、下、左、右移動(dòng)操作。

      6)信息常駐:檢查時(shí)鐘、電網(wǎng)潮流、電壓、電流、功率等信息常駐界面。7)歷史庫界面:允許瀏覽,維護(hù)(增加,刪除,修改)等多項(xiàng)操作。8)權(quán)限及口令:支持操作員口令、權(quán)限功能限制和嚴(yán)格的驗(yàn)證機(jī)制。5.4.5 網(wǎng)絡(luò)、數(shù)據(jù)庫功能 5.4.5.1 網(wǎng)絡(luò)功能

      1)接點(diǎn)配置::接點(diǎn)任務(wù)配置及自啟動(dòng)。2)服務(wù)器切換:服務(wù)器切換(人工和自動(dòng))。

      3)運(yùn)行監(jiān)視:網(wǎng)絡(luò)運(yùn)行模式及接點(diǎn)、進(jìn)程狀態(tài)監(jiān)視,相應(yīng)故障事項(xiàng)形成日志記錄,拒絕執(zhí)行相關(guān)的控制命令。

      4)主備切換:雙網(wǎng)絡(luò)主備切換。5.4.5.2 數(shù)據(jù)庫功能

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      1)表格:支持表格信息的增加,刪除。

      2)存儲(chǔ)密度:歷史數(shù)據(jù)庫存儲(chǔ)密度可調(diào)(分鐘級)。3)監(jiān)視及報(bào)警:硬盤使用率監(jiān)視及數(shù)據(jù)庫容量報(bào)警。4)備份與恢復(fù):數(shù)據(jù)庫的備份與恢復(fù)。5)存儲(chǔ)、查詢:歷史事項(xiàng)的存儲(chǔ)、查詢。

      6)歷史數(shù)據(jù):所有歷史數(shù)據(jù)必須及時(shí)保存在硬盤中,達(dá)到一定容量時(shí)能自動(dòng)將前面部分轉(zhuǎn)存外設(shè),這些數(shù)據(jù)均可在線顯示、處理,并能拷貝及調(diào)用。

      7)報(bào)警、備份:當(dāng)硬盤達(dá)到一定容量時(shí)系統(tǒng)應(yīng)有聲光及事項(xiàng)報(bào)警。若數(shù)據(jù)無法自動(dòng)轉(zhuǎn)存,則系統(tǒng)應(yīng)自動(dòng)覆蓋最早的歷史數(shù)據(jù),并保證歷史數(shù)據(jù)以某種方式進(jìn)行備份。

      8)保存數(shù)據(jù):所有歷史數(shù)據(jù)均以遞推方式或覆蓋方式在線保存一年以上。5.4.6 繪圖、報(bào)表、打印功能 5.4.6.1 繪圖功能

      1)操作:圖元、區(qū)域、文字操作。

      2)自定義:自定義圖符(可增加刪除)。3)一體化:圖模一體化。

      4)繪制:曲線圖、棒圖、餅圖、潮流圖、通道狀態(tài)圖等圖形的繪制。5.4.6.2 報(bào)表及打印功能

      1)報(bào)表管理:報(bào)表管理(日、月運(yùn)行報(bào)表的制作、顯示功能)。2)參數(shù):參數(shù)查詢(變電站運(yùn)行參數(shù)表等)。

      3)查詢、打?。喊磿r(shí)段、類別、站名可分別查詢、打印歷史事項(xiàng)。

      4)報(bào)表類別:具有按年、月、周、日的電壓、電流、有功、無功峰、谷值統(tǒng)計(jì)等報(bào)表。5)最大、最小、平均值:顯示、打印任一時(shí)間段的最大值、最小值、平均值數(shù)值及最大值、最小值的發(fā)生時(shí)間。

      6)實(shí)時(shí)、歷史統(tǒng)計(jì)值:顯示、打印任一日、月、年的實(shí)時(shí)統(tǒng)計(jì)值、歷史統(tǒng)計(jì)值及其發(fā)生時(shí)間。

      7)運(yùn)行、停運(yùn)的時(shí)間及次數(shù):顯示、打印任一設(shè)備的運(yùn)行時(shí)間、停運(yùn)時(shí)間、停運(yùn)次數(shù)。8)修改、錄入:實(shí)現(xiàn)對報(bào)表數(shù)據(jù)進(jìn)行修改的功能,且錄入實(shí)時(shí)或歷史數(shù)據(jù)庫,取代原有值參加運(yùn)算。對歷史計(jì)算量進(jìn)行重新計(jì)算時(shí),應(yīng)根據(jù)輸入的時(shí)間,對此時(shí)間段內(nèi)的特定歷史計(jì)算量進(jìn)行重新計(jì)算,而不影響其它時(shí)間段的歷史計(jì)算量。

      9)檢索、預(yù)覽:可從任一接點(diǎn)上檢索、預(yù)覽和使用報(bào)表,表格能夠自適應(yīng)各規(guī)格紙張,且在紙型更換后無需對報(bào)表格式進(jìn)行調(diào)整。

      10)打?。褐С志W(wǎng)絡(luò)和事項(xiàng)打印。5.4.7 系統(tǒng)基本技術(shù)和實(shí)時(shí)性指標(biāo)

      1)掃描周期:系統(tǒng)對裝置掃描周期≤2S 2)故障切換:雙機(jī)故障切換≤30S 3)CPU負(fù)荷:系統(tǒng)中各中央處理單元CPU負(fù)荷≤30% 4)狀態(tài)量變化顯示:狀態(tài)量變化傳送到人機(jī)工作站顯示器顯示≤2S 5)遙測量變化顯示:遙測量變化傳送到人機(jī)工作站顯示器顯示≤3S 6)事故信號(hào)顯示:電網(wǎng)事故信號(hào)傳送到人機(jī)工作站顯示器顯示≤2S 7)操作命令傳送周期:操作命令傳送周期(包括返校時(shí)間)≤3S 8)畫面調(diào)看:顯示器畫面調(diào)看響應(yīng)時(shí)間≤2S 9)數(shù)據(jù)刷新:顯示器畫面動(dòng)態(tài)數(shù)據(jù)刷新時(shí)間(可調(diào))≤3S 5.5 監(jiān)控電源系統(tǒng) 5.5.1 電源屏柜檢查

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      1)電源屏檢查:檢查編號(hào)、容量等標(biāo)識(shí)

      2)備用電源:裝置故障時(shí),應(yīng)能自動(dòng)切換到備用電源狀態(tài),切換時(shí)不引起裝置復(fù)位 5.5.2 逆變電源檢查

      1)運(yùn)行指示燈:指示正確

      2)直流輸入:直流輸入電壓在80%~120%額定值220V范圍內(nèi)(176V~264V)變化 3)輸出電壓:輸出電壓在97%~103%額定電壓220V范圍內(nèi)(213.4V~226.6V)變化 4)過負(fù)荷能力:帶150%額定負(fù)荷運(yùn)行60s,帶125%額定負(fù)荷運(yùn)行10min 5)雙機(jī)檢查:逆變電源雙機(jī)應(yīng)采用并聯(lián)方式 5.6 全站對時(shí)系統(tǒng)驗(yàn)收項(xiàng)目

      1)外觀檢查:完好無損壞。2)運(yùn)行指示燈:指示正確。

      3)準(zhǔn)確度:輸出時(shí)間與協(xié)調(diào)世界(UTC)時(shí)間實(shí)現(xiàn)同步準(zhǔn)確。6 站用直流系統(tǒng)驗(yàn)收 6.1 直流屏接線

      1)設(shè)備屏、柜的固定及接地,應(yīng)可靠,門與柜之間經(jīng)截面不小于6 mm2的裸體軟導(dǎo)線可靠連接。

      2)導(dǎo)線外觀,絕緣層完好,無中間接頭,排列整齊。3)配線連接(螺接、插接、焊接或壓接),應(yīng)牢固、可靠。4)導(dǎo)線配置符合背面接線圖要求。

      5)導(dǎo)線端頭標(biāo)志,清晰正確,且不宜脫色。6)用于可動(dòng)部位的導(dǎo)線為多股軟銅線。

      7)電纜標(biāo)牌標(biāo)識(shí),電纜型號(hào)、截面、起始位置清晰正確。8)結(jié)束綁扎松緊和形式,松緊適當(dāng)、勻稱,形成一致。9)導(dǎo)線束的固定應(yīng)牢固、整齊。

      10)每個(gè)接線端子并接芯線數(shù)≤2根。11)備用芯預(yù)留長度至最遠(yuǎn)端子處。

      12)導(dǎo)線接引處預(yù)留長度,適當(dāng),且各線余量一致。13)電氣回路連接(螺接、插接、焊接或壓接),緊固可靠。14)導(dǎo)線芯線端部彎曲,順時(shí)針方向、且大小合適。15)多股軟導(dǎo)線端部處理,加終端附件或搪錫。16)導(dǎo)線端部標(biāo)志,正確、清晰,不易脫色。17)接地檢查: a)二次回路,設(shè)有專用螺栓。

      b)屏蔽電纜,屏蔽層按設(shè)計(jì)要求可靠接地。18)裸露部分對地距離,負(fù)荷>63A,應(yīng)不小于6mm。19)盤、柜及電纜穿孔應(yīng)作好封堵,封堵平整、美觀。6.2 硬母線連接

      1)母線應(yīng)矯正平直,切斷面應(yīng)平整,均勻、無毛刺。2)母線搭接,直線連接63mm、搭接63mm。

      3)主母線、分支母線、引下線及設(shè)備連接線,對稱一致、平衡、豎直、整齊美觀。6.3 直流系統(tǒng)反措驗(yàn)收

      6.3.1系統(tǒng)配置:330KV及以上電壓等級變電站應(yīng)采用三臺(tái)充電、浮充電裝置,兩組蓄電池組的供電方式。

      6.3.2直流母線,應(yīng)采用分段運(yùn)行方式,每段母線應(yīng)分別采用獨(dú)立的蓄電池組供電,并在兩段直流母線之間設(shè)置連絡(luò)開關(guān),正常運(yùn)行時(shí)開關(guān)處于斷開位置。

      甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      6.3.3直流屏內(nèi)空開、熔斷器:

      1)當(dāng)直流斷路器與熔斷器配合時(shí),應(yīng)考慮動(dòng)作特性的不同,對級差做適當(dāng)調(diào)整,直流斷路器下一級不應(yīng)再接熔斷器。

      2)各級熔斷器的定值整定,應(yīng)保證級差的合理配合。

      3)上、下級熔體之間(同一系列產(chǎn)品)額定電流值,應(yīng)保證2~4級級差,電源端選上限,網(wǎng)絡(luò)末端選下線。

      4)為防止事故情況下蓄電池組熔斷器無選擇性熔斷,該熔斷器與分熔斷器之間,應(yīng)保證3~4級級差。

      5)空氣開關(guān)采用帶脫扣直流空氣開關(guān),且空開(熔斷器)配置滿足級差配置要求。6.3.4饋出網(wǎng)絡(luò)應(yīng)采用輻射狀供電方式,不應(yīng)采用環(huán)狀供電方式。6.4 直流系統(tǒng)微機(jī)監(jiān)控器

      1)外殼接地,可靠、牢固。

      2)交流、直流參數(shù),應(yīng)能監(jiān)視交流、直流輸入電壓值。

      3)量測交流實(shí)際輸入量,實(shí)測值與微機(jī)監(jiān)控器采樣值一致(380V±10%)。4)監(jiān)視蓄電池電壓,負(fù)荷電流和浮充電的電流、電壓。

      5)自診斷和顯示功能,微機(jī)監(jiān)控器能診斷內(nèi)部的電路故障和不正常的運(yùn)行狀態(tài),并能發(fā)出聲光告警且遠(yuǎn)方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常;恢復(fù)正常后,故障自動(dòng)解除。

      6)自動(dòng)充電功能,控制充電裝置自動(dòng)進(jìn)行恒流限壓→恒壓充電→浮充電→進(jìn)入正常運(yùn)行狀態(tài)。

      7)定期充電功能,控制充電裝置定期自動(dòng)地對蓄電池組進(jìn)行均衡充電。8)均、浮充自動(dòng)、手動(dòng)轉(zhuǎn)換功能,自動(dòng)、手動(dòng)轉(zhuǎn)換工作試驗(yàn)正常。9)充電電流限流功能,應(yīng)≤I10(10h率放電電流)。

      10)電池均、浮充電壓設(shè)置功能,根據(jù)蓄電池說明書及規(guī)程要求對蓄電池均、浮充電壓進(jìn)行參數(shù)設(shè)置。

      11)閥控蓄電池溫度補(bǔ)充系數(shù)設(shè)置功能,基準(zhǔn)溫度為25℃時(shí),每下降(上升)1℃,單體2V閥控蓄電池浮充電壓值應(yīng)提高(下降)(3-5mV)。

      12)“三遙”功能,通過“三遙”接口,能了解和控制控制直流電源裝置的運(yùn)行方式。a)遙信內(nèi)容:直流母線電壓過高或過低信號(hào)、直流母線接地信號(hào),充電裝置故障等信號(hào)。

      b)遙測內(nèi)容:直流母線電壓及電流值、蓄電池組電壓值,充電電流值等參數(shù)。c)遙控內(nèi)容:直流電源裝置的開機(jī)、停機(jī)、充電裝置的切換。

      13)交流失壓及過、欠壓告警試驗(yàn),監(jiān)控單元顯示故障信息、告警且遠(yuǎn)方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常。

      14)控母過、欠壓告警試驗(yàn),監(jiān)控單元顯示故障信息、告警且遠(yuǎn)方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常。

      15)蓄電池電壓過、欠壓告警試驗(yàn),監(jiān)控單元顯示故障信息、告警且遠(yuǎn)方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常。

      16)熔斷器熔斷告警試驗(yàn),熔斷器熔斷微機(jī)監(jiān)控器顯示故障信號(hào)且遠(yuǎn)方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常。

      17)空氣開關(guān)脫扣告警試驗(yàn),空氣開關(guān)脫扣,微機(jī)監(jiān)控器顯示故障信號(hào)且遠(yuǎn)方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常。

      18)充電模塊(通訊)故障告警試驗(yàn),微機(jī)監(jiān)控器顯示故障信號(hào)且遠(yuǎn)方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常。

      19)絕緣監(jiān)測儀(通訊)故障試驗(yàn),微機(jī)監(jiān)控器顯示絕緣監(jiān)測儀(通訊)故障信號(hào)且遠(yuǎn) 22 甘肅酒泉超高壓輸變公司

      750kV變電站電氣二次系統(tǒng)現(xiàn)場驗(yàn)收規(guī)范

      方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常。6.5 直流充電裝置

      1)充電模塊固定牢固、外殼可靠接地,連接正確。

      2)輸出線相色,正-赭色、負(fù)-藍(lán)色,與母線、蓄電池極性一致。

      3)直流母線絕緣電阻應(yīng)不小于10MΩ;絕緣強(qiáng)度應(yīng)受工頻2KV,耐壓1min,應(yīng)不閃絡(luò)、不擊穿。

      4)手動(dòng)、自動(dòng)試驗(yàn)交流互投裝置準(zhǔn)確、可靠。5)柜內(nèi)各表計(jì),顯示數(shù)據(jù)正確,且有校驗(yàn)合格證。6)恒流充電穩(wěn)流精度范圍,應(yīng)不大于±(0.5%-1%)。7)恒壓充電穩(wěn)壓精度范圍,應(yīng)不大于±(0.1%-0.5%)。8)直流母線紋波系數(shù)范圍,應(yīng)不大于(0.2%-0.5%)。9)蓄電池組浮充電壓穩(wěn)定范圍:(90%-125%)直流標(biāo)稱電壓。10)蓄電池組充電電壓穩(wěn)定范圍:(90%-130%)直流標(biāo)稱電壓。11)充電模塊均流不平衡度:≤±5A。

      12)充電模塊噪聲≤55dB(A),若裝設(shè)通風(fēng)機(jī)時(shí)應(yīng)不大于60dB(A).6.6 絕緣檢測裝置

      1)絕緣檢測儀固定牢固、外殼可靠接地、連接正確。

      2)若裝有微機(jī)型絕緣監(jiān)測儀,任何一支路的絕緣狀態(tài)或接地都能監(jiān)測、顯示和報(bào)警。遠(yuǎn)方信號(hào)的顯示、監(jiān)測及報(bào)警應(yīng)正常。

      3)母線正負(fù)對地電壓平衡且無波動(dòng)現(xiàn)象。6.7 電壓調(diào)節(jié)裝置

      1)自動(dòng)、手動(dòng),升、降控制母線電壓5-7V。2)調(diào)節(jié)繼電器接點(diǎn),滿足直流負(fù)荷容量要求。3)連接線纜,滿足直流負(fù)荷容量要求。6.8 事故照明裝置

      1)交、直流回路,切換試驗(yàn)正常、無短路。

      2)交、直流接觸器接點(diǎn),滿足變電站事故時(shí)的負(fù)荷容量要求。3)饋出開關(guān),滿足變電站事故時(shí)的負(fù)荷容量要求。4)饋出線纜,滿足變電站事故時(shí)的負(fù)荷容量要求。附件(范例)750kV線路保護(hù)及二次回路驗(yàn)收細(xì)則

      1)詳細(xì)內(nèi)容見附件。

      2)其余間隔參考750kV線路間隔內(nèi)容編制執(zhí)行。

      第二篇:電氣二次系統(tǒng)自查報(bào)告

      電氣二次系統(tǒng)自查報(bào)告

      根據(jù)內(nèi)蒙古電力集團(tuán)《轉(zhuǎn)發(fā)國家電網(wǎng)華北電力調(diào)控分中心關(guān)于開展電網(wǎng)二次系統(tǒng)專項(xiàng)檢查的通知》,結(jié)合我廠電氣二次系統(tǒng)實(shí)際情況,針對豐鎮(zhèn)發(fā)電廠#3—#6機(jī)組、220KV系統(tǒng)、500KV系統(tǒng)設(shè)備運(yùn)行狀況,尤其對涉網(wǎng)設(shè)備,安排相關(guān)繼電保護(hù)人員進(jìn)行全面檢查,并針對相關(guān)問題制定整改計(jì)劃,現(xiàn)將自查報(bào)告匯報(bào)如下:

      一. 繼電保護(hù)運(yùn)行管理

      1.反措管理:我廠國家電網(wǎng)及內(nèi)蒙電網(wǎng)下發(fā)的各項(xiàng)反措文件齊全,所有繼電保護(hù)裝置和安全自動(dòng)裝置滿足國調(diào)印發(fā)的專業(yè)檢測要求。

      2.軟件版本管理:我廠所有線路保護(hù)、發(fā)變組保護(hù)軟件版本都有臺(tái)賬,所有保護(hù)、安全自動(dòng)裝置都升級記錄

      3.檢修管理:現(xiàn)場繼電保護(hù)設(shè)備檢驗(yàn)記錄、標(biāo)準(zhǔn)化作業(yè)指導(dǎo)書、工作記錄齊全,并嚴(yán)格執(zhí)行。現(xiàn)場檢查保護(hù)作業(yè)指導(dǎo)書齊全,但現(xiàn)場工作記錄不完整,需要整改。

      4.現(xiàn)場運(yùn)維管理:繼電保護(hù)及安全自動(dòng)裝置現(xiàn)場運(yùn)行管理規(guī)程齊全,保護(hù)日常巡視記錄齊全,繼電保護(hù)與安全自動(dòng)裝置的軟、硬投退壓板與調(diào)控機(jī)構(gòu)一致,定值單與調(diào)控機(jī)構(gòu)一致。

      二. 繼電保護(hù)設(shè)備管理: 1.設(shè)備臺(tái)賬管理:設(shè)備臺(tái)賬記錄齊全、保護(hù)動(dòng)作、記錄異常分析齊全,滿足要求。

      2.反措文件落實(shí)到位,文件齊全,保護(hù)年報(bào)、月報(bào)齊全

      三. 安全自動(dòng)裝置:

      1.安控裝置軟件本版管理:齊全

      2.安控臺(tái)賬管理:我廠有高周切機(jī)1套,分布穩(wěn)定裝置1套。臺(tái)賬齊全。

      3.安控系統(tǒng)策略造冊與管理;我廠分布穩(wěn)定作為執(zhí)行子站,策略造冊按執(zhí)行總站執(zhí)行,按內(nèi)蒙網(wǎng)調(diào)策略執(zhí)行,高周切機(jī)有定值單執(zhí)行記錄,現(xiàn)場打印與定值單一致。

      四. 網(wǎng)源協(xié)調(diào)管理:

      1.重點(diǎn)機(jī)組涉網(wǎng)控制系統(tǒng)參數(shù):我廠勵(lì)磁系統(tǒng)、調(diào)速、PSS、一次調(diào)頻、進(jìn)相等試驗(yàn)報(bào)告齊全,試驗(yàn)項(xiàng)目齊全

      2.重點(diǎn)機(jī)組涉網(wǎng)保護(hù)參數(shù):保護(hù)參數(shù)、保護(hù)定值與系統(tǒng)一致。

      五. 廠站自動(dòng)化設(shè)備運(yùn)行與管理:

      1. 廠站自動(dòng)化設(shè)備供電電源和運(yùn)行環(huán)境情況:我廠自動(dòng)化設(shè)備供電電源滿足要求,環(huán)境、消防設(shè)施滿足要求。

      2. 廠站電力二次系統(tǒng)安全防護(hù):滿足要求。3. 并網(wǎng)機(jī)組自動(dòng)化管理:我廠機(jī)組AVC滿足規(guī)定和規(guī)程要求,根據(jù)電網(wǎng)調(diào)度要求投入實(shí)際運(yùn)行。我廠機(jī)組AGC滿足規(guī)定和規(guī)程要求。

      六. 自動(dòng)化通道數(shù)據(jù)網(wǎng):

      1.自動(dòng)化通信通道:我廠自動(dòng)化通信通道有2路,雙通道可以切換,數(shù)據(jù)網(wǎng)采用獨(dú)立的電力專用通信網(wǎng)。

      2.調(diào)度數(shù)據(jù)網(wǎng)和電力系統(tǒng)二次防護(hù);調(diào)度數(shù)據(jù)網(wǎng)和電力二次系統(tǒng)加裝二次物理隔離,各區(qū)域安全。

      七. 發(fā)現(xiàn)的問題及其解決方案

      1、廠內(nèi)保護(hù)裝置還未實(shí)現(xiàn)同步功能,但網(wǎng)控和各臺(tái)機(jī)組已安裝了GPS裝置,近期廠家來調(diào)試后,就可以完成同步功能。

      2、我廠550KV升壓站開關(guān)失靈重合閘保護(hù)有檢驗(yàn)超期和超服役情況,但已申請升級改造,費(fèi)用下來就可以更換。

      第三篇:110kv變電站二次系統(tǒng)設(shè)計(jì)

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      本論文主要講述的是110kV變電站繼電保護(hù)的配置,整定計(jì)算。目前,110kV變電站主要是直接向廣大用戶供應(yīng)和分配電能,是包括發(fā)電、輸變電和配電在內(nèi)的整個(gè)電力系統(tǒng)的最終環(huán)節(jié)。由于電力系統(tǒng)具有發(fā)、供、用同時(shí)的特點(diǎn),一旦配電系統(tǒng)發(fā)生故障,將造成系統(tǒng)對用戶供電的中斷,同時(shí)也有可能使整個(gè)電力系統(tǒng)受到影響,甚至被破壞,造成巨大的經(jīng)濟(jì)損失。因此,必須提高110kV配電系統(tǒng)的可靠性,給變電站的設(shè)備裝設(shè)動(dòng)作可靠、迅速、性能完善的保護(hù),把故障影響限制在最小范圍內(nèi),保證向用戶提供持續(xù)的電能。

      電力系統(tǒng)繼電保護(hù)和安全自動(dòng)裝置是電力系統(tǒng)的重要組成部分。它對電力系統(tǒng)安全穩(wěn)定地運(yùn)行和對用戶的不間斷供電起著極為重要的作用,沒有繼電保護(hù)的電力系統(tǒng)是不能運(yùn)行的。電力系統(tǒng)繼電保護(hù)的設(shè)計(jì)與配置是否合理直接影響到電力系統(tǒng)的安全穩(wěn)定運(yùn)行。如果設(shè)計(jì)與配置不當(dāng),繼電保護(hù)將不能正確動(dòng)作,從而會(huì)擴(kuò)大事故的停電范圍。給國民經(jīng)濟(jì)帶來嚴(yán)重的惡果,有時(shí)還可能造成人身和設(shè)備安全事故。因此,為了保證110kV變電站的正常運(yùn)行,必須根據(jù)《規(guī)程》來設(shè)置變電站所需要的保護(hù)裝置,并根據(jù)滿足選擇性、速動(dòng)性、靈敏性、可靠性進(jìn)行整定值,使整個(gè)系統(tǒng)的各種繼電保護(hù)有機(jī)協(xié)調(diào)地布置,正確地發(fā)揮作用。

      設(shè)計(jì)共分為六個(gè)章節(jié),第二章給出了系統(tǒng)的原始數(shù)據(jù)并確定了主接線方式;第三章介紹了各種繼電保護(hù)的原理;第四章為短路計(jì)算,確定系統(tǒng)短路時(shí)的短路電流;第五章為整定計(jì)算,為系統(tǒng)配備的各種繼電保護(hù)整定出動(dòng)作值。其中變壓器的主保護(hù)包括瓦斯保護(hù)和縱聯(lián)差動(dòng)保護(hù),后備保護(hù)包括復(fù)合電壓啟動(dòng)過電流保護(hù)、零序電流保護(hù)和過負(fù)荷保護(hù)。母線配備了母線完全電流差動(dòng)保護(hù),簡單可靠。110kV側(cè)線路配備了三段距離保護(hù),35kV側(cè)配備了三段距離保護(hù)和電流速斷保護(hù),10kV側(cè)只設(shè)置了電流速斷保護(hù)即可滿足要求。關(guān)鍵詞:配電系統(tǒng), 變電站, 電力系統(tǒng)繼電保護(hù), 短路電流,整定計(jì)算

      I ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      Abstract

      What this text mainly told is system disposition of relay protection of 110kV distribution, calculate whole definitely.At present, 110kV transformer substation to supply the masses of users with and assign the electric energy directly mainly, it is the final links of the whole power system including generate electricity , the power transmission and transformation and distribution.Because the power system takes place, supports, uses the characteristic at the same time , once the distribution system breaks down, the ones that cause the system to supply power to users break down, may make the whole power system influenced at the same time , even destroyed, cause the enormous economic losses.So must improve 110kV distribution dependability of system, apparatus to give transformer substation install movement reliable , rapidly , complete protection of performance, influence the trouble to confine to minimum range, guarantee to offer the lasting electric energy to users.The relay protection of power system and security automatics are important components of the power system.It operates and plays an extremely important role safly in users' incessant power supply steadily in the power system, the power system without relay protection can not run.The peace and steadiness that design and disposition of relay protection of power system influence the power system directly rationally runs.It design and it is the improper since it dispose,relay protection can movements correct,it thus not will expand by power cut range of accident.Bring the serious evil consequence to national economy, may also cause the apparatus incident of personal sum sometimes.So for guarantee 110kV normal running of transformer substation , must follow “ rules ” come , set up protector transformer substation need, and moving , sensitivity , dependability carry on whole definite value according to the alternative of meeting, rapidly, make various relay protection of the whole system fix up organically coordinating , function correctly.Design is divided into six chapters, the system is given in chapter II of the

      II ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      original data and determine the main wiring;third chapter describes the principles of various relay;fourth chapter short circuit calculations, determine the system's short circuit short circuit current;fifth chapter setting calculation, the system is equipped with a variety of protective relaying action value set.In which the main transformer protection, including gas conservation and differential protection, backup protection, including composite voltage start over-current protection, zero sequence current protection and overload protection.Bus equipped with a bus full current differential protection, simple and reliable.110kV side of the line with three distance relay, 35kV side with three distance relay and Current Protection, 10kV side only set the trip current protection requirements can be met.Keyword: distribution system , transformer substation , power system relay protection, short circuit electric current, complete calculation

      III ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      目 錄 緒論.............................................................1

      1.1 繼電保護(hù)的作用.............................................1 1.2 繼電保護(hù)系統(tǒng)設(shè)計(jì)基本要求...................................2 1.3 繼電保護(hù)裝置的組成.........................................3 2 原始數(shù)據(jù)及主接線介紹.............................................5 2.1 主變壓器及線路主要參數(shù).....................................5 2.2 變電站電氣主接線簡介.......................................7 3 繼電保護(hù)原理介紹.................................................9 3.1 變壓器保護(hù).................................................9 3.1.1 縱聯(lián)差動(dòng)保護(hù)..........................................9 3.1.2瓦斯保護(hù).............................................13 3.1.3復(fù)合電壓啟動(dòng)過電流保護(hù)...............................14 3.1.4 零序電流保護(hù).........................................15 3.1.5過負(fù)荷保護(hù)...........................................15 3.2 母線保護(hù)..................................................16 3.3 線路保護(hù)..................................................17 3.3.1 三段式電流保護(hù).......................................17 3.3.2相間距離保護(hù).........................................20 4 短路電流計(jì)算....................................................22 4.1短路計(jì)算說明...............................................22 4.2母線短路電流計(jì)算...........................................22 4.2.2三相對稱短路時(shí)的電流計(jì)算.............................23 4.2.3不對稱短路的電流計(jì)算.................................25 4.3線路短路電流計(jì)算...........................................27 4.3.1各線路阻抗參數(shù).......................................27 4.3.2 110kV線路短路電流計(jì)算...............................27 4.3.3 35kV線路短路電流計(jì)算................................29

      IV ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      4.3.4 10kV線路短路電流計(jì)算................................31 5 整定計(jì)算........................................................33 5.1線路最大負(fù)荷電流計(jì)算.......................................33 5.2主變壓器保護(hù)的整定計(jì)算.....................................35 5.2.1縱差動(dòng)保護(hù)整定計(jì)算...................................35 5.2.2 復(fù)合電壓啟動(dòng)過電流保護(hù)的整定計(jì)算.....................37 5.2.3 過負(fù)荷保護(hù)的整定計(jì)算.................................38 5.3 母線保護(hù)的整定計(jì)算........................................38 5.4 線路保護(hù)的整定計(jì)算........................................41 5.4.1 110kV線路保護(hù)的整定計(jì)算.............................41 5.4.2 35kV線路保護(hù)的整定計(jì)算..............................43 5.4.3 10kV線路保護(hù)整定計(jì)算................................47 6 總結(jié)............................................................51 致謝..............................................................52 參考文獻(xiàn)..........................................................53

      V ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書 緒 論

      1.1 繼電保護(hù)的作用

      電力系統(tǒng)在運(yùn)行中,可能發(fā)生各種故障和不正常運(yùn)行狀態(tài),最常見同時(shí)也是最危險(xiǎn)的故障是發(fā)生各種型式的短路。在發(fā)生短路時(shí)可能產(chǎn)生以下的后果: 1.通過故障點(diǎn)的很大的短路電流和所燃起的電弧,使故障元件損壞; 2.短路電流通過非故障元件,由于發(fā)熱和電動(dòng)力的作用,引起它們的損壞或縮短它們的使用壽命;

      3.電力系統(tǒng)中部分地區(qū)的電壓大大降低,破壞用戶工作的穩(wěn)定性或影響工廠產(chǎn)品質(zhì)量;

      4.破壞電力系統(tǒng)并列運(yùn)行的穩(wěn)定性,引起系統(tǒng)振動(dòng),甚至使整個(gè)系統(tǒng)瓦解;

      電氣元件的正常工作遭到破壞,但沒有發(fā)生故障,這種情況屬于不正常運(yùn)行狀態(tài)。例如,因負(fù)荷超過電氣設(shè)備的額定值而引起的電流升高(一般又稱過負(fù)荷),就是一種最常見的不正常運(yùn)行狀態(tài)。由于過負(fù)荷,使元件載流部分和絕緣材料的溫度不斷升高,加速絕緣的老化和損壞,就可能發(fā)展成故障。此外,系統(tǒng)中出現(xiàn)功率缺額而引起的頻率降低,發(fā)電機(jī)突然甩負(fù)荷而產(chǎn)生的過電壓,以及電力系統(tǒng)發(fā)生振蕩等,都屬于不正常運(yùn)行狀態(tài)。

      故障和不正常運(yùn)行狀態(tài),都可能在電力系統(tǒng)中引起事故。事故,就是指系統(tǒng)或其中一部分的正常工作遭到破壞,并造成對用戶少送電或電能質(zhì)量變壞到不能容許的地步,甚至造成人身傷亡和電氣設(shè)備的損壞。

      系統(tǒng)事故的發(fā)生,除了由于自然條件的因素(如遭受雷擊等)以外,一般者是由于設(shè)備制造上的缺陷、設(shè)計(jì)和安裝的錯(cuò)誤、檢修質(zhì)量不高或運(yùn)行維護(hù)不當(dāng)而引起的。因此,只要充分發(fā)揮人的主觀能動(dòng)性,正確地掌握客觀規(guī)律,加強(qiáng)對設(shè)備的維護(hù)和檢修,就可能大大減少事故發(fā)生的機(jī)率,把事故消滅在發(fā)生之前。

      在電力系統(tǒng)中,除應(yīng)采取各項(xiàng)積極措施消除或減少發(fā)生故障的可能性以外,故障一旦發(fā)生,必須迅速而有選擇性地切除故障元件,這是保證電力系統(tǒng)安全運(yùn)行的最有效方法之一。切除故障的時(shí)間常常要求小到十分之幾甚至百分之幾秒,實(shí)踐證明只有裝設(shè)在每個(gè)電氣元件上的保護(hù)裝置才有可能滿足這個(gè)要求。****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      這種保護(hù)裝置直到目前為止,大多是由單個(gè)繼電器或繼電器與其附屬設(shè)備的組合構(gòu)成的,故稱為繼電保護(hù)裝置。在電力式靜態(tài)保護(hù)裝置和數(shù)字式保護(hù)裝置出現(xiàn)以后,雖然繼電器已被電力元件計(jì)算機(jī)所代替,但仍沿用此名稱。在電業(yè)部門常用繼電保護(hù)一詞泛指繼電保護(hù)技術(shù)式由各種繼電保護(hù)裝置組成的繼電保護(hù)系統(tǒng)。繼電保護(hù)裝置一詞則指各種具體的裝置。

      繼電保護(hù)裝置,就是指能反應(yīng)電力系統(tǒng)中電氣元件發(fā)生故障或不正常運(yùn)行狀態(tài),并動(dòng)作于斷路器跳閘或發(fā)出信號(hào)的一種自動(dòng)裝置。它的基本任務(wù)是: 1.自動(dòng)、迅速、有選擇性地將故障元件從電力系統(tǒng)中切除,使故障元件免于繼續(xù)遭到破壞,保證其它無故障部分迅速恢復(fù)正常運(yùn)行;

      2.反應(yīng)電氣元件的不正常運(yùn)行狀態(tài),并根據(jù)運(yùn)行維護(hù)的條件(例如有無經(jīng)常值班人員),而動(dòng)作于發(fā)出信號(hào)、減負(fù)荷或跳閘。此時(shí)一般不要求保護(hù)迅速動(dòng)作,而是根據(jù)對電力系統(tǒng)及其元件的危害程度規(guī)定一定的延時(shí),以免不必要的動(dòng)作和由于干擾而引起的誤動(dòng)作。

      1.2 繼電保護(hù)系統(tǒng)設(shè)計(jì)基本要求

      電網(wǎng)對繼電保護(hù)的基本要求是可靠性、選擇性、快速性、靈敏性,即通常所說的“四性”,這些要求之間,有的相輔相成、有的相互制約,需要對不同的使用條件分別進(jìn)行協(xié)調(diào)。

      (l)可靠性:是對繼電保護(hù)最基本的性能要求,它又可分為可信賴性和安全性2個(gè)方面。可信賴性要求繼電保護(hù)在異?;蚬收锨闆r下,能準(zhǔn)確地完成設(shè)計(jì)所要求的動(dòng)作;安全性要求繼電保護(hù)在非設(shè)計(jì)所要求動(dòng)作的所有情況下,能夠可靠地不動(dòng)作。

      (2)選擇性:是指在對電網(wǎng)影響可能最小的地方,實(shí)現(xiàn)斷路器的控制操作,以終止故障或電網(wǎng)事故的發(fā)展。如對電力設(shè)備的繼電保護(hù),當(dāng)電力設(shè)備故障時(shí),要求最靠近故障點(diǎn)的斷路器動(dòng)作斷開電網(wǎng)的供電電源,即電力設(shè)備繼電保護(hù)的選擇性。選擇性除了決定于繼電保護(hù)裝置本身的性能外,還要求滿足從電源算起,愈靠近故障點(diǎn),其繼電保護(hù)裝置的故障啟動(dòng)值愈小,動(dòng)作時(shí)間愈短;而對振蕩解列裝置,則要求當(dāng)電網(wǎng)失去同步穩(wěn)定性時(shí),其所動(dòng)作的斷路器斷開點(diǎn),在解列后兩側(cè)電網(wǎng)可以各自安全地同步運(yùn)行,從而終止振蕩等。

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      (3)快速性:是指繼電保護(hù)應(yīng)以允許的可能最快的速度動(dòng)作于斷路器跳閘,以斷開故障或終止異常狀態(tài)的發(fā)展。繼電保護(hù)快速動(dòng)作可以減輕故障元件的損壞程度,提高線路故障后自動(dòng)重合閘的成功率,并特別有利于故障后的電力系統(tǒng)同步運(yùn)行的穩(wěn)定性。快速切除線路和母線的短路故障,是提高電力系統(tǒng)暫態(tài)穩(wěn)定的最重要手段。

      (4)靈敏性:是指繼電保護(hù)對設(shè)計(jì)規(guī)定要求動(dòng)作的故障和異常狀態(tài)能夠可靠動(dòng)作的能力。故障時(shí)進(jìn)入裝置的故障量與給定的裝置啟動(dòng)值之比,為繼電保護(hù)的靈敏系數(shù),它是考核繼電保護(hù)靈敏性的具體指標(biāo),在一般的繼電保護(hù)設(shè)計(jì)與運(yùn)行規(guī)程中都有具體的規(guī)定要求。

      1.3 繼電保護(hù)裝置的組成

      一般而言,整套繼電保護(hù)裝置由測量元件、邏輯環(huán)節(jié)和執(zhí)行輸出三部分組 成,如圖1.1所示,分述如下。

      圖1.1繼電保護(hù)裝置的組成

      (1)測量比較部分

      測量比較部分是測量通過被保護(hù)的電氣元件的物理參量,并與給定的值進(jìn)行比較,根據(jù)比較的結(jié)果,給出“是”、“非”(“0”或“1”)性質(zhì)的一組邏輯信

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      號(hào),從而判斷保護(hù)裝置是否應(yīng)該啟動(dòng)。

      (2)邏輯部分

      邏輯部分使保護(hù)裝置按一定的邏輯關(guān)系判斷故障的范圍和類型,最后確定 是應(yīng)該使斷路器跳閘、發(fā)出信號(hào)或是不動(dòng)作及是否延時(shí)等,并將對應(yīng)的指令傳給執(zhí)行輸出部分。

      (3)執(zhí)行輸出部分

      執(zhí)行輸出部分根據(jù)邏輯部分傳來的指令,最后完成保護(hù)裝置所擔(dān)負(fù)的任務(wù)。如在故障時(shí)動(dòng)作于跳閘;不正常運(yùn)行時(shí)發(fā)出信號(hào);而在正常運(yùn)行時(shí)不動(dòng)作等。

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書 原始數(shù)據(jù)及主接線介紹

      2.1 主變壓器及線路主要參數(shù)

      1、主變壓器參數(shù)如下:

      型號(hào):SSZ9 31500/110 額定電壓:110±8×1.25%/38.5±2×2.5%/10.5 容量比:100/100/100 參數(shù):Uk1-2%=10.5 Uk1-3%=17.5 Uk2-3%=6.5 接線方式:YN,yd,d11

      2、系統(tǒng)示意圖及各側(cè)出線參數(shù):

      圖2.1系統(tǒng)示意圖

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      表2-1 110kV側(cè)出線參數(shù)

      線型 Pmax(MW)Pmin(MW)COSΦ L(km)1 LGJ-300 50 40 0.86 50 2 LGJ-300 60 45 0.86 60 3 LGJ-150 55 42 0.86 50 4 LGJ-150 48 35 0.86 40 表2-2 35kV側(cè)出線參數(shù)

      線型 Pmax(MW)回路數(shù) COSΦ L(km)供電方式 1 LGJ-120 14 1 0.8 12 架空 2 LGJ-120 15 1 0.8 15 架空 3 LGJ-120 27 1 0.85 8 架空 4 LGJ-120 18 1 0.85 6 架空 5 LGJ-120 17 1 0.8 10 架空 6 LGJ-120 25 1 0.85 12 架空 表2-3 10kV側(cè)出線參數(shù)

      線型 Pmax(MW)回路數(shù) COSΦ L(km)供電方式 1 LGJ-120 5 1 0.8 6 架空 2 LGJ-120 4 1 0.8 4 架空 3 LGJ-120 3 1 0.8 3 架空 4 LGJ-120 8 1 0.8 8 架空 5 LGJ-120 4 1 0.8 7 架空 6 LGJ-120 5 1 0.8 5 架空 7 LGJ-120 7 1 0.8 8 架空 8 LGJ-120 3 1 0.8 9 架空

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      2.2 變電站電氣主接線簡介

      電氣主接線是由各種電氣設(shè)備及其接線組成,用以接收和分配電能,是供電系統(tǒng)的重要組成部分。它與電源的回路數(shù),電壓等級和負(fù)荷的大小、級別以及所用變壓器的臺(tái)數(shù)、容量等因素有關(guān)。確定變電所的主接線對變電所電器設(shè)備的選擇,配電裝置的布置及運(yùn)行的可靠性與經(jīng)濟(jì)性等都有密切的關(guān)系,主接線設(shè)計(jì)是變電所設(shè)計(jì)中的重要任務(wù)之一。

      1、電氣主接線設(shè)計(jì)原則

      電氣主接線設(shè)計(jì)時(shí),所遵循的原則:符合設(shè)計(jì)任務(wù)書的要求,符合有關(guān)的方針,政策和技術(shù)規(guī)范,規(guī)程;結(jié)合具體工程特點(diǎn),設(shè)計(jì)出技術(shù)經(jīng)濟(jì)合理的主接線。根據(jù)以上原則于任務(wù)書本設(shè)計(jì)主接線方案應(yīng)達(dá)到以下要求:

      一、根據(jù)變電所在電力系統(tǒng)中的地位,作用和用戶性質(zhì),應(yīng)滿足電力負(fù)荷,特別是其中一、二及負(fù)荷對供電的可靠性要求,保證必要的供點(diǎn)可靠性。

      二、主接線應(yīng)力求接線簡單,運(yùn)行靈活與操作方便。應(yīng)能適應(yīng)必要的各種運(yùn)行方式,便于切換操作和檢修,切適應(yīng)負(fù)荷的發(fā)展。

      三、應(yīng)符合有關(guān)國家標(biāo)準(zhǔn)和技術(shù)規(guī)范的要求,能充分保證運(yùn)行,維護(hù)和檢修的安全和方便,保證人身和設(shè)備的安全。

      四、在保證以上幾項(xiàng)要求的條件下,應(yīng)盡量使主接線簡單,降低投資,節(jié)省運(yùn)行費(fèi)用。節(jié)約電能和有色金屬的消耗量。

      五、滿足擴(kuò)建的要求。

      2、電氣主接線方案比較及選擇

      (1)110kV側(cè)主接線方案

      對于僅有兩條到四條110 kV出線的變電所,由于110 kV開關(guān)站間隔不多,主接線不宜設(shè)計(jì)得過于復(fù)雜,同時(shí)各個(gè)主變應(yīng)考慮接在同一條母線上,以減小兩臺(tái)主變同時(shí)失去的可能性。故從各個(gè)方面綜合考慮,單母線接線是一種相對合理的選擇。

      單母線接線中,主變110 kV側(cè)設(shè)開關(guān),各側(cè)有一套斷路器,各主變間通過母線連接,以減小兩臺(tái)主變同時(shí)跳閘的概率。

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      結(jié)合本站實(shí)際,從接線的可靠性、靈活性、經(jīng)濟(jì)性等進(jìn)行全面比較后,最終采用了單母線分段的接線方案。

      (2)35kV側(cè)主接線方案

      電壓等級為35kV~60kV,出線為4~8回,可采用單母線分段接線。當(dāng)一段母線發(fā)生故障時(shí),分段斷路器自動(dòng)將故障段隔離,保證正常段母線不間斷供電,不致使重要用戶停電,可提高供電可靠性和靈活性。

      經(jīng)分析35kV側(cè)采用單母線分段接線,既考慮了供電可靠性又考慮了經(jīng)濟(jì)性。

      (3)10kV側(cè)主接線方案

      6~10kV配電裝置出線回路數(shù)目為6回及以上時(shí),可采用單母線分段接線。

      2、主接線的最終確定(1)110kV接線

      出線四回,采用單母分段接線。(2)35kV接線

      出線六回,采用單母分段接線。(3)10kV接線

      出線八回,采用單母分段接線。(4)系統(tǒng)參數(shù)(電源)

      110KV側(cè)Sn=5210MVA 等值電抗Xd=0.0192

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書 繼電保護(hù)原理介紹

      3.1 變壓器保護(hù)

      變壓器是電力系統(tǒng)普遍使用的重要電氣設(shè)備。它的安全運(yùn)行直接關(guān)系到電力系統(tǒng)供電和穩(wěn)定運(yùn)行,特別是大容量變壓器,一旦因故障而損壞造成的損失就更大。因此必須針對變壓器的故障和異常工作情況,根據(jù)其容量和重要程度,裝設(shè)動(dòng)作可靠,性能良好的繼電保護(hù)裝置。一般包括:

      1.反映內(nèi)部短路和油面降低的非電量(氣體)保護(hù),又稱瓦斯保護(hù)。2.反映變壓器繞組和引出線的多相短路及繞組匝間短路的縱聯(lián)差動(dòng)保護(hù),或電流速斷保護(hù)。

      3.作為變壓器外部相間短路和內(nèi)部短路的后備保護(hù)的過電流保護(hù)(或帶有復(fù)合電壓起動(dòng)的過電流保護(hù)或負(fù)序電流保護(hù)或阻抗保護(hù))。

      4.反映中性點(diǎn)直接接地系統(tǒng)中外部接地短路的變壓器零序電流保護(hù)。5.反映大型變壓器過勵(lì)磁的變壓器過勵(lì)磁保護(hù)及過電壓保護(hù)。6.反映變壓器過負(fù)荷的變壓器過負(fù)荷(信號(hào))保護(hù)。7.反映變壓器非全相運(yùn)行的非全相保護(hù)。

      3.1.1 縱聯(lián)差動(dòng)保護(hù)

      變壓器的縱差動(dòng)保護(hù)主要用來反應(yīng)變壓器繞組及其套管、引出線上的相間短路,同時(shí)也可以反應(yīng)變壓器繞組匝間短路及中性點(diǎn)直接接地系統(tǒng)側(cè)繞組、套管、引出線的單相接地短路。

      本次設(shè)計(jì)所采用的變壓器型號(hào)均為:SSZ9 31500/110對于這種大型變壓器而言,它都必需裝設(shè)單獨(dú)的變壓器差動(dòng)保護(hù),這是因?yàn)樽儔浩鞑顒?dòng)保護(hù)通常采用三側(cè)電流差動(dòng),其中高電壓側(cè)電流引自高壓熔斷器處的電流互感器,中低壓側(cè)電流分別引自變壓器中壓側(cè)電流互感器和低壓側(cè)電流互感器,這樣使差動(dòng)保護(hù)的保護(hù)范圍為三組電流互感器所限定的區(qū)域,從而可以更好地反映這些區(qū)域內(nèi)相間短路,高壓側(cè)接地短路以及主變壓器繞組匝間短路故障。所以我們用縱聯(lián)差動(dòng)保護(hù)作為兩臺(tái)變壓器的主保護(hù),其接線原理圖如圖3.1。正常情況下,I'2=I''2即:

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      'I1''''n2I1I1??????nT(變壓器變比)

      'n1n1n2I1所以這時(shí)Ir=0,實(shí)際上,由于電流繼電器接線方式,變壓器勵(lì)磁電流,變比誤差等影響導(dǎo)致不平衡電流的產(chǎn)生,故Ir不等于0,針對不平衡電流產(chǎn)生的原因不同可以采取相應(yīng)的措施來減小。

      盡管縱聯(lián)差動(dòng)保護(hù)有很多其它保護(hù)不具備的優(yōu)點(diǎn),但當(dāng)大型變壓器內(nèi)部產(chǎn)生嚴(yán)重漏油或匝數(shù)很少的匝間短路故障以及繞組斷線故障時(shí),縱聯(lián)差動(dòng)保護(hù)不能動(dòng)作,這時(shí)我們還需對變壓器裝設(shè)另外一個(gè)主保護(hù)——瓦斯保護(hù)。

      圖3.1 縱聯(lián)差動(dòng)保護(hù)原理示意圖

      保護(hù)的構(gòu)成:主要由帶短路線圈的BCH-2型差動(dòng)繼電器構(gòu)成; 保護(hù)的電流互感器:接至變壓器三側(cè)的斷路器內(nèi)側(cè);

      保護(hù)裝置的保護(hù)范圍:除了變壓器本身外還包括變壓器至三側(cè)斷路器之間的連線;

      保護(hù)動(dòng)作:跳開變壓器三側(cè)的斷路器;

      保護(hù)的動(dòng)作時(shí)限:保護(hù)裝置本身的動(dòng)作時(shí)間(即0秒切除故障);

      變壓器縱聯(lián)差動(dòng)保護(hù)整定原則如下:

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      (1)按平均電壓(變壓器額定電壓及變壓器最大額定容量)計(jì)算各側(cè)二次額定電流,完成主變電流互感器參數(shù)、額定電流、平衡系數(shù)的計(jì)算。1)一次側(cè)額定電流

      IN1?SN3UN

      (3-1)

      式中

      SN——變壓器額定容量。由設(shè)計(jì)任務(wù)書知為40MVA;

      UN——變壓器各側(cè)額定電壓; 2)選擇電流互感器變比為

      nTACal?KjxIN(3-2)

      式中

      Kjx——為電流互感器接線系數(shù)。當(dāng)三角形接線時(shí),Kjx?3;當(dāng)為星形接線時(shí),Kjx?1。

      選擇標(biāo)準(zhǔn)變比nTA?nTACal 3)二次側(cè)額定電流

      IN2?KjxIN1nTA

      (3-3)

      式中

      Kjx——為電流互感器接線系數(shù)。當(dāng)三角形接線時(shí),Kjx?3;當(dāng)為星形接線時(shí),Kjx?1。

      (2)計(jì)算各側(cè)外部短路時(shí)的短路電流值

      按短路電流計(jì)算方法進(jìn)行各側(cè)短路電流值的計(jì)算(3)計(jì)算差動(dòng)保護(hù)的動(dòng)作電流

      按下述條件計(jì)算差動(dòng)保護(hù)的動(dòng)作電流,并選取最大者。

      1)按躲過變壓器空投時(shí)和外部故障切除后電壓恢復(fù)時(shí)變壓器產(chǎn)生的勵(lì)磁涌流計(jì)算,即

      Idz?KkIeb

      (3-4)

      式中

      Idz——保護(hù)動(dòng)作電流;

      Ieb——變壓器額定電流(折算至基本側(cè));

      Kk——可靠系數(shù),取1.3。

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      2)按躲過外部短路時(shí)的最大不平衡電流計(jì)算,即

      Idz?KkIbp

      (3-5)

      式中

      Ibp——不平衡電流;

      Kk——可靠系數(shù),取1.3。

      3)按躲過電流互感器二次回路斷線時(shí)計(jì)算,即

      Idz?1.3Ifh.max

      (3-6)

      式中

      Ifh.max——正常運(yùn)行時(shí)變壓器的最大負(fù)荷電流。當(dāng)不能確定時(shí),采用變壓器額定電流。

      計(jì)算中,各側(cè)所有的短路電流均應(yīng)歸算到基本側(cè)。這樣求出的是基本側(cè)的動(dòng)作電流計(jì)算值(Idz.jb.js)。

      選用上述三條件算得的保護(hù)動(dòng)作電流的最大值作為計(jì)算值。(4)基本側(cè)繼電器線圈匝數(shù)計(jì)算

      三繞組變壓器基本側(cè)直接接差動(dòng)線圈,其余兩側(cè)接相應(yīng)的平衡繞圈。基本側(cè)繼電器動(dòng)作電流計(jì)算為

      Idzj.jb.js?(Idzj.bh.jb.js?Kjx)/nLH.jb

      (3-7)

      式中

      Idzj.jb.js——基本側(cè)繼電器動(dòng)作電流計(jì)算值;

      Idz.jb.js——基本側(cè)保護(hù)動(dòng)作計(jì)算值;

      nLH.jb——基本側(cè)電流互感器變比;

      Kjx——電流互感器的接線系數(shù)?;緜?cè)繼電器線圈匝數(shù)(差動(dòng)線圈匝數(shù))計(jì)算為

      Wg.jb.js?Wcd.js?AW0Idzj.jb.js?60Idzj.jb.js

      (3-8)

      式中

      AW0——繼電器的動(dòng)作安匝,一般可用實(shí)測值。若無此值,可采用額定值,即AW0?60;

      Wcd.js——差動(dòng)線圈匝數(shù)計(jì)算值(直接接基本側(cè))。接繼電器線圈實(shí)有抽頭,選用較計(jì)算值小而相近的抽頭匝數(shù),作為差動(dòng)線圈的整定匝數(shù)(Wcd.z)。

      基本側(cè)實(shí)際的繼電器動(dòng)作電流計(jì)算為

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      Idzj.jb?AW0

      (3-9)Wcd.z

      保護(hù)的實(shí)際動(dòng)作電流計(jì)算

      Idz.jb?Idzj.jbnLH

      (3-10)Kjx式中

      nLH——電流互感器變比;

      Kjx——為電流互感器接線系數(shù)。當(dāng)三角形接線時(shí),Kjx?3;當(dāng)為星形接線時(shí),Kjx?1。

      (5)保護(hù)靈敏度計(jì)算,即

      Klm?KconIk?.min?

      2(3-11)

      Iop.b式中

      Ik?.min——變壓器內(nèi)部故障時(shí),歸算至基本側(cè)總的最小短路電流;若為單電源變壓器,應(yīng)為歸算至電源側(cè)的最小短路電流;

      Kcon——接線系數(shù);

      Iop.b——基本側(cè)保護(hù)一次動(dòng)作電流;若為單側(cè)電源變壓器,應(yīng)為電源側(cè)保護(hù)一次動(dòng)作電流。

      3.1.2瓦斯保護(hù)

      瓦斯保護(hù)主要用來保護(hù)變壓器的內(nèi)部故障,它由于一方面簡單,靈敏,經(jīng)濟(jì);另一方面動(dòng)作速度慢,且僅能反映變壓器油箱內(nèi)部故障,就注定了它只有與差動(dòng)保護(hù)配合使用才能做到優(yōu)勢互補(bǔ),共同構(gòu)成變壓器的主保護(hù)。(1)瓦斯保護(hù)的工作原理:

      瓦斯保護(hù)的測量元件是瓦斯繼電器。瓦斯繼電器安裝于變壓器油箱和油枕的通道上,當(dāng)變壓器內(nèi)部故障時(shí),故障點(diǎn)的局部溫度將使變壓器油溫上升,體積膨脹,甚至出現(xiàn)沸騰,有熱空氣被排出而形成上升氣流,在故障點(diǎn)產(chǎn)生電弧,則變壓器油和絕緣材料將分解出大量氣體,這些氣體自油箱流向油枕上部,故障程度越嚴(yán)重,產(chǎn)生的氣體越多,流向油枕的氣流速度越快,甚至氣流中還夾雜著變壓器油,利用上述氣體來實(shí)現(xiàn)的保護(hù)裝置叫瓦斯保護(hù)。

      為了便于氣體順利通過瓦斯繼電器,在安裝時(shí)應(yīng)使變壓器油箱頂蓋及連接

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      管與水平面稍有傾斜。

      當(dāng)變壓器內(nèi)部發(fā)生輕微故障時(shí),有輕瓦斯產(chǎn)生,瓦斯繼電器KG的上觸點(diǎn)閉合,作用于預(yù)告信號(hào);當(dāng)發(fā)生嚴(yán)重故障時(shí),重瓦斯沖出,瓦斯繼電器的下觸點(diǎn)閉合,經(jīng)中間繼電器KC作用于信號(hào)繼電器KS,發(fā)出警報(bào)信號(hào),同時(shí)斷路器跳閘。瓦斯繼電器的下觸點(diǎn)閉合,也可利用切換片XB切換位置,只給出報(bào)警信號(hào)。(2)瓦斯保護(hù)的整定:

      瓦斯保護(hù)有重瓦斯和輕瓦斯之分,它們裝設(shè)于油箱與油枕之間的連接導(dǎo)管上。其中輕瓦斯按氣體容積進(jìn)行整定,整定范圍為:250~300cm3,一般整定在250cm3。重瓦斯按油流速度進(jìn)行整定,整定范圍為:0.6~1.5m/s,一般整定在1m/s。瓦斯保護(hù)原理如圖3.2所示。

      圖3.2 瓦斯保護(hù)原理示意圖

      3.1.3復(fù)合電壓啟動(dòng)過電流保護(hù)

      當(dāng)靈敏度不滿足要求時(shí)宜采用復(fù)合電壓起動(dòng)的過電流保護(hù)(1)安裝在高壓側(cè)的過電流保護(hù): 保護(hù)的構(gòu)成:主要由電流繼電器組成;

      保護(hù)裝置的作用:作為變壓器本身主保護(hù)的后備以及相鄰元件的后備; 保護(hù)的電流互感器:安裝在變壓器高壓側(cè);

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      保護(hù)的動(dòng)作時(shí)限:

      第一段時(shí)限使中壓側(cè)斷路器跳開(即0.5秒切除故障); 第二段時(shí)限使變壓器三側(cè)的斷路器跳開(即1秒切除故障);

      保護(hù)構(gòu)成:主要由電流繼電器、低電壓繼電器和負(fù)序電壓繼電器組成; 保護(hù)裝置的作用:作為變壓器本身主保護(hù)的后備以及相鄰元件的后備;(2)安裝在高壓側(cè)復(fù)合電壓起動(dòng)電流保護(hù):

      保護(hù)的電流互感器:安裝在變壓器高壓側(cè);

      保護(hù)的電壓互感器:安裝在變壓器中壓側(cè);

      保護(hù)的動(dòng)作時(shí)限:

      第一段時(shí)限使中壓側(cè)斷路器跳開(即0.5秒切除故障); 第二段時(shí)限使變壓器三側(cè)的斷路器跳開(即1秒切除故障)

      3.1.4 零序電流保護(hù)

      在中性點(diǎn)直接接地系統(tǒng)中,接地短路是常見的故障形式,所以處于該系統(tǒng)中的變壓器要裝設(shè)接地(零序)保護(hù),以反映變壓器高壓繞組、引出線上的接地短路,并作為變壓器主保護(hù)和相鄰母線、線路接地保護(hù)的后備保護(hù)。

      對降壓變壓器,如果中、低壓側(cè)沒有電源(無發(fā)電機(jī))時(shí),即使中性點(diǎn)接地運(yùn)行,其中性點(diǎn)的零序電流保護(hù)也沒必要運(yùn)行。

      3.1.5過負(fù)荷保護(hù)

      為防御變壓器差動(dòng)保護(hù)范圍外的相間短路引起變壓器過流,應(yīng)裝設(shè)變壓器過流保護(hù),如果變壓器過負(fù)荷時(shí)間過長將引起變壓器過電流,勢必影響繞組絕緣的壽命,因此還應(yīng)加裝過負(fù)荷保護(hù)。

      保護(hù)構(gòu)成:主要由電流繼電器組成; 保護(hù)的電流互感器:安裝在變壓器高壓側(cè)上;

      保護(hù)裝置的作用:作為變壓器本身主保護(hù)的后備以及相鄰元件的后備; 保護(hù)動(dòng)作:發(fā)出變壓器過負(fù)荷信號(hào);

      保護(hù)的動(dòng)作時(shí)限:比變壓器復(fù)合電壓起過電流保護(hù)的動(dòng)作時(shí)限大0.5秒(即1秒);

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      3.2 母線保護(hù)

      母線故障是電氣設(shè)備最嚴(yán)重的故障之一,它將使連接于故障母線上的所有設(shè)備被迫停電。當(dāng)未裝設(shè)專用的母線保護(hù)時(shí),如果母線故障,只能依靠相鄰元件保護(hù)的后備作用切除故障,這將延長故障切除時(shí)間,并且往往會(huì)擴(kuò)大停電范圍,對高壓電網(wǎng)安全運(yùn)行不利,因此在35~500KV的發(fā)電廠或變電所母線上,應(yīng)裝設(shè)專用的母線保護(hù)裝置。

      由設(shè)計(jì)的已知條件可知,110kV母線均是采用單母線接線,對于單母線我們可以采用母線完全電流差動(dòng)保護(hù)。

      母線完全差動(dòng)保護(hù)的原理接線圖如圖3.5所示,和其它元件的差動(dòng)保護(hù)一樣,也是按環(huán)流法的原理構(gòu)成。在母線的所有連接元件上必須裝設(shè)專用的電流互感器,而且這些電流互感器的變比和特性完全相同,并將所有電流互感器的二次繞組在母線側(cè)的端子互相連接,在外側(cè)的端子也互相連接,差動(dòng)繼電器則接于兩連接線之間,差動(dòng)電流繼電器中流過的電流是所有電流互感器二次電流的相量和。這樣,在一次側(cè)電流總和為零時(shí),在理想的情況下,二次側(cè)電流的總和也為零。此圖為母線外部K點(diǎn)短路的電流分布圖,設(shè)電流流進(jìn)母線的方向?yàn)檎较?。圖中線路I,II接于系統(tǒng)電源,而線路III則接于負(fù)載。

      圖3.4 母線完全電流差動(dòng)保護(hù)的原理接線圖

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      3.3 線路保護(hù)

      3.3.1 三段式電流保護(hù)

      (1)瞬時(shí)(無時(shí)限)電流速斷保護(hù) 1)整定計(jì)算

      瞬時(shí)電流速斷保護(hù)(又稱第Ⅰ段電流保護(hù))它是反映電流升高,不帶時(shí)限動(dòng)作的一種電流保護(hù)。

      在單側(cè)電源輻射形電網(wǎng)各線路的始端裝設(shè)有瞬時(shí)電流速斷保護(hù)。當(dāng)系統(tǒng)電源電勢一定,線路上任一點(diǎn)發(fā)生短路故障時(shí),短路電流的大小與短路點(diǎn)至電源之間的電抗(忽略電阻)及短路類型有關(guān),三相短路和兩相短路時(shí),流過保護(hù)安裝地點(diǎn)的短路電流為

      Ik?3??Es(3-12)

      Xs?X1lEs3?(3-13)2Xs?X1lIk?2??式中 Es——系統(tǒng)等效電源相電勢;

      Xs——系統(tǒng)等效電源到保護(hù)安裝處之間的電抗;

      X1——線路單位公里長度的正序電抗;

      l——短路點(diǎn)至保護(hù)安裝處的距離,km。

      電流速斷保護(hù)的動(dòng)作電流可按大于本線路末端短路時(shí)流過保護(hù)安裝處的最大短路電流來整定,即

      11Iop?K1relIkB.max(3-14)

      1式中 Iop又稱一次動(dòng)1——保護(hù)裝置Ⅰ段瞬時(shí)電流速斷保護(hù)的動(dòng)作電流,作電流;

      1Krel——可靠系數(shù),考慮到繼電器的整定誤差、短路電流計(jì)算誤差和非周期分量的影響等而引入的大于1的系數(shù),一般取1.2~1.3;IkB.max——被保護(hù)線路末端B母線上三相短路時(shí)流過保護(hù)安裝處的最大短路電流,一般取次暫態(tài)短路電流周期分量的有效值。2)靈敏系數(shù)的校驗(yàn)

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      瞬時(shí)電流速斷保護(hù)的靈敏系數(shù),是用其最小保護(hù)范圍來衡量的,規(guī)程規(guī)定,最小保護(hù)范圍lmin不應(yīng)小于線路全長的15%~20%。

      由上得最小保護(hù)長度

      lmin?1Es(1?Xs.max)(3-15)X1Iop1式中 Xs.max——系統(tǒng)最小運(yùn)行方式下,最大等值電抗,?;

      X1——輸電線路單位公里正序電抗,?/km。同理,最大保護(hù)長度

      lmax?E1(1s?Xs.min)X1Iop1(3-16)

      式中 Xs.min——系統(tǒng)最大運(yùn)行方式下,最小等值電抗,?;

      通常規(guī)定,最大保護(hù)范圍lmax?50%l(l為被保護(hù)線路長度),最小保護(hù)范圍lmin?(15%~20%)l時(shí),才能裝設(shè)瞬時(shí)電流速斷保護(hù)。(2)限時(shí)電流速斷保護(hù)

      由于瞬時(shí)電流速斷保護(hù)不能保護(hù)線路全長,因此可增加一段帶時(shí)限的電流速斷保護(hù)(又稱第Ⅱ段電流保護(hù))。用以保護(hù)瞬時(shí)電流速斷保護(hù)保護(hù)不到的那段線路,因此,要求限時(shí)電流速斷保護(hù)應(yīng)能保護(hù)線路全長。1)整定計(jì)算

      限時(shí)電流速斷保護(hù)的動(dòng)作電流IⅡop1應(yīng)大于相鄰支路的瞬時(shí)電流速斷保護(hù)的ⅡⅠ動(dòng)作電流IⅠop2,即Iop1?Iop2,寫成等式為

      ⅡⅠIⅡ?Kop1relIop2(3-17)

      式中 KⅡrel——配合系數(shù),因考慮短路電流非周期分量已經(jīng)衰減,一般取1.1~1.2。

      2)靈敏系數(shù)的校驗(yàn)

      其計(jì)算公式為

      Ksen?Ik.min(3-18)ⅡIop 18 ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      式中 Ik.min——在被保護(hù)線路末端短路時(shí),流過保護(hù)安裝處的最小短路電流;

      IⅡop——被保護(hù)線路的限時(shí)電流速斷保護(hù)的動(dòng)作電流。規(guī)程規(guī)定,Ksen?1.3~1.5。3)時(shí)限整定

      Ⅱ?yàn)榱吮WC選擇性,保護(hù)1的限時(shí)電流速斷保護(hù)的動(dòng)作時(shí)限t1,還要與保護(hù)2的瞬時(shí)電流速斷保護(hù)、保護(hù)3的差動(dòng)保護(hù)(或瞬時(shí)電流速斷保護(hù))動(dòng)作時(shí)限tⅠ

      2、tⅠ3相配合,即

      Ⅱt1?tⅠ2??t Ⅱt1?tⅠ3??t

      式中 ?t——時(shí)限級差。

      對于不同型式的斷路器及保護(hù)裝置,?t在0.3~0.6s范圍內(nèi)。

      (3)定時(shí)限過電流保護(hù) 1)整定計(jì)算

      定時(shí)限過電流保護(hù)動(dòng)作電流整定一般應(yīng)按以下兩個(gè)原則來確定: A.在被保護(hù)線路通過最大正常負(fù)荷電流時(shí),保護(hù)裝置不應(yīng)動(dòng)作,即

      ⅢIop1?IL.max(3-19)

      B.為保證在相鄰線路上的短路故障切除后,保護(hù)能可靠地返回,保護(hù)裝置的返回電流Ire應(yīng)大于外部短路故障切除后流過保護(hù)裝置的最大自起動(dòng)電流Is.max,即

      Ire?Is.max(3-20)

      根據(jù)第B條件,過電流保護(hù)的整定式為

      Iop1ⅢⅢKrelKss?IL.max

      (3-21)

      KreⅢ式中 Krel——可靠系數(shù),取1.15~1.25;

      Kss——負(fù)荷自起動(dòng)系數(shù),由電網(wǎng)電壓及負(fù)荷性質(zhì)所決定,取2~5;

      Kre——返回系數(shù),與保護(hù)類型有關(guān)。電流繼電器的返回系數(shù)一般取0.85~0.95;

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      IL.max——最大負(fù)荷電流。2)靈敏系數(shù)的校驗(yàn)

      其計(jì)算公式為

      Ksen?Ik.min(3-22)ⅢIop當(dāng)過電流保護(hù)作為本線路主保護(hù)的近后備保護(hù)時(shí),Ik.min應(yīng)采用最小運(yùn)行方式下,本線路末端兩相短路的短路電流來進(jìn)行校驗(yàn),要求Ksen?1.3~1.5;當(dāng)過電流保護(hù)作為相鄰線路的遠(yuǎn)后備保護(hù)時(shí),Ik.min應(yīng)采用最小運(yùn)行方式下,相鄰線 路末端兩相短路時(shí)的短路電流來進(jìn)行校驗(yàn),要求Ksen?1.2;作為y,d連接的變壓器遠(yuǎn)后備保護(hù)時(shí),短路類型應(yīng)根據(jù)過電流保護(hù)接線而定。3)時(shí)限整定

      為了保證選擇性,過電流保護(hù)的動(dòng)作時(shí)限按階梯原則進(jìn)行整定,這個(gè)原則是從用戶到電源的各保護(hù)裝置的動(dòng)作時(shí)限逐級增加一個(gè)?t。

      在一般情況下,對于線路Ln的定時(shí)限過電流保護(hù)動(dòng)作時(shí)限整定的一般表達(dá)式為

      tn?t(n?1).max??t(3-23)

      式中 tn——線路Ln過電流保護(hù)的動(dòng)作時(shí)間,s;

      t(n?1).max——由線路Ln供電的母線上所接的線路、變壓器的過電流保護(hù)最長動(dòng)作時(shí)間,s。

      3.3.2相間距離保護(hù)

      電流保護(hù)的主要優(yōu)點(diǎn)是簡單,可靠,經(jīng)濟(jì),但它的靈敏性受系統(tǒng)運(yùn)行方式變化的影響較大,特別是在重負(fù)荷,長距離,電壓等級高的復(fù)雜網(wǎng)絡(luò)中,很難滿足選擇性,靈敏性以及快速切除故障的要求,為此,必須采用性能完善的保護(hù)裝置,因而就引入了“距離保護(hù)”。

      距離保護(hù)是反饋故障點(diǎn)至保護(hù)安裝點(diǎn)之間的距離或阻抗,并根據(jù)距離的遠(yuǎn)近而確定動(dòng)作時(shí)間的一種保護(hù)裝置。該裝置的主要元件為距離或阻抗繼電器,它可根據(jù)其端子所加的電壓和電流側(cè)知保護(hù)安裝處至短路點(diǎn)之間的阻抗值,此

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      阻抗稱為阻抗繼電器的測量阻抗。其主要特點(diǎn)是:短路點(diǎn)距離保護(hù)安裝點(diǎn)越近,其測量阻抗越??;相反地,短路點(diǎn)距離保護(hù)安裝點(diǎn)越遠(yuǎn),其測量阻抗越大,動(dòng)作時(shí)間就越長。這樣就可保證有選擇地切除故障線路,如圖5.6所示,K點(diǎn)短路時(shí),保護(hù)1的測量阻抗是Zk,保護(hù)2的測量阻抗是(ZAB+ZK)。由于保護(hù)1距離短路點(diǎn)較近,而保護(hù)2距離短路點(diǎn)較遠(yuǎn),所以,保護(hù)1的動(dòng)作時(shí)間就比保護(hù)2的 短。這樣故障就由保護(hù)1動(dòng)作切除,不會(huì)引起保護(hù)2的誤動(dòng)作。這種選擇性的配合是靠適當(dāng)?shù)倪x擇各保護(hù)的整定阻抗值和動(dòng)作時(shí)限來完成的。

      圖3.6 距離保護(hù)的基本原理

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書 短路電流計(jì)算

      4.1短路計(jì)算說明

      短路計(jì)算是電力系統(tǒng)設(shè)計(jì),設(shè)備選擇,繼電保護(hù)設(shè)計(jì),整定的依據(jù),是解決一系列問題的基本計(jì)算。一般包括發(fā)生短路時(shí)的系統(tǒng)的運(yùn)行方式及短路類型和短路點(diǎn)等條件。在實(shí)用計(jì)算中,采取一些簡化假設(shè):

      1、所有電源電勢等電位。

      2、不記磁路飽和,忽略線路電容、電阻。

      3、把負(fù)荷當(dāng)作恒定電抗。

      4、電力系統(tǒng)均為金屬性短路。

      4.2母線短路電流計(jì)算

      4.2.1主變標(biāo)幺值參數(shù)計(jì)算(取SB=100MVA,UB=UAV,SN=31.5MVA)

      Uk1%?11(Uk(1?3)%?Uk(1?2)%?Uk(2?3)%)?(17.5?10.5?6.5)?10.75 2211Uk2%?(Uk(1?2)%?Uk(2?3)%?Uk(1?3)%)?(10.5?6.5?17.5)??0.25(4-1)

      2211Uk3%?(Uk(1?3)%?Uk(2?3)%?Uk(1?2)%)?(17.5?6.5?10.5)?6.75

      22得XT1?Uk1%SB10.75100????0.34 100STN10031.5Uk2%SB?0.25100?????0.008(近似為0)(4-2)100STN10031.5Uk3%SB6.75100????0.21 100STN10031.5XT2?XT3?

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      系統(tǒng)等值阻抗圖:

      圖4.1 系統(tǒng)等值阻抗圖

      4.2.2三相對稱短路時(shí)的電流計(jì)算

      基準(zhǔn)值的選擇,取SB=100MVA,Ud1=115kV,Ud2=37kV,Ud3=10.5kV

      最大運(yùn)行方式下:

      d1(3)時(shí)有

      Xd1 =x1=0.0192

      (3)Id1?SB1?

      圖4.2短路等值阻抗圖

      0.01923Ud1=26.15(kA)

      (3)d2時(shí)有

      1Xd2 =x1+x2

      2=0.0192+0.17

      =0.1892

      圖4.3短路等值阻抗圖

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      I(3)1d2?SB0.1892?3U d=8.25(kA)d(3)3時(shí)有

      Xd3 =(x1+112x2)+ 2x3

      =(0.0192+0.17)+0.105 =0.2942 I(3)1SBd3?0.2942?3U

      d3=18.69(kA)

      最小運(yùn)行方式下:

      d(3)1時(shí)有

      Xd1 =x1=0.0192 I(3)d1?10.0192?SB3U

      d1=26.15(kA)d(3)2時(shí)有

      Xd2 =x1+x2

      =0.0192+0.34

      =0.3592

      I(3)1d2?SB0.3592?3U d2

      圖4.4短路等值阻抗圖

      圖4.5短路等值阻抗圖

      圖4.6短路等值阻抗圖

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      =4.34(kA)

      d3時(shí)有(3)Xd3 =x1+x2+x3

      =0.0192+0.34+0.21

      =0.5692(3)Id3?SB

      1?0.56923Ud3=9.66(kA)

      圖4.7短路等值阻抗圖

      4.2.3不對稱短路的電流計(jì)算

      電力系統(tǒng)中的短路故障大多數(shù)是不對稱的。為了保證電力系統(tǒng)和各種電氣設(shè)備的安全運(yùn)行,需進(jìn)行各種不對稱故障的分析和計(jì)算。發(fā)生不對稱短路時(shí),電力系統(tǒng)的三相電流和電壓是不平衡的。因此,不能采用計(jì)算三相短路電流的算法進(jìn)行分相計(jì)算。一般求解不對稱故障問題常用的方法是對稱分量法。在用對稱分量發(fā)分析和計(jì)算系統(tǒng)短路時(shí),所采用的參數(shù)是電力系統(tǒng)各元件的相序參數(shù)。一般在線性電路中可以應(yīng)用疊加原理,得到不對稱分量分別按對稱三相電路求解,然后將結(jié)果疊加起來,得到不對稱三相電路的解,用于后面的繼電保護(hù)靈敏度的校驗(yàn)。最大運(yùn)行方式下

      零序網(wǎng)如右圖所示

      X1?Xd1?0.0192 Xd0?3X1//(X2?X3)

      =0.0576∥0.55

      =0.052 d1(1)時(shí)有

      圖4.8零序阻抗圖

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      3If0?SB3E?

      (4-3)

      2x1?Xd03Ud11003?115 =33.19?=16.66(kA)d1(1.1)時(shí)有

      3If0?SB3E100??24.35??12.22(kA)x1?2Xd03Ud13?115最小運(yùn)行方式下由于零序阻抗值基本不變化,所以所有數(shù)據(jù)與最大運(yùn)行方式下近似相等。

      由課本可知,當(dāng)系統(tǒng)為無限大系統(tǒng)或距短路點(diǎn)很遠(yuǎn)時(shí),此時(shí)的兩相短路電流可采用實(shí)用計(jì)算方法。本系統(tǒng)電源的容量為5210MVA,為了減少計(jì)算量可以近似按無限大系統(tǒng)是計(jì)算。

      即:

      (2)Id? 3(3)Id

      (4-4)

      2最大運(yùn)行方式下:

      d1(2)時(shí)有

      (2)Id1?3(3)Id1?22.65(kA)2最小運(yùn)行方式下:

      d1(2)時(shí)有

      (2)Id1?3(3)Id1?22.65(kA)2

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      4.3線路短路電流計(jì)算

      4.3.1各線路阻抗參數(shù)

      查手冊得:LGJ-300型線路x0?0.404(Ω)/km LGJ-150型線路x0?0.425(Ω)/km LGJ-120型線路x0?0.435(Ω)/km 實(shí)際計(jì)算阻抗有名值為:x?x0?l(Ω)(4-5)表4-1 各側(cè)阻抗計(jì)算值(Ω)L-1 L-2 L-3 L-4 L-5 L-6 L-7 L-8 110KV 20.2 24.24 21.25 17 35KV 5.22 6.525 3.48 2.61 4.35 5.22 10KV 2.61 1.74 1.305 3.48 3.045 2.175 3.48 3.915 標(biāo)幺值計(jì)算為:x*?x?SB;(4-6)2UB表4-2 各側(cè)阻抗標(biāo)幺值

      L-1 L-2 L-3 L-4 L-5 L-6 L-7 L-8

      110KV 0.15 0.18 0.16 0.13 35KV 0.38 0.48 0.25 0.19 0.32 0.38 10KV 2.37 1.58 1.18 3.16 2.76 1.97 3.16 3.55

      4.3.2 110kV線路短路電流計(jì)算

      最大運(yùn)行方式下

      發(fā)生d(3)時(shí)Id?1SB計(jì)算數(shù)值如下: ?Xd1?xL3Ud1L-1 Id?1100??3.14(kA)0.0192?0.153?115 27 ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      L-2 Id?1100??2.52(kA)0.0192?0.183?1151100??2.80(kA)

      0.0192?0.163?1151100??3.36(kA)0.0192?0.133?115SB3E?

      2x1?x03Ud1L-3 Id?L-4 Id?發(fā)生d(1)時(shí)x1?Xd1?xL;x0?Xd0?3xL;3If0?計(jì)算數(shù)值如下:

      L-1 x1?0.0192?0.15?0.1692

      x0?0.052?0.45?0.502 3If0?3100??1.79(kA)0.84043?115L-2 x1?0.0192+0.18=0.1992 x0?0.052+0.54=0.592 3If0?3100??1.52(kA)0.99043?115L-3 x1?0.0192+0.16=0.1792 x0?0.052+0.48=0.532 3If0?3100??1.22(kA)0.89043?115L-4 x1?0.0192+0.13=0.1492 x0?0.052+0.39=0.442 3If0?3100??2.03(kA)0.74043?115 28 ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      發(fā)生d(1.1)時(shí)

      x1?Xd1?xL;x0?Xd0?3xL;3If0?計(jì)算數(shù)值如下:

      L-1 x1?0.0192?0.15?0.1692

      x0?0.052?0.45?0.502 3If0?SB3E?

      x1?2x03Ud13100??1.28(kA)1.17323?115L-2 x1?0.0192+0.18=0.1992 x0?0.052+0.54=0.592

      3If0?3100??1.09(kA)1.38323?115L-3 x1?0.0192+0.16=0.1792 x0?0.052+0.48=0.532 3If0?3100??1.21(kA)1.24323?115L-4 x1?0.0192+0.13=0.1492 x0?0.052+0.39=0.442 3If0?3100??1.46(kA)1.03323?115最小運(yùn)行方式下由于變壓器等效阻抗值變化不大,所以所有數(shù)據(jù)與最大運(yùn)行方式下近似相等

      4.3.3 35kV線路短路電流計(jì)算

      最大運(yùn)行方式下發(fā)生d(3)時(shí)Id?SB1? 計(jì)算數(shù)值如下:

      Xd2?xL3Ud2 29 ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      L-1 I1d?0.1892?0.38?1003?37?2.74(kA)L-2 I1d?0.1892?0.48?1003?37?2.33(kA)

      L-3 I1d?0.1892?0.25?1003?37?3.55(kA)L-4 I1d?0.1892?0.19?1003?37?4.11(kA)

      L-5 I1d?0.1892?0.32?1003?37?3.06(kA)

      L-6 I?1d0.1892?0.38?1003?37?2.74(kA)

      最小運(yùn)行方式下發(fā)生d(3)時(shí)I1SBd?X?d2?xL3Ud2L-1 Id?10.3592?0.38?1003?37?2.11(kA)

      L-2 I1d?0.3592?0.48?1003?37?1.86(kA)

      L-3 I1d?0.3592?0.25?1003?37?2.56(kA)

      L-4 I1d?0.3592?0.19?1003?37?2.84(kA)L-5 I1d?0.3592?0.32?1003?37?2.30(kA)L-6 I1d?0.3592?0.38?1003?37?2.11(kA)

      計(jì)算數(shù)值如下:

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      4.3.4 10kV線路短路電流計(jì)算

      最大運(yùn)行方式下發(fā)生d(3)時(shí)Id?SB1 計(jì)算數(shù)值如下: ?Xd3?xL3Ud3L-1 I1d?0.2942?2.37?1003?10.5?2.06(kA)L-2 I1d?0.2942?1.58?1003?10.5?2.93(kA)

      L-3 I1d?0.2942?1.18?1003?10.5?3.73(kA)L-4 I1d?0.2942?3.16?1003?10.5?1.59(kA)L-5 I1d?0.2942?2.76?1003?10.5?1.80(kA)

      L-6 I1d?0.2942?1.97?1003?10.5?2.43(kA)

      L-7 I1d?0.2942?3.16?1003?10.5?1.59(kA)

      L-8 I1d?0.2942?3.55?1003?10.5?1.43(kA)

      最小運(yùn)行方式下發(fā)生d(3)時(shí)I1SBd?X?d3?xL3Ud3L-1 I1d?0.5692?2.37?1003?10.5?1.87(kA)L-2 I1d?0.5692?1.58?1003?10.5?2.56(kA)

      計(jì)算數(shù)值如下:

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      L-3 Id?1100??3.73(kA)0.5692?1.183?10.51100??3.14(kA)

      0.5692?3.163?10.51100??1.65(kA)

      0.5692?2.763?10.51100??2.17(kA)0.5692?1.973?10.51100??3.14(kA)0.5692?3.163?10.51100??1.33(kA)0.5692?3.553?10.5 L-4 Id?L-5 Id?L-6 Id?L-7 Id?L-8 Id?

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書 整定計(jì)算

      5.1線路最大負(fù)荷電流計(jì)算

      IL.max?由前面線路參數(shù)表可計(jì)算如下: 1、110KV側(cè)線路 L-1 IL.max?Pmax(5-1)

      3UNcos?503?115?0.86603?115?0.86?0.29?kA? ?0.35?kA? L-2 IL.max?L-3 IL.max?553?115?0.86483?115?0.86?0.32?kA? ?0.28?kA? L-4 IL.max?2、35KV側(cè)線路 L-1 IL.max?143?37?0.8?0.27?kA?

      L-2 IL.max?153?37?0.8273?37?0.85?0.29?kA?

      ?0.49?kA? L-3 IL.max?L-4 IL.max?183?37?0.85?0.33?kA?

      L-5 IL.max?173?37?0.8?0.33?kA?

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      L-6 IL.max?3、10KV側(cè)線路 L-1 IL.max?253?37?0.85?0.46?kA?

      53?10.5?0.843?10.5?0.8?0.34?kA?

      L-2 IL.max??0.27?kA?

      L-3 IL.max?33?10.5?0.883?10.5?0.843?10.5?0.853?10.5?0.873?10.5?0.8?0.21?kA? ?0.55?kA? ?0.27?kA? ?0.34?kA? L-4 IL.max?L-5 IL.max?L-6 IL.max?L-7 IL.max??0.48?kA?

      L-8 IL.max?33?10.5?0.8?0.21?kA?

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      5.2主變壓器保護(hù)的整定計(jì)算

      5.2.1縱差動(dòng)保護(hù)整定計(jì)算

      一、計(jì)算變壓器各側(cè)一次電流,選擇電流互感器的變比,確定各側(cè)二次額定電流:

      表5-1

      變壓器相關(guān)參數(shù)計(jì)算

      名稱

      各側(cè)數(shù)值

      額定電壓(kV)

      115

      10.5

      額定電流(A)31.5?1033?115?158.131.5?1033?37?491.5

      31.5?1033?10.5?1732.1

      電流互感器 Y

      Y

      D 接線方式

      電流互感器

      158.1/5

      491.5/5

      3?1732.1/5 計(jì)算變比

      選用電流互 200/5

      500/5

      3000/5 感器變比

      二次額定電 158.1/40=3.95

      491.5/100=4.915

      3000/600=5 流(A)

      10.5kV側(cè)的二次額定電流最大,所以選取該側(cè)為保護(hù)的基本側(cè)。

      二、確定保護(hù)的一次動(dòng)作電流:

      1、按躲開變壓器的勵(lì)磁涌流整定:

      Idz?Kk?Ie.B

      (Kk取1.5)

      (5-2)

      =1.5×1732.1

      =2598.15(A)

      2、器外部三相短路時(shí)的最大不平衡電流來整定

      (3)Idz?Kk(Kfzq?Ktxfwc??U??fza)Id(Kk取1.3)(5-3).max

      = 1.3(1.0×1×0.1 + 0.1+ 0.05)×3.73×1000

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      =994(A)其中Ktx為電流互感器同型系數(shù),型號(hào)相同時(shí)取0.5,型號(hào)不同時(shí)取1,這

      Kfzq為非周期分量引起的誤差,里為避免以后更換設(shè)備的方便故取1;取1;?fza(3)建議采用中間值0.05;?U取0.1;Id.max為變壓器外部最大運(yùn)行方式下的三相短路電流。

      3、按躲開電流互感器二次回路斷線時(shí)變壓器的最大負(fù)荷電流整定:

      Ldz?Kk?Ith.max

      (Kk取1.3)

      = 1.3×1732.1 = 2251.7(A)

      三、確定保護(hù)的二次動(dòng)作電流:

      1、基本側(cè)差動(dòng)繼電器的動(dòng)作電流為:

      Idzdz.j.jb?kjx?In

      ?3?2598.1530050?7.5(A)

      2、基本側(cè)差動(dòng)線圈工匝數(shù)為:(AW0為60)

      WAW0cd.jb.z?I

      dz?j?jb

      ?607.5?8

      選用的差動(dòng)線圈匝數(shù)為8匝

      四、差動(dòng)保護(hù)的實(shí)際動(dòng)作電流:

      1、差動(dòng)保護(hù)的實(shí)際二次動(dòng)作電流:

      IAW0dz.j.jb?W?60?7.5(A)

      cd?jb?z8

      ∴ 差動(dòng)保護(hù)實(shí)際一次動(dòng)作電流為:

      5-4)

      5-5)

      5-6)(((****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      Idz.jb?Idz?j?jb?nLKjx7.5?3000

      3(5-7)

      ?5?2598.2(A)

      五、動(dòng)作時(shí)限:0秒

      六、靈敏度校驗(yàn):

      Id?.min為實(shí)際可能的方式下在差動(dòng)保護(hù)范圍內(nèi)發(fā)生兩相短路時(shí)總的最小短路電流;

      Id?.min是在系統(tǒng)最小運(yùn)行方式下兩臺(tái)變壓器并聯(lián)運(yùn)行時(shí)低壓側(cè)兩相短路取得;接線系數(shù)Kjx取2

      kjx?Id?.minIdz.j.jb?nL.jb2??3?9.66?10002?3.72?2(滿足要求)

      (5-8)7.5?30005Ksen?5.2.2 復(fù)合電壓啟動(dòng)過電流保護(hù)的整定計(jì)算

      過電流元件動(dòng)作值Iop按躲開站變額定電流IN.st整定,即: Iop?110kV側(cè):krel?IN.st(5-9)kre ?1.1531500??214(A)0.853?115 其中krel可靠系數(shù),一般為1.15~1.25,這里取1.15, kre是返回系數(shù),這里取0.85 運(yùn)行方式下線路末端的兩相短路電流對保護(hù)裝置進(jìn)行靈敏度的校驗(yàn)。

      3(3)3Id.min?1.33?1000?2?2?5.4?1.3,滿足要求。(5-10)

      IOP213Ksen 37 ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      35kV側(cè):Iop?krel1.1531500?IN.st???665(A)kre0.853?37取最小運(yùn)行方式下線路末端的兩相短路電流對保護(hù)裝置進(jìn)行靈敏度的校驗(yàn)。

      3(3)3Id.min?1.33?1000?2?2?1.73?1.3,滿足要求

      IOP665krel1.1531500?IN.st???2343(A)kre0.853?10.5Ksen10kV側(cè):Iop?取最小運(yùn)行方式下線路末端的兩相短路電流對保護(hù)裝置進(jìn)行靈敏度的校驗(yàn)。

      3(3)3Id.min?1.33?100022???0.5?1.3,不滿足要求 IOP2343Ksen最終整定電流取最小值即110KV側(cè)的整定結(jié)果。保護(hù)動(dòng)作時(shí)限為0.5秒。

      5.2.3 過負(fù)荷保護(hù)的整定計(jì)算

      取可靠系數(shù)Krel為1.05,返回系數(shù)Kres為0.85,IN為保護(hù)安裝側(cè)變壓器的額定電流。因是單側(cè)電源三繞組降壓變壓器且三側(cè)繞組容量相同,則過負(fù)荷保護(hù)裝在電源側(cè)(即110KV側(cè))。

      按躲開變壓器額定電流來整定:

      IdzKk1.0531.5?103??IN???195.35(A)Kh0.853?115動(dòng)作時(shí)限:比降壓變壓器復(fù)合電壓起動(dòng)的過電流保護(hù)的動(dòng)作時(shí)限大0.5秒,即0.5+0.5=1秒。

      5.3 母線保護(hù)的整定計(jì)算

      根據(jù)本設(shè)計(jì)的實(shí)際情況,決定采用完全電流差動(dòng)母線保護(hù)對變電站的母線進(jìn)行保護(hù)。

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      所用設(shè)備差動(dòng)繼電器的動(dòng)作電流按下述兩個(gè)原則整定,并取其中的較大者為整定值。

      (1)躲過外部故障時(shí)的最大不平衡電流。其動(dòng)作電流按下式計(jì)算

      Iop,K?KrelIdsp.max?Krel?0.1?Ik..max/nTA(5-11)式中:Krel為可靠系數(shù),取為1.3;

      Ik..max為在母線范圍外任一連接元件上短路時(shí),流過差動(dòng)保護(hù)電流互感器的最大短路電流;

      nTA為母線保護(hù)用電流互感器的變比。110kV母線: Iop,K?Krel?0.1?Ik..max/nTA

      =1.3?0.1?36?1000/40

      =10.92(A)

      35kV母線:

      Iop,K?Krel?0.1?Ik..max/nTA

      =1.3?0.1?4.11?1000/100

      =5.343(A)

      10kV母線:

      Iop,K?Krel?0.1?Ik..max/nTA

      =1.3?0.1?3.73?1000/600

      =0.808(A)

      (2)躲過電流互感器二次回路一相短線時(shí)流過差動(dòng)繼電器的最大電流。

      其動(dòng)作電流按下式計(jì)算

      Iop,K?Krel?Il..max/nTA

      (5-12)式中Il..max為所有連接元件中最大的負(fù)荷電流。

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      110kV母線: Iop,K?Krel?Il..max/nTA

      =1.3?350/40

      =11.38(A)

      35kV母線: Iop,K?Krel?Il..max/nTA

      =1.3?490/100

      =6.37(A)

      10kV母線: Iop,K?Krel?Il..max/nTA

      =1.3?550/600

      =1.19(A)

      根據(jù)計(jì)算值可知母線動(dòng)作電流如下:

      110kV母線:Iop,K?11.38(A)

      35kV母線:Iop,K?6.37(A)10kV母線:Iop,K?1.19(A)

      當(dāng)保護(hù)范圍內(nèi)部故障時(shí),應(yīng)采用下式校驗(yàn)靈敏系數(shù),其值一般應(yīng)不低于2。

      Ksen?Ik.min

      (5-13)

      Iop.k?nTA式中Ik.min為母線故障時(shí)的最小短路電流。110kV母線: Ksen?Ik.min22.65?1000??49.76?2

      Iop.k?nTA11.38?404.34?3?10002?5.9?2 6.37?100 40 35kV母線: Ksen?Ik.min?Iop.k?nTA****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      10kV母線: Ksen?Ik.min?Iop.k?nTA9.66?3?10002?11.7?2 1.19?600

      由計(jì)算結(jié)果知整定值符合要求。

      5.4 線路保護(hù)的整定計(jì)算

      5.4.1 110kV線路保護(hù)的整定計(jì)算

      一、相間距離保護(hù)的整定計(jì)算 1.距離Ⅰ段

      為了保證選擇性,保護(hù)瞬時(shí)動(dòng)作的距離Ⅰ段動(dòng)作阻抗應(yīng)按躲過相鄰下一元件首端短路的條件選擇,即

      ' Zop?krel?ZL 可靠系數(shù)krel=0.85

      (5-14)

      '?0.85?20.2=17.17(Ω)L-1 Zop'?0.85?24.24=20.604(Ω)L-2 Zop'?0.85?21.25=18.0625(Ω)L-3 Zop'?0.85?17=14.45(Ω)L-4 Zop2.距離Ⅱ段

      動(dòng)作阻抗按下式整定

      “ Zop ?ksen?ZL 靈敏系數(shù)ksen=1.3

      (5-15)”?1.3?20.2=26.26(Ω)L-1 Zop“?1.3?24.24=31.512(Ω)L-2 Zop”?1.3?21.25=27.625(Ω)L-3 Zop“?1.3?17=22.1(Ω)L-4 Zop

      3.距離Ⅲ段

      動(dòng)作阻抗按下式整定

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      ”'Zop?ZL.min

      (5-16)

      krel?kre?kzq0.9Ee ZL.min?IL.max

      3(5-17)

      krel?1.3 kre?1.2 kzq?2

      式中Ee為電網(wǎng)的額定線電壓;

      IL.max為線路的最大負(fù)荷電流。

      0.9?110“' L-1 Zop?30.290.9?1103/1.3?1.2?2?63.17(?)

      ”' L-2 Zop?0.350.9?1103/1.3?1.2?2?52.34(?)

      “' L-3 Zop?0.320.9?1103/1.3?1.2?2?57.25(?)

      ”' L-4 Zop?0.28/1.3?1.2?2?65.43(?)

      靈敏度校驗(yàn) Ksen?L-1 Ksen?“'ZopZl

      63.17?3.13?1.5 20.252.34L-2 Ksen??2.16?1.5

      24.2457.25L-3 Ksen??2.69?1.5

      21.2565.43L-4 Ksen??3.85?1.5

      17由以上計(jì)算可知整定結(jié)果符合要求。

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      5.4.2 35kV線路保護(hù)的整定計(jì)算

      一、相間距離保護(hù)的整定計(jì)算 1.距離Ⅰ段

      'Zop?krel?ZL krel?0.85

      '?0.85?5.22?4.437(?)L-1 Zop'?0.85?6.525?5.55(?)L-2 Zop'?0.85?3.48?2.958(?)L-3 Zop'?0.85?2.61?2.22(?)L-4 Zop'?0.85?4.35?3.70(?)L-5 Zop'?0.85?5.22?4.437(?)L-6 Zop2.距離Ⅱ段

      動(dòng)作阻抗按下式整定

      Zop”?ksen?ZL 靈敏系數(shù)ksen=1.3

      ''?1.3?5.22?6.786(?)L-1 Zop''?1.3?6.525?8.48(?)L-2 Zop''?1.3?3.48?4.524(?)L-3 Zop''?1.3?2.61?3.393(?)L-4 Zop''?1.3?4.35?5.655(?)L-5 Zop''?1.3?5.22?6.786(?)L-6 Zop3.距離Ⅲ段

      動(dòng)作阻抗按下式整定

      “'Zop?ZL.min ZL.min?krel?kre?kzq0.9EeIL.max3

      krel?1.3 kre?1.2 kzq?2

      0.9?35”'L-1 Zop?30.27/1.3?1.2?2?21.59(?)

      ****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      0.9?35L-2 Z“'3op?0.29/1.3?1.2?2?20.1(?)

      0.9?35L-3 Z”'3op?0.49/1.3?1.2?2?11.90(?)

      0.9?35L-4 Z“'3op?0.33/1.3?1.2?2?17.66(?)

      0.9?35L-5 Z”'3op?0.33/1.3?1.2?2?17.66(?)

      0.9?35L-6 Z“'3op?0.46/1.3?1.2?2?12.67(?)

      靈敏度校驗(yàn)

      KZ”'opsen?Z

      lL-1 K21.59sen?5.22?4.14?1.5 L-2 K20.1sen?6.525?3.08?1.5

      L-3 K11.9sen?3.48?3.42?1.5

      L-4 K?17.66sen2.61?6.77?1.5

      L-5 K17.66sen?4.35?4.06?1.5

      L-6 K?12.67sen5.22?2.43?1.5

      由以上計(jì)算可知整定結(jié)果符合要求。二、三段式電流保護(hù)的整定計(jì)算 瞬時(shí)電流速斷保護(hù)(又稱第Ⅰ段電流保護(hù))

      I'op?krel?Id.max krel?1.2 式中Id.max為線路在最大運(yùn)行方式下的三相短路值

      L-1 I'op?1.2?2.74?3.288(kA)44

      5-18)(****大學(xué)畢業(yè)設(shè)計(jì)(論文)說明書

      L-2 I'op?1.2?2.33?2.796(kA)L-3 I'op?1.2?3.55?4.26(kA)L-4 I'op?1.2?4.11?4.932(kA)L-5 I'op?1.2?3.06?3.672(kA)L-6 I'op?1.2?2.74?3.288(kA)靈敏度校驗(yàn):按線路30%處發(fā)生d(2)故障時(shí)校驗(yàn)

      I(2)3SBd.min?2?1X? d2?xL30%3UBL-1 I(2)1d.min?2?10.1892?0.38?30%?10037?4.45(kA)L-2 I(2)?11d.min2?0.1892?0.48?30%?10037?4.05(kA)L-3 I(2)d.min?12?11000.1892?0.25?30%?37?5.11(kA)L-4 I(2)d.min?12?10.1892?0.19?30%?10037?5.48(kA)L-5 I(2)d.min?12?10.1892?0.32?30%?10037?4.73(kA)L-6 I(2)d.min?12?10.1892?0.38?30%?10037?4.45(kA)因?yàn)镮(2)d.min?Iop所以靈敏度合格 限時(shí)電流速斷保護(hù)(第又稱Ⅱ段電流保護(hù))

      (2)I“minop?Id.k ksen?1.3 sen3L-1 I”op?2.11?21.3?1.4(kA)L-2 I“1.86?3op?21.3?1.24(kA)L-3 I”2.56?3op?21.3?1.71(kA)

      5-19)(

      第四篇:變電站輔助設(shè)施標(biāo)準(zhǔn)化驗(yàn)收規(guī)范

      河南電網(wǎng)變電站輔助設(shè)施標(biāo)準(zhǔn)化驗(yàn)收規(guī)范

      前 言

      變電站輔助設(shè)施作為電網(wǎng)生產(chǎn)輔助系統(tǒng),是提高變電站運(yùn)行維護(hù)管理能力,提高電網(wǎng)的設(shè)備運(yùn)行環(huán)境的重要基礎(chǔ),也是實(shí)現(xiàn)電網(wǎng)運(yùn)行管理信息化的基礎(chǔ)。

      對變電站輔助設(shè)施進(jìn)行認(rèn)真、全面、嚴(yán)格、規(guī)范的標(biāo)準(zhǔn)化驗(yàn)收,是保證變電站在驗(yàn)收交付后穩(wěn)定、安全、可靠運(yùn)行的重要手段,也是項(xiàng)目規(guī)范化管理的必要階段。

      為使河南電網(wǎng)所轄的變電站輔助設(shè)施系統(tǒng)驗(yàn)收工作更具專業(yè)性、規(guī)范性和可操作性,特制定本規(guī)范

      范圍

      本規(guī)范規(guī)定了河南電網(wǎng)變電站輔助設(shè)施系統(tǒng)的驗(yàn)收階段、驗(yàn)收組織管理、驗(yàn)收原則及依據(jù)、驗(yàn)收內(nèi)容及要求、驗(yàn)收大綱編制、現(xiàn)場驗(yàn)收、整體考核驗(yàn)收等方面的要求。

      本規(guī)范適用于河南電新建、改建、擴(kuò)建的變電站。2 驗(yàn)收組織管理

      2.1 驗(yàn)收階段

      變電站輔助設(shè)施系統(tǒng)驗(yàn)收分為兩個(gè)階段,即現(xiàn)場驗(yàn)收、整體考核驗(yàn)收;整體考核驗(yàn)收階段包括試運(yùn)行考核期和整體考核驗(yàn)收,試運(yùn)行考核期不得少于3 個(gè)月。

      2.2 驗(yàn)收職責(zé)

      2.2.1 各地區(qū)供電局(建設(shè)單位)職責(zé): a)負(fù)責(zé)組織變電站輔助設(shè)施系統(tǒng)的現(xiàn)場驗(yàn)收; b)負(fù)責(zé)組織完成各階段驗(yàn)收測試大綱的編制及審核; c)編制各階段驗(yàn)收文件;

      d)負(fù)責(zé)編制項(xiàng)目工程文檔,匯編項(xiàng)目工程清冊。2.2.2 制造單位職責(zé):

      a)輔助設(shè)施制造單位參與現(xiàn)場驗(yàn)收和整體考核驗(yàn)收; b)制造單位負(fù)責(zé)組織輔助設(shè)施的工廠驗(yàn)收,參與現(xiàn)場驗(yàn)收; c)制造單位負(fù)責(zé)編制工廠驗(yàn)收大綱,參與現(xiàn)場驗(yàn)收大綱編制; d)參與編制工廠驗(yàn)收、現(xiàn)場驗(yàn)收文件。e)提供所生產(chǎn)設(shè)備的質(zhì)量證明文件、特種設(shè)備須提供生產(chǎn)制造許可證復(fù)印件

      2.2.3 安裝調(diào)試單位職責(zé): a)參與現(xiàn)場驗(yàn)收大綱的編制; b)參與現(xiàn)場驗(yàn)收;

      c)完成現(xiàn)場施工圖檔資料的編制。2.2.4 設(shè)計(jì)單位職責(zé):

      a)參與變電站輔助設(shè)施的各階段驗(yàn)收; b)參與各階段驗(yàn)收測試大綱編制;

      c)對驗(yàn)收中發(fā)現(xiàn)的由于設(shè)計(jì)原因造成的缺陷應(yīng)及時(shí)進(jìn)行設(shè)計(jì)變更;

      d)負(fù)責(zé)竣工圖紙的編制,并按照河南電網(wǎng)關(guān)于變電站輔助設(shè)施移交的規(guī)定和合同要求提交給建設(shè)單位。

      2.3 驗(yàn)收組織

      2.3.1 負(fù)責(zé)項(xiàng)目各階段驗(yàn)收組織工作的單位在驗(yàn)收條件具備后,及時(shí)組織成立相應(yīng)的驗(yàn)收工作組,啟動(dòng)該階段驗(yàn)收流程。

      2.3.2 各階段驗(yàn)收工作組包括領(lǐng)導(dǎo)小組和工作小組,工作小組負(fù)責(zé)變電站現(xiàn)場的驗(yàn)收測試。

      2.3.3 驗(yàn)收工作組在驗(yàn)收開始前必須嚴(yán)格審查驗(yàn)收大綱,驗(yàn)收大綱經(jīng)審批通過后,進(jìn)入驗(yàn)收流程。

      2.3.4 在驗(yàn)收過程中,驗(yàn)收工作組必須嚴(yán)格按照驗(yàn)收大綱和驗(yàn)收流程進(jìn)行驗(yàn)收測試工作,并負(fù)責(zé)編制驗(yàn)收報(bào)告。3 驗(yàn)收原則及驗(yàn)收依據(jù) 3.1 驗(yàn)收原則

      3.1.1 變電站輔助設(shè)施的驗(yàn)收應(yīng)堅(jiān)持科學(xué)、嚴(yán)謹(jǐn)、認(rèn)真的工作態(tài)度,參與驗(yàn)收測試的人員必須具備相應(yīng)的專業(yè)技術(shù)水平;驗(yàn)收測試工作應(yīng)規(guī)范、標(biāo)準(zhǔn),應(yīng)使用專用的測試儀器和專業(yè)測試軟件,并使用標(biāo)準(zhǔn)化、規(guī)范化的測試用例。

      3.1.2 驗(yàn)收工作遵循現(xiàn)場驗(yàn)收、整體考核驗(yàn)收的順序進(jìn)行,只有在前一階段驗(yàn)收合格通過后,方可進(jìn)入下一階段工作。

      3.1.3 制造單位在各驗(yàn)收階段所提供的使用手冊等文檔必須為按系統(tǒng)實(shí)際版本進(jìn)行編制,驗(yàn)收大綱中功能測試項(xiàng)目的測試步驟應(yīng)按技術(shù)文檔對應(yīng)的敘述進(jìn)行編制,以驗(yàn)證技術(shù)文檔的正確性和有效性;

      如該項(xiàng)測試步驟不能正確執(zhí)行,則視為該項(xiàng)測試不通過。3.1.4 若各階段驗(yàn)收測試結(jié)果證明某一設(shè)備、軟件功能或性能不合格,制造單位必須更換不合格的設(shè)備或修改不合格的軟件,對于第三方提供的設(shè)備或軟件同樣適用。設(shè)備更換或軟件修改完成后,與該設(shè)備及軟件關(guān)聯(lián)的功能及性能測試項(xiàng)目必須重新測試。

      4.2 驗(yàn)收依據(jù)

      4.2.1 各階段驗(yàn)收均應(yīng)嚴(yán)格遵循國家和行業(yè)的技術(shù)規(guī)范、標(biāo)準(zhǔn)、規(guī)程、項(xiàng)目合同技術(shù)協(xié)議書及歷次技術(shù)(設(shè)計(jì))聯(lián)絡(luò)會(huì)議紀(jì)要的所有技術(shù)方面的條款,以及合同執(zhí)行過程中產(chǎn)生的技術(shù)澄清文件(以下合稱“項(xiàng)目技術(shù)文件”)。

      4.2.2 各階段驗(yàn)收的設(shè)備及資料核查應(yīng)按照本規(guī)范的具體要求執(zhí)行。驗(yàn)收內(nèi)容及要求 5.1 驗(yàn)收內(nèi)容及要求

      各階段驗(yàn)收工作組可根據(jù)變電站輔助設(shè)施的實(shí)際配置和要求進(jìn)行取舍選擇,并根據(jù)項(xiàng)目技術(shù)文件進(jìn)行補(bǔ)充和細(xì)化。

      5.1.1 設(shè)備核查 5.1.1.1 核查內(nèi)容

      a)根據(jù)項(xiàng)目合同所列的所有軟硬件設(shè)備清單,對設(shè)備型號(hào)、外觀、數(shù)量及附屬的配件及隨機(jī)資料逐項(xiàng)清點(diǎn)確認(rèn);

      b)對各軟硬設(shè)備配置進(jìn)行檢查確認(rèn)。5.1.1.2 核查要求

      a)各設(shè)備的型號(hào)和數(shù)量應(yīng)與設(shè)備清單一致,應(yīng)為全新購置的產(chǎn)品;附屬的配件及隨機(jī)資料應(yīng)與設(shè)備發(fā)貨(裝箱)清單一致;

      b)設(shè)備的配置應(yīng)不低于設(shè)備清單所列的具體配置要求,設(shè)備序列號(hào)(出廠編號(hào))唯

      一、有效。

      c)輔助設(shè)施出廠后,所有設(shè)備發(fā)送至現(xiàn)場。在現(xiàn)場安裝前,建設(shè)單位、制造單位及各設(shè)備供應(yīng)商可按上述要求進(jìn)行現(xiàn)場設(shè)備到貨驗(yàn)收,并形成設(shè)備現(xiàn)場到貨驗(yàn)收報(bào)告。

      5.1.2 文件核查 5.1.2.1 核查內(nèi)容

      a)制造單位提供的技術(shù)文檔,至少包括維護(hù)手冊、使用手冊及第三方軟件最終用戶授權(quán)書,b)各階段驗(yàn)收所需的工程文檔及報(bào)告。5.1.2.2 核查要求

      a)技術(shù)文檔完整、齊全、正確; b)工程文檔及報(bào)告齊全、完整。3 給水、排水、消防系統(tǒng)驗(yàn)收規(guī)范

      3.1 給水管道及配件安裝質(zhì)量驗(yàn)收規(guī)范

      室內(nèi)給水管道的水壓試驗(yàn)必須符合設(shè)計(jì)要求。當(dāng)設(shè)計(jì)未注明時(shí),各種材質(zhì)的給水管道系統(tǒng)試驗(yàn)壓力均為工作壓力的1.5倍,但不得小于0.6 MPa。

      檢驗(yàn)方法:金屬及復(fù)合管給水管道在試驗(yàn)壓力下觀測10min,壓力降不應(yīng)大于0.02MPa,然后降到工作壓力進(jìn)行檢查,應(yīng)不滲不漏;塑料管給水系統(tǒng)應(yīng)在試驗(yàn)壓力下穩(wěn)壓1h,壓力降不得超過0.05MPa,然后在工作壓力的1.15倍狀態(tài)下穩(wěn)壓2h,壓力降不直超過0.03MPa,同時(shí)檢查各連接處不得滲漏。

      3.1.1 給水系統(tǒng)交付使用前必須進(jìn)行通水試驗(yàn)并做好記錄。檢查方法:觀察和開啟閥門、水嘴等放水。

      3.1.2 生產(chǎn)給水系統(tǒng)管道在交付使用前必須沖洗和消毒,并經(jīng)有關(guān)部門取樣檢驗(yàn),符合國家《生活飲用水標(biāo)準(zhǔn)》方可使用。

      檢驗(yàn)方法:檢查有關(guān)部門提供的檢測報(bào)告。

      3.1.3 室內(nèi)直埋給水管道(塑料管道和復(fù)合管道除外)應(yīng)做防腐處理。埋地管道防腐層標(biāo)材質(zhì)和結(jié)構(gòu)應(yīng)符合設(shè)計(jì)要求。

      檢驗(yàn)方法:觀察或局部解剖檢查 3.2 室內(nèi)消火栓系統(tǒng)驗(yàn)收

      3.2.1 室內(nèi)消火栓系統(tǒng)安裝完成后應(yīng)取屋頂層(或水箱間內(nèi))試驗(yàn)消火栓和首層取二處消火栓做試射試驗(yàn),達(dá)到設(shè)計(jì)要求為合格。

      檢驗(yàn)方法:實(shí)地試射檢查。

      3.2.2 安裝消火栓水龍帶,水龍帶與水槍和快速接頭綁扎好后,應(yīng)根據(jù)箱內(nèi)構(gòu)造將水龍帶掛放在箱內(nèi)的掛釘、托盤或支架上。

      檢查方法:觀察檢查。

      3.2.3 施工單位在竣工時(shí)往往不按規(guī)定把水龍掛在消火栓箱內(nèi)掛釘或水龍帶卷盤上,而將水龍帶卷放在消火栓箱內(nèi)交工,建設(shè)單位接管后必須重新安裝,否則失火時(shí)會(huì)影響使用。

      3.2.4 箱式消火栓的安裝應(yīng)符合下列規(guī)定: 1:栓口應(yīng)朝外,并不應(yīng)安裝在門軸側(cè)。2:栓口中心距地面為1.1m,允許偏差±20mm。

      3:閥門中心距箱側(cè)面料140mm,距箱后內(nèi)表面為100mm,允許偏差±5mm。

      4:消火栓箱體安裝的垂直度允許偏差為3mm.檢驗(yàn)方法:觀察和尺量檢查。3.3 給水設(shè)備安裝質(zhì)量驗(yàn)收

      3.3.1 水泵就位前的基礎(chǔ)混凝土強(qiáng)度、坐標(biāo)、標(biāo)高、尺寸和螺栓孔位置必須符合設(shè)計(jì)規(guī)定。

      檢驗(yàn)方法:對照圖紙用儀器和尺量檢查。3.3.2 水泵試運(yùn)轉(zhuǎn)的軸承溫升必須符合設(shè)備說明書的規(guī)定。檢驗(yàn)方法:溫度計(jì)實(shí)測檢查。

      3.3.3 敞口水相的滿水試驗(yàn)和密閉水箱(罐)的水壓試驗(yàn)必須符合設(shè)計(jì)與本規(guī)范的規(guī)定。

      檢驗(yàn)方法:滿水試驗(yàn)靜置24h觀察,不滲不漏;水壓試驗(yàn)在試驗(yàn)壓力下10min壓力不降,不滲不漏。

      3.4 室內(nèi)排水系統(tǒng)安裝

      3.4.1 本章適用于室內(nèi)排水管道、雨水管道安裝工程的質(zhì)量檢驗(yàn)與驗(yàn)收。

      3.4.2 生活污水管道應(yīng)使用塑料管、鑄鐵管或混凝土管(由成組洗臉盆或飲用噴水器到共用水封之間的排水管和連接衛(wèi)生器具的排水短管,可使用鋼管)。

      雨水管道宜使用塑料管、鑄鐵、鍍鋅鋼管或混凝土管等。懸吊管道定使用塑料管、鑄鐵管或塑料管。易受振動(dòng)的雨水管道(如鍛造車間等)應(yīng)使用鋼管。

      3.4.3 隱蔽或埋地的排水管道在隱蔽前必須做灌水試驗(yàn),其灌水高度應(yīng)不低于底層衛(wèi)生器具的上邊緣或底層地面高度。檢驗(yàn)方法:滿水15min水面下降后,再灌滿觀察5min,液面不降,管道及接口無滲漏為合格。

      3.4.4 生活污水鑄鐵管道的坡度必須符合設(shè)計(jì)的規(guī)定。4 火災(zāi)自動(dòng)報(bào)警系統(tǒng)的驗(yàn)收 4.1 火災(zāi)自動(dòng)報(bào)警系統(tǒng)竣工驗(yàn)收,應(yīng)在公安消防監(jiān)督機(jī)構(gòu)監(jiān)督下,由建設(shè)主管單位主持、設(shè)計(jì)、施工、調(diào)試等單位參加,共同進(jìn)行。

      4.1.2 火災(zāi)自動(dòng)報(bào)警系統(tǒng)驗(yàn)收應(yīng)包括下列裝置:

      1:火災(zāi)自動(dòng)報(bào)警系統(tǒng)裝置(包括各種火災(zāi)探測器、手動(dòng)報(bào)警按鈕、區(qū)域報(bào)警控制器和集中報(bào):警控制器等);

      2:滅火系統(tǒng)控制裝置(包括室內(nèi)消火栓、自動(dòng)噴水、鹵代烷、二氧化碳、干粉、泡沫等固定滅火系統(tǒng)的控制裝置); 3:電動(dòng)防火門、防火卷簾控制裝置;

      4:通風(fēng)空調(diào)、防煙排煙及電動(dòng)防火閥等消防控制裝置; 5:火災(zāi)事故廣播、消防通訊、消防電源、消防電梯和消防控制室的控制裝置;

      6:火災(zāi)事故照明及疏散指示控制裝置。

      4.1.3 消防用電設(shè)備電源的自動(dòng)切換裝置,應(yīng)進(jìn)行3次切換試驗(yàn),每次試驗(yàn)均應(yīng)正常。

      4.1.4 火災(zāi)報(bào)警控制器應(yīng)按下列要求進(jìn)行功能抽驗(yàn): 1:實(shí)際安裝數(shù)量在5臺(tái)以下者,全部抽驗(yàn): 2:實(shí)際安裝數(shù)量在6~10臺(tái)者,抽驗(yàn)5臺(tái);

      3:實(shí)際安裝數(shù)量超過10臺(tái)者,按實(shí)際安裝數(shù)量30%~50%的比例、但不少于5臺(tái)抽驗(yàn)。抽驗(yàn)時(shí)每個(gè)功能應(yīng)重復(fù)1~2次,被抽驗(yàn)控制器的基本功能應(yīng)符合現(xiàn)行國家標(biāo)準(zhǔn)《火災(zāi)報(bào)警控制器通用技術(shù)條件》中的功能要求。4.1.5 火災(zāi)探測器(包括手動(dòng)報(bào)警按鈕),應(yīng)按下列要求進(jìn)行模擬火災(zāi)響應(yīng)試驗(yàn)和故障報(bào)警抽驗(yàn):

      1:實(shí)際安裝數(shù)量在100只以下者,抽驗(yàn)10只;

      2:實(shí)際安裝數(shù)量超過100只,按實(shí)際安裝數(shù)量5%~10%的比例,但不少于10只抽驗(yàn)。被抽驗(yàn)探測器的試驗(yàn)均應(yīng)正常。

      3:室內(nèi)消火栓的功能驗(yàn)收應(yīng)在出水壓力符合現(xiàn)行國家有關(guān)建筑設(shè)計(jì)防火規(guī)范的條件下進(jìn)行。

      4:自動(dòng)噴水滅火系統(tǒng)的抽驗(yàn),應(yīng)在符合現(xiàn)行國家標(biāo)準(zhǔn)《自動(dòng)噴水滅火系統(tǒng)設(shè)計(jì)規(guī)范》的條件。

      4.1.6 本節(jié)各項(xiàng)檢驗(yàn)項(xiàng)目中,當(dāng)有不合格者時(shí),應(yīng)限期修復(fù)或更換,并進(jìn)行復(fù)驗(yàn)。復(fù)驗(yàn)時(shí),對有抽驗(yàn)比例要求的,應(yīng)進(jìn)行加倍試驗(yàn)。復(fù)驗(yàn)不合格者,不能通過驗(yàn)收。

      4.1.7 火災(zāi)自動(dòng)報(bào)警系統(tǒng)投入運(yùn)行前,使用單位應(yīng)有經(jīng)過專門培訓(xùn),并經(jīng)過考試合格的專人負(fù)責(zé)系統(tǒng)的管理操作和維護(hù)。5 事故照明系統(tǒng)驗(yàn)收規(guī)范

      5.1 事故照明系統(tǒng)施工應(yīng)符合設(shè)計(jì)文件及相關(guān)技術(shù)規(guī)范、規(guī)程、國家、行業(yè)標(biāo)準(zhǔn)的要求。

      5.2 事故照明設(shè)施,如開關(guān)、應(yīng)急燈應(yīng)有明確的標(biāo)識(shí),標(biāo)語識(shí)別。

      5.3 事故照明系統(tǒng)的基本要求:

      5.3.1 當(dāng)正常照明因故障熄滅后,需確保正常工作或活動(dòng)繼續(xù)進(jìn)行的場所,備用照明系統(tǒng)應(yīng)能正常啟動(dòng)。5.3.2 當(dāng)正常照明因故障熄滅后,需確保處于潛在危險(xiǎn)之中的人員安全的場所,安全照明應(yīng)能正確啟動(dòng)。

      5.3.3 當(dāng)正常照明因故障熄滅后,需確保人員安全疏散的出入口和通道,疏散照明應(yīng)能覆蓋變電站主要出入口。6 遙視系統(tǒng)驗(yàn)收規(guī)范

      6.1 站端設(shè)備配置要求:站端設(shè)備安裝在變電站現(xiàn)場,完成變電站現(xiàn)場各種信息采集、處理、監(jiān)控并可與監(jiān)控中心進(jìn)行網(wǎng)絡(luò)傳輸和通信。設(shè)備應(yīng)符合變電站自動(dòng)化設(shè)備設(shè)計(jì)要求及有關(guān)標(biāo)準(zhǔn)。

      6.2 站端監(jiān)控主機(jī)或視頻處理單元必須具備數(shù)字硬盤錄像功能,且在軟件或硬件上采取防止系統(tǒng)死機(jī)的措施,以保證持續(xù)穩(wěn)定工作。

      6.3 站端遙視系統(tǒng)應(yīng)滿足遠(yuǎn)方調(diào)閱功能,圖像應(yīng)清晰、無卡頓現(xiàn)象。站內(nèi)攝像頭應(yīng)具有遠(yuǎn)方遙控功能,攝像頭的安裝位置應(yīng)能100%覆蓋站內(nèi)主要出入口、關(guān)鍵變配電設(shè)備、主控室等。7 其他輔助設(shè)施驗(yàn)收規(guī)范

      7.1 電動(dòng)大門外觀清潔油漆美觀,開關(guān)試驗(yàn)良好(包括遙控、就地),熔斷器、鑰匙配備充足,專業(yè)人員認(rèn)可。

      7.2 高低壓配電室的通風(fēng)系統(tǒng)應(yīng)完善、風(fēng)機(jī)應(yīng)能可靠工作,噪聲應(yīng)在限值范圍內(nèi)。

      第五篇:智能變電站二次系統(tǒng)設(shè)計(jì)論文

      1智能變電站二次系統(tǒng)配置方案

      1.1保護(hù)配置

      保護(hù)配置主要從變壓器保護(hù)、線路保護(hù)以及母線保護(hù)三個(gè)方面進(jìn)行。在進(jìn)行線路保護(hù)時(shí)要注意提高采樣值差量和暫態(tài)量的速度。在進(jìn)行變壓器保護(hù)時(shí)要注意勵(lì)磁涌流的影響,通常會(huì)采用廣義瞬時(shí)功率保護(hù)原理來輔助差動(dòng)保護(hù)。這兩點(diǎn)都是易于實(shí)現(xiàn)的主保護(hù)原理。廣域后備保護(hù)系統(tǒng)由于其具有智能決策功能,可以在進(jìn)行后背保護(hù)在線整定時(shí)集中全網(wǎng)信息,利用最少的通信量最快的數(shù)據(jù)更新速度完成決策工作。智能變電站二次系統(tǒng)在進(jìn)行保護(hù)時(shí)簡化了原來的布線,將主保護(hù)功能由原集控室下放到設(shè)備單元內(nèi),使通信網(wǎng)絡(luò)的負(fù)擔(dān)減輕。并利用集中式母線保護(hù)和具有主站的分布式差動(dòng)來實(shí)現(xiàn)母線主保護(hù)。

      1.2通信配置

      在通信配置這一方面,智能變電站與傳統(tǒng)變電站的差別不大,但是就其發(fā)展而言,數(shù)據(jù)的更快速的傳播與數(shù)據(jù)量的加大會(huì)對通信配置提出更加安全可靠的要求。1.3計(jì)量配置采用三態(tài)數(shù)據(jù)為預(yù)處理數(shù)據(jù)的計(jì)量模塊,進(jìn)行誤差量溯源實(shí)現(xiàn)現(xiàn)場檢驗(yàn)和遠(yuǎn)程檢驗(yàn)。根據(jù)計(jì)量模塊所具有的通信優(yōu)勢,促進(jìn)變電站與大用戶之間的互動(dòng),進(jìn)行信息采集與資源的優(yōu)化配置,促進(jìn)各個(gè)智能化電網(wǎng)環(huán)節(jié)的協(xié)調(diào)運(yùn)行。

      2智能變電站二次系統(tǒng)設(shè)計(jì)方案及應(yīng)用

      2.1系統(tǒng)構(gòu)成過程層、間隔層、站控層是變電站二次系統(tǒng)在功能邏輯方面的劃分。其中站控層對間隔層以及過程層起到一個(gè)全面監(jiān)測與管理的作用。其主要構(gòu)成是操作員站、主機(jī)、保護(hù)故障信息子站、遠(yuǎn)動(dòng)通信裝置、功能站。間隔層具有獨(dú)立運(yùn)作的能力,能夠在沒有網(wǎng)絡(luò)的狀態(tài)下或是站控層失效的狀態(tài)下獨(dú)立完成監(jiān)控,由測量、保護(hù)、錄波、相量測量等組成。過程層主要進(jìn)行采集電氣量、監(jiān)測設(shè)備運(yùn)行狀態(tài)以及執(zhí)行控制命令的工作,由合并單元、互感器、智能終端構(gòu)成。

      2.2網(wǎng)絡(luò)結(jié)構(gòu)

      過程網(wǎng)絡(luò)的組網(wǎng)標(biāo)準(zhǔn)是電壓等級。主要的網(wǎng)絡(luò)形式有雙星形、單星形、點(diǎn)對點(diǎn)等。通常要依據(jù)不同電壓等級和電氣一次主接線配置不同的網(wǎng)絡(luò)形式。單套配置的保護(hù)及安全自動(dòng)裝置、測控裝置要采用相互獨(dú)立的數(shù)據(jù)接口控制器同時(shí)接入兩套不同的過程層網(wǎng)絡(luò)。雙重化配置的保護(hù)及安全自動(dòng)裝置應(yīng)分別接入不同的過程層網(wǎng)絡(luò)。單星形以太網(wǎng)絡(luò)適合用于110KV變電站站控層、間隔層網(wǎng)絡(luò)。雙重化星形以太網(wǎng)絡(luò)適合用于220KV及以上變電站站控層、間隔層網(wǎng)絡(luò)??紤]到變電站網(wǎng)絡(luò)安全方面以及運(yùn)行維護(hù)。智能變電站,特別是高電壓等級、聯(lián)網(wǎng)運(yùn)行的變電站,在兼顧網(wǎng)絡(luò)跳閘方式的同時(shí)仍保留直采直跳的方式。

      2.3二次系統(tǒng)網(wǎng)絡(luò)設(shè)計(jì)原則

      本文以220KV變電站為例,分析站控層設(shè)備的配置。遠(yuǎn)動(dòng)通信裝置與主機(jī)均采用雙套配置,無人值班變電站主機(jī)可兼操作員工作站和工程師站。保護(hù)及故障信息子站與變電站系統(tǒng)共享信息采集,無需獨(dú)立配置。

      1)網(wǎng)絡(luò)通信設(shè)備配置需按一定原則進(jìn)行。特別是交換機(jī)的端口數(shù)量一定要符合工程規(guī)模需求,端口規(guī)格在100M~1000M范圍內(nèi)。兩臺(tái)智能電子設(shè)備所接的數(shù)據(jù)傳輸路由要控制在4個(gè)交換機(jī)以內(nèi)。每臺(tái)交換機(jī)的光纖接入量要控制在16對以內(nèi)。由于網(wǎng)絡(luò)式數(shù)據(jù)連接中交換機(jī)起到重要的作用,為保證智能變電站的安全運(yùn)行,交換機(jī)必須保證安全穩(wěn)定,避免故障的發(fā)生。

      2)應(yīng)對獨(dú)立配置的隔層設(shè)備測控裝置進(jìn)行單套配置,采用保護(hù)測控一體化裝置對110KV及以下電壓等級進(jìn)行配置,采用保護(hù)測控一體化裝置對繼電保護(hù)就地安裝的220KV電壓等級進(jìn)行配置。繼電保護(hù)裝置的配置原則與常規(guī)變電站一致,220KV變電站故障錄波及網(wǎng)絡(luò)分析記錄裝置按照電壓等級分別配置,統(tǒng)一配置110KV及以下變電站,單獨(dú)配置主變壓器。

      3)過程層的配置。對于110KV及以上主變壓器本體配置單套的智能終端,對于采用開關(guān)柜布置的66KV及以下配電裝置無需配置智能終端。在配電裝置場地智能組件柜中分散布置智能終端。

      4)合并單元的配置。110KV及以下電壓等級各間隔單套配置,雙重化保護(hù)的主變各側(cè)冗余配置,同一間隔內(nèi)電壓互感器和電流互感器合用一個(gè)合并單元。

      3結(jié)束語

      綜上所述,智能變電站的發(fā)展、變革以及建設(shè)是實(shí)現(xiàn)電網(wǎng)發(fā)展完善的基礎(chǔ)。智能變電站二次系統(tǒng)設(shè)計(jì)方法的不斷發(fā)展優(yōu)化會(huì)促進(jìn)智能變電站作用及優(yōu)勢的更好的發(fā)揮。針對我國智能化變電站二次系統(tǒng)設(shè)計(jì)的實(shí)踐經(jīng)驗(yàn)及相關(guān)原則,其應(yīng)用發(fā)展道路一定會(huì)更廣闊。

      下載變電站電氣二次系統(tǒng)驗(yàn)收規(guī)范(小編整理)word格式文檔
      下載變電站電氣二次系統(tǒng)驗(yàn)收規(guī)范(小編整理).doc
      將本文檔下載到自己電腦,方便修改和收藏,請勿使用迅雷等下載。
      點(diǎn)此處下載文檔

      文檔為doc格式


      聲明:本文內(nèi)容由互聯(lián)網(wǎng)用戶自發(fā)貢獻(xiàn)自行上傳,本網(wǎng)站不擁有所有權(quán),未作人工編輯處理,也不承擔(dān)相關(guān)法律責(zé)任。如果您發(fā)現(xiàn)有涉嫌版權(quán)的內(nèi)容,歡迎發(fā)送郵件至:645879355@qq.com 進(jìn)行舉報(bào),并提供相關(guān)證據(jù),工作人員會(huì)在5個(gè)工作日內(nèi)聯(lián)系你,一經(jīng)查實(shí),本站將立刻刪除涉嫌侵權(quán)內(nèi)容。

      相關(guān)范文推薦

        變電站二次安防系統(tǒng)實(shí)施方案(5篇)

        變電站二次安防系統(tǒng)實(shí)施方案 本方案為了加強(qiáng)變電站二次系統(tǒng)安全防護(hù),確保電力監(jiān)控系統(tǒng)及電力調(diào)度數(shù)據(jù)網(wǎng)絡(luò)的安全,主要依據(jù)國家電力監(jiān)管委員會(huì)第5號(hào)令《電力二次系統(tǒng)安全防護(hù)規(guī)......

        110kV變電站電氣一次系統(tǒng)設(shè)計(jì)研究(大全)

        110kV變電站電氣一次系統(tǒng)設(shè)計(jì)研究 云南欣博工程咨詢有限公司 云南昆明 650051 摘要:我國電力工業(yè)的電力水平和技術(shù)水平都在不斷的提高,已經(jīng)有許多變電站實(shí)現(xiàn)了集中控制和采......

        《建筑電氣工程施工質(zhì)量驗(yàn)收規(guī)范》

        強(qiáng)制性條文、條文說明及實(shí)施要點(diǎn)《建筑電氣工程施工質(zhì)量驗(yàn)收規(guī)范》(GB50303-2015)強(qiáng)制性條文13.1.5高壓的電氣設(shè)備和布線系統(tǒng)及繼電保護(hù)系統(tǒng)必須交接試驗(yàn)合格。【條文說明】本......

        建筑電氣驗(yàn)收規(guī)范[五篇范例]

        建筑電氣驗(yàn)收規(guī)范3.2.1主要設(shè)備、材料、成品和半成品進(jìn)場檢驗(yàn)結(jié)論應(yīng)有記錄,確認(rèn)符合本規(guī)范規(guī)定,才能在施工中應(yīng)用。3.2.2因有異議送有資質(zhì)試驗(yàn)室進(jìn)行抽樣檢測,試驗(yàn)室應(yīng)出具檢測......

        消火栓系統(tǒng)設(shè)計(jì)及驗(yàn)收規(guī)范

        管道設(shè)計(jì)及選用 8.2.1 消防給水系統(tǒng)供水管道所采用的消防設(shè)施、管材和管件的工作壓力不應(yīng)小于消防給水系統(tǒng)的工作壓力。 8.2.2 消防給水系統(tǒng)管網(wǎng)的工作壓力應(yīng)符合下列規(guī)......

        變電站自動(dòng)化系統(tǒng)標(biāo)準(zhǔn)化驗(yàn)收作業(yè)指導(dǎo)書(精)

        編號(hào):Q/ 孔目江500kV 變電站自動(dòng)化設(shè)備竣工驗(yàn)收標(biāo)準(zhǔn)化作業(yè)指導(dǎo)書 編寫: 年 月 日 審核: 年 月 日 批準(zhǔn): 年 月 日 作業(yè)負(fù)責(zé)人: 作業(yè)日期:20 年 月 日 時(shí)至20 年 月 日 時(shí) 國網(wǎng)江西......

        110kV變電站電氣一次系統(tǒng)設(shè)計(jì)文獻(xiàn)綜述大全

        110kV變電站電氣一次系統(tǒng)設(shè)計(jì)文獻(xiàn)綜述 一、引言 隨著國民經(jīng)濟(jì)的發(fā)展和人民生活水平的提高,用戶對供電質(zhì)量的要求日益提高。國家提出了加快城網(wǎng)和農(nóng)網(wǎng)建設(shè)及改造、拉動(dòng)內(nèi)需的......

        《電氣火災(zāi)監(jiān)控系統(tǒng)設(shè)計(jì)、安裝及驗(yàn)收規(guī)范》(征求意見稿)編制說明

        廣西區(qū)地方標(biāo)準(zhǔn) 電氣火災(zāi)監(jiān)控系統(tǒng)設(shè)計(jì)、安裝及驗(yàn)收規(guī)范 送審稿 編制說明 二〇一二年二月二十日 《電氣火災(zāi)監(jiān)控系統(tǒng)設(shè)計(jì)、安裝及驗(yàn)收規(guī)范》 編制說明 一、 規(guī)范的提出 隨著......